Comprehensive Guide to High-Frequency Fault Handling of AC Contactors: 90% of Problems Solved with One Method

Felix Spark
Field: Failure and maintenance
China

1. Fault Phenomena, Cause Analysis and Handling Methods

Contactor does not operate or operates abnormally after coil energization

  • Open circuit in coil control circuit; Check if there is wire breakage or loosening at the terminal blocks. If there is a wire breakage, replace the corresponding wire; if there is loosening, fasten the corresponding terminal block.

  • Coil damage; Measure the coil resistance with a multimeter. If the resistance is ∞, replace the coil.

  • Thermal relay not reset after operation; Use the resistance range of a multimeter to measure the resistance between the two normally closed contacts of the thermal relay. If the resistance is ∞, press the reset button of the thermal relay.

  • Rated voltage of the coil is higher than the line voltage; Replace with a coil suitable for the control circuit voltage.

  • Excessive pressure of contact spring or release spring; Adjust the spring pressure or replace the spring.

  • Poor contact of button contacts or auxiliary contacts; Clean the contacts of the button or replace the corresponding component.

  • Excessive contact overtravel; Adjust the contact overtravel.

Contactor does not release or releases with delay after coil de-energization

  • No air gap in the middle column of the magnetic system, resulting in excessive residual magnetism; File off a part of the pole surface at the residual magnetism gap to make the gap 0.1~0.3mm, or connect a 0.1μF capacitor in parallel at both ends of the coil.

  • Oil on the surface of the iron core of a new contactor or oil accumulation after a period of use; Wipe off the anti-rust oil on the iron core surface. The iron core surface should be flat but not too smooth, otherwise it may easily cause delayed release.

  • Poor anti-welding performance of contacts; When starting the motor or in case of line short circuit, large current causes the contacts to weld and fail to release (pure silver contacts are more prone to welding). The main contacts of AC contactors should use silver-based alloys with strong anti-welding ability, such as silver-iron, silver-nickel, etc.

  • Incorrect wiring of the control circuit; Correct the incorrectly wired parts according to the control circuit diagram.

Coil overheating, burning or damage

  • The operating frequency and duty cycle of the coil exceed the product technical requirements; Replace with a coil that matches the corresponding operating frequency and duty cycle.

  • Uneven pole surface of the iron core or excessive air gap in the middle column; Clean the pole surface, adjust the iron core, or replace the coil.

  • Mechanical damage, stuck moving parts; Repair the mechanical parts and replace the coil.

  • Excessively high ambient temperature, humid air or corrosive gas causing coil insulation damage; Change the installation location and replace the coil.

  • Excessive noise from the electromagnet

  • Broken short-circuit ring; Replace the short-circuit ring or the iron core.

  • Excessive contact spring pressure or excessive contact overtravel; Adjust the contact spring pressure or reduce the overtravel.

  • Loose connecting pin between the armature and the mechanical part, or loose clamping screws; Reinstall the connecting pin and fasten the clamping screws.

Coil overheating, burning or damage.jpg

Phase-to-phase short circuit

  • Excessive dust accumulation on the contactor or moisture/oil contamination causing insulation damage; Regularly clean the contactor to keep it clean and dry.

  • In circuits using only electrical interlocking, the switching time of reversible contactors is shorter than the arc duration; Add mechanical interlocking.

  • Broken arc-extinguishing cover, or contactor components carbonized due to arc burning; Replace the arc-extinguishing cover or the damaged components.

Handling Methods for Excessive Noise Fault of AC Contactors

For an AC contactor with excessive noise during operation, the following measures can be taken:

  • Insufficient power supply voltage leading to insufficient electromagnetic attraction and noise; Take measures to increase the voltage of the control circuit.

  • Improper assembly of the magnetic system, skewing due to vibration, or stuck mechanical parts, preventing the iron core from being fully attracted; Adjust the magnetic system and identify and eliminate the causes of inflexible mechanical parts.

  • Rust on the pole surface or foreign objects (such as oil, dust, lint, etc.) on the iron core pole surface; Clean the iron core pole surface.

  • Excessive contact spring pressure causing electromagnet noise; Usually, adjust the contact spring pressure.

  • Noise caused by a broken short-circuit ring; Replace the iron core or the short-circuit ring.

  • Excessive wear and unevenness of the iron core pole surface; Replace the iron core.

  • Inter-turn short circuit of the coil; Usually, replace the coil.

Give a tip and encourage the author!
Recommended
Ultimate Guide to AC Contactor Abnormal Noise: From Electromagnetic Noise to Mechanical Vibration, Accurate Diagnosis and Handling
In electrical control systems, AC contactors are among the commonly used electrical components, and they are also a common source of various electrical faults. After long-term use—especially in harsh environments with high levels of dust—AC contactors may sometimes emit squeaking or rattling noises after being pulled in and held. The causes of this phenomenon are analyzed as follows.Squeaking Noise After Pull-In and HoldingA fully functional AC contactor makes no noise when energized and pulled
Felix Spark
09/11/2025
Mismatched AC Contactor Sizing? These 4 Typical Issues You Must Not Ignore – Click to View Solutions
AC contactors (with the electrical schematic code KM) are core electrical devices used to control the connection/disconnection between power supplies and loads in circuits, and they are also common equipment that electricians need to work with regularly. In practice, it is not uncommon to find that some peers make mistakes in selecting AC contactors, leading to improper sizing and subsequent persistent issues. Here, four of the most typical common mistakes are highlighted for reference.I. Over-R
James
09/11/2025
Proper Installation of AC Contactors | A Practical Guide to Avoid Burning and Misoperation, Master It in One Article
AC contactors are widely used for switching and controlling power circuits. They use main contacts to open and close circuits, and auxiliary contacts to execute control commands. Main contacts typically only have normally open contacts, while auxiliary contacts often have two pairs of contacts with normally open and normally closed functions. Small-sized contactors are also frequently used as intermediate relays to work with main circuits, thereby achieving the function of remote control or cont
James
09/11/2025
Application and Maintenance of AC Contactors | Comprehensive Analysis of Common Fault Handling, Master It in One Article
1 Analysis of Key Components of AC ContactorsAn AC contactor is an automated electromagnetic switch used for long-term, high-frequency switching of AC main circuits and control circuits. It features advantages such as automatic operation, under-voltage and no-voltage protection, high-capacity operation, strong stability, and low maintenance requirements. In the electrical control circuits of machine tools, AC contactors are mainly used to control electric motors and other loads.The key component