Current Limiting Reactor

Edwiin
Edwiin
Field: Power switch
China

Current Limiting Reactor

A current limiting reactor is an inductive coil characterized by a significantly higher inductive reactance compared to its resistance, designed to restrict short-circuit currents during fault conditions. These reactors also mitigate voltage disturbances in the remainder of the power system. They are installed in feeders, tie lines, generator leads, and between bus sections to reduce the magnitude of short-circuit currents and alleviate associated voltage fluctuations.

Under normal operating conditions, current reactors allow unimpeded power flow. However, during a fault, the reactor restricts disturbances to the faulty section. Since the system's resistance is negligible compared to its reactance, the reactor's presence has minimal impact on overall system efficiency.

Main Function of Current Limiting Reactor

The primary objective of a current limiting reactor is to maintain its reactance when large short-circuit currents flow through its windings. When fault currents exceed approximately three times the rated full-load current, iron-cored reactors with large cross-sectional areas are used to limit fault currents. However, their high cost and weight due to bulky iron cores make air-cored reactors the preferred choice for short-circuit current limitation in most applications.

  • Iron-Cored Reactors: Prone to hysteresis and eddy current losses, leading to higher power consumption.

  • Air-Cored Reactors: Exhibit total losses typically around 5% of their KVA rating, making them more efficient.

Functions of Current Limiting Reactor

  • Fault Current Protection: Reduces short-circuit current flow to safeguard equipment from mechanical stress and overheating.

  • Voltage Disturbance Mitigation: Dampens voltage fluctuations caused by short circuits.

  • Fault Isolation: Restricts fault currents to the affected section, preventing spread to healthy feeders and maintaining supply continuity.

Drawbacks of Current Limiting Reactor

  • Increases the total percentage reactance of the circuit when integrated into the network.

  • Degrades power factor and exacerbates voltage regulation issues.

Location of Reactors in Power Systems

Reactors are strategically placed in series with generators, feeders, or bus bars to limit short-circuit currents:

  • Generator Reactors: Installed between generators and generator buses to provide individual machine protection, typically with a reactance of ~0.05 per unit.

    • Drawback: A fault in one feeder can impact the entire system due to shared reactor configuration.

Disadvantages of Such Reactors

The drawbacks of this type of reactor are twofold: it fails to protect generators against short-circuit faults occurring across bus bars, and it causes constant voltage drops and power losses during normal operation.

Bus-Bar Reactors

When reactors are installed in bus bars, they are termed bus-bar reactors. Inserting reactors into bus bars helps avoid constant voltage drops and power losses. Below is an explanation of bus-bar reactors in ring systems and tie systems:

Bus-Bar Reactors (Ring System)

Bus-bar reactors serve to connect separate bus sections, which consist of generators and feeders linked to a common bus bar. In this configuration, each feeder is typically supplied by a single generator. Under normal operation, only a small amount of power flows through the reactors, resulting in low voltage drops and power losses. To minimize voltage drops across them, bus-bar reactors are therefore designed with high ohmic resistance.

When a fault occurs in any feeder, only one generator supplies the fault current, while the current from other generators is limited by the bus-bar reactors. This reduces heavy current and voltage disturbances caused by short circuits on a bus section, confining them to the faulty section alone. The only drawback of this reactor configuration is its inability to protect generators connected to the faulted section.

Bus-Bar Reactors (Tie-Bus System)

This represents a modification of the above system. In a tie-bus configuration, generators are connected to the common bus bar via reactors, with feeders supplied from the generator side.

The system operates similarly to the ring system but offers additional advantages. In this configuration, if the number of sections increases, the fault current will not exceed a specific value, which is determined by the specifications of individual reactors.

Give a tip and encourage the author!
Recommended
PT Fuse Slow Blow: Causes, Detection & Prevention
PT Fuse Slow Blow: Causes, Detection & Prevention
I. Fuse Structure and Root Cause AnalysisSlow Fuse Blowing:From the design principle of fuses, when a large fault current passes through the fuse element, due to the metal effect (certain refractory metals become fusible under specific alloy conditions), the fuse first melts at the soldered tin ball. The arc then rapidly vaporizes the entire fuse element. The resulting arc is quickly extinguished by quartz sand.However, due to harsh operating environments, the fuse element may age under the comb
Edwiin
10/24/2025
Why Fuses Blow: Overload, Short Circuit & Surge Causes
Why Fuses Blow: Overload, Short Circuit & Surge Causes
Common Causes of Fuse BlowingCommon reasons for fuse blowing include voltage fluctuations, short circuits, lightning strikes during storms, and current overloads. These conditions can easily cause the fuse element to melt.A fuse is an electrical device that interrupts the circuit by melting its fusible element due to heat generated when current exceeds a specified value. It operates on the principle that, after an overcurrent persists for a certain period, the heat produced by the current melts
Echo
10/24/2025
Fuse Maintenance & Replacement: Safety and Best Practices
Fuse Maintenance & Replacement: Safety and Best Practices
1. Fuse MaintenanceFuses in service should be regularly inspected. The inspection includes the following items: Load current should be compatible with the rated current of the fuse element. For fuses equipped with a fuse blown indicator, check whether the indicator has actuated. Check the conductors, connection points, and the fuse itself for overheating; ensure connections are tight and making good contact. Inspect the fuse exterior for cracks, contamination, or signs of arcing/discharge. Liste
James
10/24/2025
Maintenance and Repair Items for 10kV High-Voltage Switchgear
Maintenance and Repair Items for 10kV High-Voltage Switchgear
I. Routine Maintenance and Inspection(1) Visual Inspection of Switchgear Enclosure No deformation or physical damage to the enclosure. Protective paint coating shows no severe rust, peeling, or flaking. Cabinet is securely installed, clean on the surface, and free of foreign objects. Nameplates and identification labels are neatly affixed and not falling off.(2) Check of Switchgear Operating Parameters Instruments and meters indicate normal values (comparable to typical operating data, with no s
Edwiin
10/24/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.