Electron capture detector(ECD) method for sf6 gas switchgear

Edwiin
Edwiin
Field: Power switch
China

图...jpg

An electron capture detector (ECD) is a highly sensitive instrument capable of detecting sulfur hexafluoride (SF6) at concentrations below 1 ppmv. This sensitivity stems from SF6's high electron attachment coefficient, which refers to its strong ability to capture electrons. The free electrons available for attachment to SF6 molecules are generated by a radioactive source within the ECD. Typically, the ECD employs a radioactive emitter in the form of a metallic membrane coated with the radionuclide nickel.

When the detector is in operation, the electrons emitted by the radioactive source are accelerated by an electric field. These accelerated electrons then ionize the background gas, which is usually ambient air. As a result, a steady - state ionization current is established as ions and electrons are collected at the electrodes.

When SF6 is present in the air sample being analyzed, it reduces the number of free electrons in the system. This occurs because the electrons become attached to the SF6 molecules. The reduction in the ionization current is directly proportional to the concentration of SF6 in the sample. However, it should be noted that other molecules also possess a certain electron attachment coefficient, which means the detector is sensitive not only to SF6 but also to these other molecules.

In essence, the ECD functions as a flow rate detector. This is because the sensor pumps the gas sample through the electric field at a constant speed. Through calibration procedures, the flow rate data is internally converted into SF6 concentrations and is then recorded in parts per million by volume (ppmv).

The accompanying photo showcases an electron capture detector (ECD).

Give a tip and encourage the author!
Recommended
 Causes and Preventive Measures of Fire and Explosion in Oil Circuit Breakers
Causes and Preventive Measures of Fire and Explosion in Oil Circuit Breakers
Causes of Fire and Explosion in Oil Circuit Breakers When the oil level in an oil circuit breaker is too low, the oil layer covering the contacts becomes too thin. Under the effect of the electric arc, the oil decomposes and releases flammable gases. These gases accumulate in the space beneath the top cover, mixing with air to form an explosive mixture, which can ignite or explode under high temperature. If the oil level inside the tank is too high, the released gases have limited space to expan
Felix Spark
11/06/2025
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
Ring main units (RMUs) are used in secondary power distribution, directly connecting to end-users such as residential communities, construction sites, commercial buildings, highways, etc.In a residential substation, the RMU introduces 12 kV medium voltage, which is then stepped down to 380 V low voltage through transformers. The low-voltage switchgear distributes electrical energy to various user units. For a 1250 kVA distribution transformer in a residential community, the medium-voltage ring m
James
11/03/2025
Why Monitoring Accuracy Matters in Power Quality Systems
Why Monitoring Accuracy Matters in Power Quality Systems
The Critical Role of Monitoring Accuracy in Power Quality Online DevicesThe measurement accuracy of online power quality monitoring devices is the core of the power system’s “perception capability,” directly determining the safety, economy, stability, and reliability of power supply to users. Inadequate accuracy leads to misjudgment, incorrect control, and flawed decision-making—potentially causing equipment damage, economic losses, or even grid failures. Conversely, high accuracy enables precis
Oliver Watts
10/30/2025