What is Transmission Tower Foundation?

Encyclopedia
Encyclopedia
Field: Encyclopedia
0
China


What is Transmission Tower Foundation?


Transmission Tower Foundation Definition


A transmission tower foundation is defined as the base that supports the tower and transfers loads to the ground.

 

583d30402f464d0fe559cf6286f031ed.jpeg


Types of Loads


The foundation of towers are normally subjected to three types of forces. These are:

 


  • The compression or downward thrust.



  • The tension or uplift.



  • The lateral forces of side thrusts in both transverse and longitudinal directions.



  • The magnitude or limit loads for foundations should be taken 10% higher than these for the corresponding towers.

 


The base slab of the foundation should be designed to handle extra forces caused by uneven load distribution.

 


The weight of concrete both above and below ground level, along with any embedded steel, should be considered to add to the down-thrust.

 


6546f68d06f1ce1b5e1e628b18ceeb1c.jpeg

 


Soil Parameters


Soil parameters For designing the foundations, following parameters are required.

 


  • Limit bearing capacity of soil.

  • Density of soil.

  • Angle of earth frustum.

 


The above values are available from soil test report.

 


 

Stability Analysis


Besides strength design, stability analysis must be conducted to prevent failures like overturning, uprooting, sliding, and tilting. Soil resistance is key to counteracting the loads on the foundation.

 


Resistance Against Uplift


The uplift loads shall be assumed to be resisted by the weight of earth in an inverted frustum of a pyramid of earth whose sides make an angle equal to the angle of report of the earth with the vertical in average soil. The volume of earth computation shall be as per enclosed drawing (Fig.3) The weight of concrete embedded in earth and that above the ground level shall also be considered for resisting the uplift. In case where the frustum of earth pyramid of two adjoining legs overlaps each other, the earth frustum shall be assumed truncated by a vertical plane passing through the center line of the tower base. Over load factor (OLF) of 10% (Ten percent) shall be considered over the design load i.e. OLF = 1.10 for suspension tower and 1.15 for angle including dead end and anchor tower. However, for special tower OLF shall be 1.20.

 


Resistance Against Down Thrust of Transmission Tower Foundation


The following load combinations shall be resisted by the bearing strength of the soil:

 


  • The down thrust loads combined with an additional weight of concrete above earth are assumed to be acting on the total area of the bottom of the footing.The moment due to side thrust forces at the bottom of the footing.


  • The structural design of the base slab shall be developed for the above load combination. In case of toe (τ) pressure calculation due to above load combination allowable bearing pressure to be increased by 25%.

 


Resistance Against Side Thrust of Transmission Tower Foundation


The chimney shall be designed as per limit state method for the combined action of axial forces, tension and compression and the associated maximum bending moment. In these calculations, the tensile strength of concrete shall be ignored.

 


Resistance Against Uprooting of Stub of Transmission Tower Foundation


OLF of 10% (Ten percent) shall be considered i.e. OLF = 1.10 for normal suspension towers and 1.15 for angle tower including Dead end/anchor tower. For special towers OLF shall be 1.20.

  


Give a tip and encourage the author!
Recommended
MVDC: Future of Efficient, Sustainable Power Grids
MVDC: Future of Efficient, Sustainable Power Grids
The Global Energy Landscape Is Undergoing a Fundamental Transformation toward a "fully electrified society," characterized by widespread carbon-neutral energy and the electrification of industry, transportation, and residential loads.In today’s context of high copper prices, critical mineral conflicts, and congested AC power grids, Medium-Voltage Direct Current (MVDC) systems can overcome many limitations of traditional AC networks. MVDC significantly enhances transmission capacity and efficienc
Edwiin
10/21/2025
Grounding Causes of Cable Lines and the Principles of Incident Handling
Grounding Causes of Cable Lines and the Principles of Incident Handling
Our 220 kV substation is located far from the urban center in a remote area, surrounded primarily by industrial zones such as Lanshan, Hebin, and Tasha Industrial Parks. Major high-load consumers in these zones—including silicon carbide, ferroalloy, and calcium carbide plants—account for approximately 83.87% of our bureau’s total load. The substation operates at voltage levels of 220 kV, 110 kV, and 35 kV.The 35 kV low-voltage side mainly supplies feeders to ferroalloy and silicon carbide plants
Felix Spark
10/21/2025
Overhead Power Lines & Towers: Types, Design & Safety
Overhead Power Lines & Towers: Types, Design & Safety
Besides ultra-high voltage AC substations, what we encounter more frequently are power transmission and distribution lines. Tall towers carry conductors that leap across mountains and seas, stretching into the distance before reaching cities and villages. This is also an interesting topic—today, let's explore transmission lines and their supporting towers.Power Transmission and DistributionFirst, let’s understand how electricity is delivered. The electric power industry primarily consists of fou
Encyclopedia
10/21/2025
Automatic Reclosing Modes: Single, Three-Phase & Composite
Automatic Reclosing Modes: Single, Three-Phase & Composite
General Overview of Automatic Reclosing ModesTypically, automatic reclosing devices are categorized into four modes: single-phase reclosing, three-phase reclosing, composite reclosing, and disabled reclosing. The appropriate mode can be selected based on load requirements and system conditions.1. Single-Phase ReclosingMost 110kV and higher transmission lines employ three-phase single-shot reclosing. According to operational experience, over 70% of short-circuit faults in high-voltage overhead li
Edwiin
10/21/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.