Electron capture detector(ECD) method for sf6 gas switchgear

Edwiin
Field: Power switch
China

图...jpg

An electron capture detector (ECD) is a highly sensitive instrument capable of detecting sulfur hexafluoride (SF6) at concentrations below 1 ppmv. This sensitivity stems from SF6's high electron attachment coefficient, which refers to its strong ability to capture electrons. The free electrons available for attachment to SF6 molecules are generated by a radioactive source within the ECD. Typically, the ECD employs a radioactive emitter in the form of a metallic membrane coated with the radionuclide nickel.

When the detector is in operation, the electrons emitted by the radioactive source are accelerated by an electric field. These accelerated electrons then ionize the background gas, which is usually ambient air. As a result, a steady - state ionization current is established as ions and electrons are collected at the electrodes.

When SF6 is present in the air sample being analyzed, it reduces the number of free electrons in the system. This occurs because the electrons become attached to the SF6 molecules. The reduction in the ionization current is directly proportional to the concentration of SF6 in the sample. However, it should be noted that other molecules also possess a certain electron attachment coefficient, which means the detector is sensitive not only to SF6 but also to these other molecules.

In essence, the ECD functions as a flow rate detector. This is because the sensor pumps the gas sample through the electric field at a constant speed. Through calibration procedures, the flow rate data is internally converted into SF6 concentrations and is then recorded in parts per million by volume (ppmv).

The accompanying photo showcases an electron capture detector (ECD).

Give a tip and encourage the author!

Recommended

Classification of Equipment Defects for Relay Protection and Safety Automatic Devices in Substations
In daily operations, various equipment defects are inevitably encountered. Whether maintenance personnel, operation and maintenance staff, or specialized management personnel, all must understand the defect classification system and adopt appropriate measures according to different situations.According to Q/GDW 11024-2013 "Operation and Management Guide for Relay Protection and Safety Automatic Devices in Smart Substations," equipment defects are classified into three levels based on severity an
12/15/2025
Under What Conditions Will the Line Circuit Breaker Auto-Reclosing Signal Be Locked Out?
The line circuit breaker auto-reclosing signal will be locked out if any of the following conditions occur:(1) Low SF6 gas pressure in circuit breaker chamber at 0.5MPa(2) Insufficient energy storage in circuit breaker operating mechanism or low oil pressure at 30MPa(3) Busbar protection operation(4) Circuit breaker failure protection operation(5) Line distance protection zone II or zone III operation(6) Short lead protection operation of circuit breaker(7) Presence of remote tripping signal(8)
12/15/2025
Application of Auto-Reclosing Residual Current Protective Devices in Lightning Protection for Communication Power Supplies
1. Power Interruption Problems Caused by RCD False Tripping During Lightning StrikesA typical communication power supply circuit is shown in Figure 1. A residual current device (RCD) is installed at the power supply input terminal. The RCD primarily provides protection against electrical equipment leakage currents to ensure personal safety, while surge protective devices (SPDs) are installed on power supply branches to protect against lightning intrusions. When lightning strikes occur, the senso
12/15/2025
Reclosing Charge Time: Why Does Reclosing Require Charging? What Effects Does Charging Time Have?
1. Function and Significance of Reclosing ChargingReclosing is a protective measure in power systems. After faults such as short circuits or circuit overloads occur, the system isolates the faulty circuit and then restores normal operation through reclosing. The function of reclosing is to ensure continuous operation of the power system, improving its reliability and safety.Before performing reclosing, the circuit breaker must be charged. For high-voltage circuit breakers, the charging time is g