Paano Pagkuha sa Kasinatian sa Short Circuit Current sa Circuit Breaker

Electrical4u
Larangan: Basic Electrical Basikong Elektikal
0
China

Pakakalkula ang Short Circuit Current

Kung adunay short circuit fault sa electrical system, usa ka dako nga short circuit current mihuyom sa system kasagaran ang circuit breaker (CB) contacts, hangtud ma-trip ang CB aron malikayan ang fault. Kung ang short circuit current mihuyom sa CB, ang uban pang current carrying parts sa circuit breaker mahimong magpadanyog sa dako nga mechanical ug thermal stresses.

Kon ang conducting parts sa CB wala naka sufficient cross-sectional area, mahimong adunay chance og dangerously high temperature rise. Kini nga taas na temperatura mahimong makaapekto sa insulation quality sa CB.

Ang CB contacts usab molihok sa taas na temperatura. Ang thermal stresses sa CB contacts proportional sa I2Rt, diin ang R mao ang contact resistance, depende sa contact pressure ug contact surface condition. Ang I mao ang rms value sa short circuit current ug t mao ang duration para asa ang short circuit current mihuyom sa contacts.

Human sa pag-initi sa fault, ang short circuit current mobaba hangtud ma-break sa interrupting unit sa CB. Busa, ang panahon t mao ang breaking time sa circuit breaker. Tungod kay kini nga panahon labi ka gamay sa scale sa mili second, gi-assume nga tanang heat nga giproduce sa fault gi-absorb sa conductor tungod kay wala gyud kaayo nga panahon alang sa convention ug radiation sa heat.
Ang temperature rise makakita sa sumusunod nga formula,

Diin, T mao ang temperature rise per second sa degree centigrade.
I mao ang
current (rms symmetrical) sa Ampere.
A mao ang cross-sectional area sa conductor.
ε mao ang temperature coefficient sa
resistivity sa conductor sa 20oC.

Gisultian nato, ang aluminum sa taas sa 160oC mawala sa iyang mechanical strength ug mabago og soft, gitumong limitahan ang temperature rise sa duol niining temperatura. Kini nga requirement gihatagan sa permissible temperature rise sa short circuit. Kini nga limit makamao pinaagi sa pag-control sa CB breaking time ug proper designing sa conductor dimension.

Short Circuit Force

Ang electromagnetic force nga naka-develop sa duha ka parallel electric current carrying conductors, gihatagan sa formula,

Diin, L mao ang length sa duha ka conductors sa inch.
S mao ang distance sa ilaha sa inch.
I mao ang current carried sa bawat
conductors.

Gisultian sa eksperimento, ang electromagnetic short circuit force maximum kon ang value sa short circuit current I, 1.75 times ang initial rms value sa symmetrical short circuit current wave.

Subalit, sa uban pang circumstances posible nga ang forces greater than these may develop, sama sa instance sa very rigid bars o tungod sa resonance sa case sa bars liable sa mechanical vibration. Gisultian usab nga ang reactions produced sa non resonating structure sa alternating current sa instant of application o removal sa forces may exceed ang reactions experienced while the current is flowing.

Busa advisable nga error sa side sa safety ug allow for all contingencies, para asa dapat intawn ang maximum force nga could be developed sa initial peak value sa asymmetrical short circuit current. Kini nga force may be taken as having a value which is twice of that calculated from the above formula.

Ang formula strictly useful sa circular cross-sectional conductor. Although L mao ang finite length sa portions sa conductors run parallel to each other, pero ang formula only suitable where the total length of each conductor is assumed as infinite.

Sa practical cases ang total length sa conductor wala infinite. Gitumong dinhi, ang flux density near the ends sa current carrying conductor considerably different than its middle portion.

Bisan unsa, kon atong gamiton ang above formula para sa short conductor, ang force calculated would be much higher than actual.

Gitumong, ang error may be eliminated considerably kon atong gamiton ang term,

stead of L/S in the above formula.
The formula then becomes,

The formula, represented by equation (2), gives error free result when the ratio L/S is greater than 20. When 20 > L/S > 4, formula (3) is suitable for error free result.
If L/S < 4, formula (2) is suitable for error free result. The above formulas are only applicable for circular cross-sectional conductors. But for rectangular cross-sectional conductor, the formula needs to have some correction factor. Say this factor is K. Hence, the above formula ultimately becomes,

Although the effect of shape of cross-section of conductor reduces rapidly if spacing between the conductor increases the value of K is maximum for strip like conductor whose thickness is quite less than its width. K is negligible when shape of cross-section of conductor is perfectly square. K is unity for perfectly circular cross-sectional conductor. This holds true for both standard and remote control circuit breaker.

Statement: Respetar el original, los buenos artículos merecen ser compartidos, si hay infracción por favor contactar para eliminar.

Maghatag og tip ug pagsalig sa author

Gipareserbado

Pangunahon nga Transformer Accidents ug Light Gas Operation Issues
1. Talaan sa Pagkamalasakit (Marso 19, 2019)Sa 16:13 sa Marso 19, 2019, ang background monitoring nagreport og light gas action sa No. 3 main transformer. Sumala sa Code for Operation of Power Transformers (DL/T572-2010), ang mga tawo sa operation and maintenance (O&M) nagsagol sa kondisyon sa No. 3 main transformer sa dapit.Konfirmasyon sa dapit: Ang WBH non-electrical protection panel sa No. 3 main transformer nagreport og Phase B light gas action sa transformer body, ug ang reset wala mae
02/05/2026
Mga Sayop ug Paghunahuna Sa Pag-atas Sa Iisa Ka Fasa Sa 10kV Distribution Lines
Mga Kinaiya ug mga Kaugalingong Detektor sa Single-Phase Ground Fault1. Mga Kinaiya sa Single-Phase Ground FaultMga Signal sa Central Alarm:Nagring ang warning bell, ug naglitaw ang indicator lamp nga gilabel “Ground Fault on [X] kV Bus Section [Y]”. Sa mga sistema nga may Petersen coil (arc suppression coil) nga naka-ground sa neutral point, ang “Petersen Coil Operated” nga indicator usab motindog.Mga Indikasyon sa Insulation Monitoring Voltmeter:Ang voltage sa nahisalaan nga phase mokubos (kon
01/30/2026
Neutral nga punto sa grounding operation mode alang sa 110kV~220kV power grid transformers
Ang pag-arrange sa mga modo ng operasyon ng grounding ng neutral point para sa 110kV~220kV power grid transformers dapat matugunan ang mga requirement ng insulation withstand sa mga neutral points ng transformer, ug usahay mao usab ang pagpanalipod sa zero-sequence impedance sa mga substation nga walay dako nga kausaban, samtang sigurado nga ang zero-sequence comprehensive impedance sa anumang punto sa short-circuit sa sistema dili mogawas sa tulo ka beses sa positive-sequence comprehensive impe
01/29/2026
Unsa ang Katuyohan sa Paggamit og Bato Gravel Pebbles ug Crushed Rock sa mga Substation?
Asa Kini ang mga Substation Usa ka Bato, Gravel, Pebbles, ug Crushed Rock?Sa mga substation, ang mga equipment sama sa power ug distribution transformers, transmission lines, voltage transformers, current transformers, ug disconnect switches nimo kinahanglan og grounding. Padulong sa grounding, karon atong ibutangan ang kahibawo bahin kon asa kini nga gravel ug crushed stone gamiton sa mga substation. Bisag ordinaryohan ra sila, importante kaayo ang papel nila sa seguridad ug pagkabana-bana.Sa d
01/29/2026
Inquiry
+86
I-klik aron i-upload ang file
Pangutana
Pangutana sa IEE-Business Application
Pangita og mga equipment gamit ang IEE-Business app asa asa ug kailan man sugad og pagkuha og solusyon pagsulay sa mga eksperto ug pagpadayon sa industriya nga pakisayran suportahan ang imong proyekto sa kuryente ug negosyo