• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Unsa ang mga kasagaran nga pagkamalas sa 35kV ka mataas nga kuryente nga circuit breaker?

Felix Spark
Larangan: Pagkabag-o ug Pagpangutana
China

High-Voltage Circuit Breakers: Common Faults and Solutions for 35kV Systems

Ang mga high-voltage circuit breakers mao ang importante nga electrical equipment sa mga power substations. Ang komprehensibong pag-ila sa ilang fault patterns ug root causes mahimong makapahimo og targeted troubleshooting, rapid power restoration, ug effective reduction sa losses gikan sa outages ug equipment damage.

I. Common Operational Faults of 35kV High-Voltage Circuit Breakers

1. Failure to Store Energy (Charging Failure)

Ang energy storage mao ang pundasyon sa operasyon sa circuit breaker. Kon ang breaker dili makapag-store og sufficient kinetic energy, mahimong dili makapahimong normal nga opening o closing operations. Ang common cause mao ang malfunctioning limit switches, nga mahimong makapahimong continuous nga pag-operate sa energy storage motor. Sa normal nga kondisyon, ang motor mag-stop automatic nga kon matapos na ang mechanical travel. Kon ang limit switch dili makadetect sa end position, ang motor magpadayon sa pag-operate, nagresulta sa energy waste ug potential damage sa motor o storage mechanism.

VCB.jpg

2. Mechanical Failures Preventing Closing

Ang mechanical faults mahimong mapasabot sa pag-prevent sa opening ug closing operations, resulta sa local manual tripping failure. Kon gi gamit ang remote control commands, ang fault sa control circuit o relay protection system mahimong mapasabot sa unsuccessful closing. Ang open circuits sa trip coil o trip control circuit mahimong makapahimong failure to close. Importante ang stable voltage supply sa operasyon; kon ang supply voltage mobaba, ang coil resistance mobata, mobaba ang tripping capability. Ang mechanical sticking o jamming sa trip process mahimong makaapekto sa closing operation, severely compromising the breaker’s functionality.

3. Closing Coil Burnout

Ang mga faults sa spring-operated mechanisms mahimong makapahimong reduce sa energy storage efficiency. Kon ang spring mobato, ang energy storage circuit dili makapag-charge fully, causing the motor to remain in continuous operation, potentially leading to motor coil overheating and burnout. Ang common cause sa closing coil burnout mao ang improper positioning sa limit switch—installed too low—causing the motor to start before the spring is fully charged. This results in excessive current draw and elevated coil temperature. Even after the switch contacts change state and cut off power, the spring may lack sufficient energy to complete the trip operation. Prolonged motor operation under these conditions can also damage the limit switch. Such faults prevent normal opening/closing operations and increase the risk of internal component damage.

II. Solutions for 35kV High-Voltage Circuit Breaker Faults

1. Monitor Energy Storage Motor Operation

Kon ang critical role sa storage motor, ang maintenance personnel kinahanglan regular nga inspeksyon sa iyang operasyon. Ang improper limit switch positioning mahimong mapasabot sa motor dili makapause correctly. Ang switch kinahanglan i-install aron masiguro ang timely motor shutdown once full energy storage is achieved, providing reliable and orderly kinetic energy supply.

2. Inspect Trip Coils Regularly

Ang maintenance staff kinahanglan conduct timely and effective inspections of trip coils to identify potential faults and hidden risks, preventing incident escalation. Key inspection points include:

  • Checking for open circuits in the trip coil (replace if damaged)

  • Verifying continuity in the trip control circuit

  • Inspecting the trip plunger for deformation

  • Ensuring the breaker can operate freely

An open circuit in the control loop prevents sufficient current flow, impairing breaker performance. Regular checks ensure safe and reliable operation.

VCB.jpg

3. Strengthen Circuit Breaker Maintenance

Enhance training for maintenance personnel on technical knowledge and fault analysis. Organize case studies to identify gaps, improve response capabilities, and build expertise in accident prevention and emergency handling. Learn from past incidents to avoid recurring human errors.

Strictly manage high-voltage switchgear. After a fault trip, never force-energize without identifying the root cause, as this risks personnel safety and may expand the incident. Isolate switchgear that tripped under abnormal conditions, conduct thorough inspections, tests, and adjustments, and only return to service after confirming complete safety.

Standardize substation operating procedures, detailing every step to ensure operational uniqueness, enhancing both personnel safety and equipment integrity.

VCB.jpg

4. Resolve Circuit Breaker Failure to Close (Refusal to Close)

To address refusal to close:

  • Insert a normally closed (NC) auxiliary contact of the high-voltage circuit breaker into the LD signal lamp circuit. After closing, no current flows through the TBJ voltage coil, eliminating holding voltage. After tripping, this setup both monitors the closing circuit integrity and indicates the open status.

  • Alternatively, relocate the LD wiring so that after TBJ operates, the LD disconnects from the voltage coil. However, this modification may be complex in some breaker mechanisms.

  • If no spare NC contact is available, connect an auxiliary resistor (R) in parallel with the TBJ voltage coil to limit its voltage to ≤30% of rated voltage, preventing unintended operation.

5. Adjust Limit Switch Position

Incorrect limit switch positioning (too high or too low) can cause faults. If energy storage is incomplete, excessive current and voltage may flow, leading to circuit failures. Maintenance personnel must promptly adjust the switch position to prevent incident escalation. Proper adjustment ensures the motor stops precisely when charging is complete. During switching operations, rely on the energy storage indicator light to confirm readiness. Only when free opening/closing is verified can the breaker be considered in good condition. Correct limit switch positioning is fundamental to reliable 35kV breaker operation and accident prevention.

Conclusion

Electricity is a vital energy source for national economic development. Ensuring high-quality power supply and grid stability is paramount. High-voltage circuit breakers are essential for protecting and controlling the safe operation of power systems. Their reliable performance is crucial to overall grid stability. Therefore, substation maintenance personnel must fully understand the operational status, fault patterns, and root causes of high-voltage circuit breakers, and be capable of implementing effective corrective actions. Timely fault resolution ensures grid safety and delivers high-quality, efficient power to users.

Maghatag og tip ug pagsalig sa author

Gipareserbado

126 (145) kV Vacuum Circuit Breaker Installation & Adjustment Guide Pamantayan sa Pag-install ug Pagsulay sa 126 (145) kV Vacuum Circuit Breaker
Ang mga high-voltage vacuum circuit breakers, tungod sa ilang excellent na mga katangian sa pagpuno sa arc, kahimtang para sa regular nga pag-operate, ug long maintenance-free intervals, gipagtubag sila sa China’s power industry—espesyalmente sa urban ug rural power grid upgrades, ug sa chemical, metallurgical, railway electrification, ug mining sectors—ug nakuha sila og widespread acclaim gikan sa mga users.Ang primary advantage sa vacuum circuit breakers nahimutang sa vacuum interrupter. Apan,
11/20/2025
Anormal nga Operasyon ug Paghahandle sa High-Voltage Circuit Breakers ug Disconnectors
Mga Karaniwang Pagsabog sa Mataas na Boltagen Circuit Breakers ug Pagkawala sa Pressure sa MechanismMga karaniwang pagsabog sa mga mataas na boltagen circuit breakers mismo kinahanglan ipasabot: pagkawala sa pagpahimutang, pagkawala sa pagbukas, kasuko nga pagpahimutang, kasuko nga pagbukas, asynchronism sa tatlo ka phase (mga contact dili magpahimutang o magbukas nang samay), pagkasira sa operating mechanism o pagkawala sa pressure, pagpugos o explosion tungod sa dili sapat nga interrupting cap
11/14/2025
Hydraulic Leak & SF6 Gas Leakage sa mga Circuit Breakers
Pagdakop sa mga Hydraulic Operating MechanismsAlang sa mga hydraulic mechanisms, ang pagdakop mahimong mogahin og short-term nga dako nga pagsugod sa pump o kauban nga dako nga panahon sa represurization. Ang dako nga internal nga pagdakop sa langis sa mga valve mahimong magresulta og pressure loss failure. Kon ang hydraulic oil mosulob sa nitrogen side sa accumulator cylinder, mahimong mag-uli og abnormal nga pagtaas sa presyon, sumala kini maapektuhan ang safe operation sa SF6 circuit breakers
10/25/2025
10kV RMU Common Faults & Solutions Guide Gidagway sa mga Karaniwang Sayop ug Solusyon alang sa 10kV RMU
Mga Isyu sa Pag-apply ug mga Pamaagi sa Pag-handle para sa 10kV Ring Main Units (RMUs)Ang 10kV ring main unit (RMU) usa ka kasagaran nga pananglitan sa elektrikal nga distribusyon sa urban nga mga network sa kuryente, gamiton sa paghatag ug distribusyon sa medium-voltage nga kuryente. Sa aktwal nga operasyon, mahimong madungog ang uban pang mga isyu. Ania ang mga kasagaran nga problema ug ang naka-corresponding nga mga pamaagi sa pag-handle.I. Mga Electrical Faults Internal Short Circuit o Pobre
10/20/2025
Inquiry
+86
I-klik aron i-upload ang file
Pangutana
Pangutana sa IEE-Business Application
Pangita og mga equipment gamit ang IEE-Business app asa asa ug kailan man sugad og pagkuha og solusyon pagsulay sa mga eksperto ug pagpadayon sa industriya nga pakisayran suportahan ang imong proyekto sa kuryente ug negosyo