• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Mga Item sa Pagsasauli at Pagmamanila para sa 10kV High-Voltage Switchgear

Edwiin
Edwiin
Larangan: Pansakto ng kuryente
China

I. Pagsasanay at Pagtingin Nang Regular

(1) Pagtingin sa Mata sa Switchgear Enclosure

  • Walang deformation o pisikal na pinsala sa enclosure.

  • Ang protective paint coating ay walang malubhang rust, peeling, o flaking.

  • Ang cabinet ay ligtas na nai-install, malinis ang ibabaw, at walang mga foreign objects.

  • Ang nameplates at identification labels ay maayos na nakalagay at hindi naglalaho.

(2) Pagsusuri ng Operating Parameters ng Switchgear

  • Ang instruments at meters ay nagpapakita ng normal na values (katulad ng typical operating data, walang malaking deviation at consistent sa estado ng equipment).

(3) Pagsusuri ng Temperature ng Mga Komponente, Electrical Connections, Wires, at Cables

  • Gumamit ng infrared thermometer para sukatin ang accessible na komponente, electrical joints, wires, at cables: operating temperature ≤ 60°C.

  • Walang kakaibang amoy sa loob ng cabinet.

(4) Pagsusuri ng Switch Positions, Indicator Lights, Meter Displays, at Selector Switch Positions

  • Tama ang open/closed position ng circuit breaker.

  • Walang alarm indications.

  • Ang lahat ng selector switches ay nasa tama na posisyon.

II. Taunang Na-schedule na Pagsasanay

(1) Pagsusuri, Paglilinis, at Paggawa ng Defect Correction sa Enclosure

  • Linisin gamit ang alcohol at malinis na cotton cloth upang siguraduhing walang dust accumulation o stains.

  • Suriin ang protective paint para sa malubhang rust o peeling; kung may natuklasan, gawin ang rust removal at repaint.

(2) Pagsusuri at Pagsasanay ng Cable Compartment

  • Ang cable entry seals ay buo.

  • Ang cable plug fixing screws ay hindi loose.

  • Ang cable identification tags at phase color markings ay naroroon at hindi nawawala o nalis.

  • Ang cable compartment ay dry, walang condensation; malinis at walang dust.

  • Linisin ang insulators gamit ang alcohol at malinis na cotton cloth upang siguraduhing walang dust o contamination.

  • Ang grounding conductor ay ligtas at walang looseness.

(3) Pagsusuri ng Grounding Switch

  • Manually operate the grounding switch through one full open-close cycle.

  • Ang operasyon ay dapat smooth, walang jamming.

  • Ang switch position ay dapat tumugma sa indicator sa front panel.

(4) Pagsusuri at Pagsasanay ng Circuit Breaker Compartment

  • Withdraw the main circuit breaker to the test position and use a trolley to pull it outside the compartment. Inspect the primary isolation contacts and connected copper busbars for signs of burning or arcing. If necessary, polish with sandpaper and clean with alcohol-soaked cloth.

  • Apply a uniform layer of conductive grease (0.5–1 mm thick) to the main circuit breaker’s isolation contacts.

  • Tighten all primary circuit bolts to specified torque values. After tightening, check that spring washers are flat. Mark anti-loosening lines on all tightened bolts.

  • Wipe all components inside the circuit breaker compartment with alcohol and clean cotton cloth to ensure no dust or contamination.

  • Reinsert the circuit breaker trolley into the compartment and move to the test position. Perform one manual close-open operation cycle. Verify smooth operation, correct mechanical position indication, breaker position indication, and spring charged/uncharged status.

  • After verification, move the breaker to the service position and perform power on/off operations as required.

(5) Pagsusuri at Pagsasanay ng Secondary Circuit Compartment

  • Suriin ang secondary wiring: ang mga koneksyon ay dapat tight at clear ang wire labels.

  • Siguraduhing malinis ang compartment: walang dust o foreign objects.

  • Kung kinakailangan, linisin at i-tighten ang secondary terminals.

III. Taunang Electrical Testing

(1) Main Circuit Insulation Resistance Test

  • Gumamit ng 2500 V megohmmeter.

  • Measured value > 50 MΩ.

(2) Power Frequency Withstand Voltage Test
(Test on main circuit: phase-to-ground, phase-to-phase, and across open contacts)

  • After major maintenance: apply test voltage as per standard.

  • During service: apply 80% of the standard test voltage.

(3) Insulation Test of Auxiliary and Control Circuits

  • Gumamit ng 500 V megohmmeter.

  • Measured value > 2 MΩ.

IV. Fault-Based Maintenance (When Required)

(1) Circuit Breaker Operating Position Alignment

  • Apply conductive grease or Vaseline to the inner ring of the moving contact.

  • Insert the trolley to the service position and then withdraw it.

  • Use a caliper to measure the effective engagement depth between moving and stationary contacts on the visible part: should be 15–25 mm.

(2) Circuit Breaker Repair or Replacement

  • Carry out in accordance with manufacturer’s specific technical specifications.

(3) Instrument and Meter Repair or Replacement

  • Carry out in accordance with manufacturer’s specific technical specifications.

Magbigay ng tip at hikayatin ang may-akda!
Inirerekomenda
Bakit Gamitin ang Solid-State Transformer?
Bakit Gamitin ang Solid-State Transformer?
Ang solid-state transformer (SST), na kilala rin bilang Electronic Power Transformer (EPT), ay isang estatikong elektrikal na aparato na nagpapakombina ng teknolohiya ng power electronic conversion at mataas na frequency na energy conversion batay sa prinsipyo ng electromagnetic induction, na nagbibigay-daan sa pagbabago ng electrical energy mula sa isang set ng power characteristics papunta sa isa pa.Kumpara sa mga conventional transformers, ang EPT ay nagbibigay ng maraming mga benepisyo, kung
Echo
10/27/2025
Bakit Nasisira ang Fuse: Dahilan ng Overload Short Circuit at Surge
Bakit Nasisira ang Fuse: Dahilan ng Overload Short Circuit at Surge
Karaniwang Dahilan ng Pagputol ng FuseAng mga karaniwang dahilan ng pagputol ng fuse ay kabilang ang pagbabago ng voltaje, short circuit, pagtama ng kidlat sa panahon ng bagyo, at sobrang kargamento ng current. Ang mga kondisyong ito ay maaaring madali na sanhi ng pagputol ng elementong fuse.Ang fuse ay isang elektrikal na aparato na nagpuputol ng circuit sa pamamagitan ng pagputol ng fusible element nito dahil sa init na lumilikha kapag ang current ay lumampas sa tiyak na halaga. Ito ay gumagan
Echo
10/24/2025
Pagsasagawa ng Pagsasainit at Pagpapalit ng Fuse: Kaligtasan at Pinakamahusay na Katutohanan
Pagsasagawa ng Pagsasainit at Pagpapalit ng Fuse: Kaligtasan at Pinakamahusay na Katutohanan
1. Pagsasagawa ng Pag-aalamin sa FuseAng mga fuse na nasa serbisyo ay dapat na regular na isinspeksyon. Ang inspeksyon ay kasama ang mga sumusunod na item: Ang load current ay dapat na kompatibel sa rated current ng fuse element. Para sa mga fuse na may fuse blown indicator, suriin kung ang indicator ay nag-actuate. Suriin ang mga conductor, connection points, at ang fuse mismo para sa pag-init; siguraduhing maigsi at maganda ang contact ng mga koneksyon. Suriin ang labas ng fuse para sa mga cra
James
10/24/2025
Ano ang mga karaniwang isyu sa pagkakasira ng linyang may gas na SF₆ at sa hindi pag-operate ng circuit breaker?
Ano ang mga karaniwang isyu sa pagkakasira ng linyang may gas na SF₆ at sa hindi pag-operate ng circuit breaker?
Ang artikulong ito ay nagbabahagi ng mga kaparusahan sa dalawang pangunahing uri: mga kaparusahan sa circuit ng gas SF₆ at mga kaparusahan sa circuit breaker na hindi gumagana. Bawat isa ay ipinapaliwanag sa ibaba:1. Mga Kaparusahan sa Circuit ng Gas SF₆1.1 Uri ng Kaparusahan: Mababang presyon ng gas, ngunit ang density relay ay hindi nagbibigay ng alarm o lockout signalDahilan: May sira ang density gauge (i.e., hindi nakakasara ang contact)Pagsisiyasat & Pag-aayos: Kalibrin ang aktwal na pr
Felix Spark
10/24/2025
Inquiry
I-download
Kumuha ng IEE-Business Application
Gamit ang app na IEE-Business upang makahanap ng kagamitan makuha ang mga solusyon makipag-ugnayan sa mga eksperto at sumama sa industriyal na pakikipagtulungan kahit kailan at saanman buong pagsuporta sa pag-unlad ng iyong mga proyekto at negosyo sa enerhiya