• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


What are the requirements for inspecting and maintaining a transformer's no-load tap changer?

Leon
Leon
Field: Fault Diagnosis
China
  1. The tap changer operating handle shall be equipped with a protective cover. The flange at the handle shall be well sealed with no oil leakage. Locking screws shall securely fasten both the handle and the drive mechanism, and the handle rotation shall be smooth without binding. The position indicator on the handle shall be clear, accurate, and consistent with the tap voltage regulation range of the winding. Limit stops shall be provided at both extreme positions.

  2. The insulating cylinder of the tap changer shall be intact and undamaged, with good insulation properties, and its support bracket shall be firmly secured. The allowable exposure time of the tap changer to air shall be the same as that of the core assembly. If the tap changer is disassembled during maintenance and cannot be reinstalled promptly, it shall be immersed in qualified transformer oil.

  3. All tap changer insulation shall be in good condition, securely bound, neatly arranged, and all joints shall be well soldered with no signs of desoldering or overheating.

  4. The surfaces of all fixed contact posts and moving contact rings shall be smooth, free of oil deposits, oxidation films, or burn marks. The silver-plated layer on the contact surfaces shall show no signs of peeling.

  5. Rotate the tap changer through all tap positions to inspect the contact condition between each moving contact ring and moving contact post, as well as the spring condition. Check the contact pressure—when tested with a feeler gauge, it should not be possible to insert the gauge between the contact surfaces. The contact resistance between any two fixed contact posts shall not exceed 500 μΩ. After inspection, the tap changer shall be returned to its original operating position.

  6. If the tap changer is removed during maintenance, clear markings and records must be made. After reinstallation, the voltage ratio shall be measured and verified.

  7. As part of preventive maintenance, the tap changer shall be rotated annually: move it 10–15 times back and forth from its operating position to remove oil sludge, oxidation films, or other deposits from the contact surfaces through friction. Then return it to the operating position and measure the DC resistance, which must be acceptable (i.e., not higher than the previous measurement result).

Give a tip and encourage the author!
Recommended
How to Identify Internal Faults in a Transformer?
How to Identify Internal Faults in a Transformer?
Measure DC resistance: Use a bridge to measure the DC resistance of each high- and low-voltage winding. Check whether the resistance values among phases are balanced and consistent with the manufacturer’s original data. If phase resistance cannot be measured directly, line resistance may be measured instead. The DC resistance values can indicate whether the windings are intact, whether there are short circuits or open circuits, and whether the contact resistance of the tap changer is normal. If
Felix Spark
11/04/2025
How to Overhaul a Transformer Conservator (Oil Pillow)?
How to Overhaul a Transformer Conservator (Oil Pillow)?
Overhaul Items for Transformer Conservator:1. Ordinary-Type Conservator Remove the end covers on both sides of the conservator, clean rust and oil deposits from inner and outer surfaces, then apply insulating varnish to the inner wall and paint to the outer wall; Clean components such as the dirt collector, oil level gauge, and oil plug; Check that the connecting pipe between the explosion-proof device and the conservator is unobstructed; Replace all sealing gaskets to ensure good sealing with n
Felix Spark
11/04/2025
Why is it difficult to increase the voltage level?
Why is it difficult to increase the voltage level?
The solid-state transformer (SST), also known as a power electronic transformer (PET), uses voltage level as a key indicator of its technological maturity and application scenarios. Currently, SSTs have reached voltage levels of 10 kV and 35 kV on the medium-voltage distribution side, while on the high-voltage transmission side, they remain in the stage of laboratory research and prototype validation. The table below clearly illustrates the current status of voltage levels across different appli
Echo
11/03/2025
Standards and Calculation of LTAC Test for Power Transformers
Standards and Calculation of LTAC Test for Power Transformers
1 IntroductionAccording to the provisions of the national standard GB/T 1094.3-2017, the primary purpose of the line terminal AC withstand voltage test (LTAC) for power transformers is to evaluate the AC dielectric strength from the high-voltage winding terminals to ground. It does not serve to assess inter-turn insulation or phase-to-phase insulation.Compared with other insulation tests (such as full lightning impulse LI or switching impulse SI), the LTAC test imposes a relatively more stringen
Oliver Watts
11/03/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.