• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Transformer Bushings: Function, Types & Installation Guide

James
James
Field: Electrical Operations
China

Transformer Bushings: External Insulation and Current-Carrying Components

Transformer bushings are the primary external insulation devices mounted on the transformer tank. The leads from the transformer windings must pass through these insulating bushings, which provide insulation between the leads as well as between the leads and the transformer tank, while also serving to mechanically secure the leads.

Depending on the voltage level, transformer bushings are available in several types: porcelain bushings, oil-filled bushings, and capacitor-type bushings.

  • Porcelain bushings are commonly used in transformers rated 10 kV and below. They consist of a conductive copper rod passing through a porcelain housing, with air providing the internal insulation.

  • Oil-filled bushings are typically used in 35 kV-class transformers. These bushings are filled with insulating oil inside the porcelain housing, through which a copper conductor passes, insulated with oil-impregnated paper.

  • Capacitor-type bushings are used in high-voltage transformers above 100 kV. They consist of a main insulation unit (capacitor core), upper and lower porcelain housings, a connecting sleeve, oil reservoir (conservator), spring assembly, base, grading ring (corona shield), measuring terminal, line terminal, rubber gaskets, and insulating oil.

Transformer bushings serve to bring the internal high-voltage and low-voltage winding leads out of the oil tank. They not only provide insulation between the leads and ground but also play a critical role in securing the leads. As one of the current-carrying components of the transformer, bushings carry load current continuously during normal operation and must withstand short-circuit current during external faults.

Actual Photo of Transformer Bushing.jpg

Therefore, the following requirements apply to transformer bushings:

  • Must have specified electrical insulation strength and sufficient mechanical strength.

  • Must exhibit good thermal stability and be capable of withstanding momentary overheating during short-circuit conditions.

  • Should have compact size, light weight, excellent sealing performance, high interchangeability, and ease of maintenance.

The bushing is mainly composed of a capacitor core, oil reservoir, flange, and upper/lower porcelain housings. The main insulation is the capacitor core, formed by concentric capacitive layers connected in series. This assembly is enclosed within a sealed chamber formed by the upper and lower porcelain housings, oil reservoir, flange, and base. The chamber is filled with treated transformer oil, resulting in an oil-paper insulation structure. Oil-resistant rubber gaskets are used at contact surfaces between major components. All components are compressed together by a central preloading force applied via a set of strong springs located in the oil reservoir, ensuring the entire bushing remains hermetically sealed.

The flange is equipped with an air vent plug, oil sampling device, and terminals for measuring dielectric loss (tan δ) and partial discharge (PD). During operation, the protective cover of the measuring terminal must be installed to ensure reliable grounding of the screen (test tap); open-circuit conditions are strictly prohibited.

There are two main connection methods between the bushing and the high-voltage leads of the transformer:

  • Cable-penetration type

  • Conductor-rod current-carrying type

Pre-Installation Inspection of Transformer Bushings:

Before installation, the following checks should be performed:

  • Check the porcelain surface for cracks or damage.

  • Ensure the inner surfaces of the flange neck and grading ring are thoroughly cleaned.

  • Confirm the bushing has passed all required tests.

  • For oil-filled bushings, verify the oil level indication is normal and check for any oil leakage.

Bushings must be used under the conditions specified by their model designation, and the following precautions should be observed:

  • Sealing Integrity: Ensuring the bushing remains sealed is key to achieving long service life. Any seal points disturbed during installation or maintenance must be carefully restored to their original sealed condition.

  • Oil Level Control and Adjustment: The oil level inside the bushing should be periodically monitored during operation. If the oil level is too high or too low, adjustment is required.

    • If the oil level is too high, excess oil can be drained slowly through the oil drain plug on the flange.

    • If the oil level is too low, qualified transformer oil of the same grade specified on the nameplate must be added through the filling port of the oil reservoir.

  • For bushings with consistently normal oil test results in annual preventive tests, the interval between preventive tests may be appropriately extended to reduce the frequency of oil sampling. Any issues should be referred to the manufacturer. The bushing must not be disassembled by the user.

Correct Oil Sampling Procedure:
Clean the area around the oil drain plug on the flange. Open the plug and slowly screw in a dedicated oil sampling nozzle into the center threaded hole of the plug until it contacts the internal seal. Tighten the nozzle to compress the sealing gasket, allowing the transformer oil inside the bushing to flow out through the nozzle. After sampling, reverse the above steps to restore the original sealed condition.

Note: When removing the nozzle, do not loosen the oil drain plug. If loosening occurs, immediately tighten the plug using the appropriate spanner.

Measuring Terminal Grounding:
A measuring terminal is provided on the flange of the bushing. When measuring dielectric loss or partial discharge, remove the terminal cover and connect the test lead—the terminal stud is insulated from the flange. After testing, the terminal cover must be securely replaced to ensure reliable grounding. The measuring terminal must never be left open-circuited during operation.

Dielectric Loss Measurement Note:
The dielectric loss value measured on-site at 10 kV may differ from factory test data due to influences such as the measuring instrument, bushing position, and environmental conditions. It is recommended to use a high-voltage Schering bridge for measurement, and data obtained under high-voltage conditions should be considered authoritative.

Give a tip and encourage the author!
Recommended
How to Diagnose Faults in H59 Distribution Transformers by Listening to Their Sounds
How to Diagnose Faults in H59 Distribution Transformers by Listening to Their Sounds
In recent years, the accident rate of H59 distribution transformers has shown an upward trend. This article analyzes the causes of failures in H59 distribution transformers and proposes a series of preventive measures to ensure their normal operation and provide effective assurance for power supply.H59 distribution transformers play a vital role in power systems. With the continuous expansion of power system scale and the increasing single-unit capacity of transformers, any transformer failure n
Noah
12/08/2025
What lightning protection measures are used for H61 distribution transformers?
What lightning protection measures are used for H61 distribution transformers?
What lightning protection measures are used for H61 distribution transformers?A surge arrester should be installed on the high-voltage side of the H61 distribution transformer. According to SDJ7–79 "Technical Code for Design of Overvoltage Protection of Electric Power Equipment," the high-voltage side of an H61 distribution transformer should generally be protected by a surge arrester. The grounding conductor of the arrester, the neutral point on the low-voltage side of the transformer, and the
Felix Spark
12/08/2025
How does the oil in oil-immersed power transformers clean itself?
How does the oil in oil-immersed power transformers clean itself?
The self-cleaning mechanism of transformer oil is typically achieved through the following methods: Oil Purifier FiltrationOil purifiers are common purification devices in transformers, filled with adsorbents such as silica gel or activated alumina. During transformer operation, convection caused by oil temperature changes drives the oil to flow downward through the purifier. Moisture, acidic substances, and oxidation byproducts in the oil are absorbed by the adsorbent, thereby maintaining oil c
Echo
12/06/2025
Avoid H59 Transformer Failure with Proper Inspection & Care
Avoid H59 Transformer Failure with Proper Inspection & Care
Measures to Prevent H59 Oil Immersed Power Distribution Transformer from Burning OutIn power systems, H59 Oil Immersed Power Distribution Transformer play an extremely critical role. Once burned out, they can cause widespread power outages, directly or indirectly affecting the production and daily lives of a large number of electricity users. Based on the analysis of multiple transformer burnout incidents, the author believes that a considerable number of such failures could have been avoided or
Noah
12/06/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.