• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Low-Voltage Electrical Room Maintenance Procedures: Ensuring Stable Power System Operation

Edwiin
Edwiin
Field: Power switch
China

Maintenance of Main and Control Circuits in Low-Voltage Switchgear (Dust Removal); Inspection and Maintenance of Isolators, Circuit Breakers, Contactors, and Relays

I. Preparation and Standards Before Maintenance

  • Pre-Maintenance Preparations:

  • (1) Working Conditions: Scheduled shutdown and power disconnection.

  • (2) Tools and Instruments:Measuring instruments and tools including: insulation resistance tester (megger), clamp meter, multimeter, combination wrenches, voltage tester, electrician pliers, screwdrivers, utility knife, etc.

  • (3) Personal Protective Equipment (PPE):Safety helmet, insulating mat, insulating shoes, grounding wires, face mask.

  • (4) Materials and Spare Parts:Conductive grease, sandpaper, clean cloth, wires, blower, replacement components.

  • (5) Safety and Technical Measures:Complete and issue work permits and power on/off permits; conduct work content briefing; verify implementation of safety measures; review and confirm safety precautions.

  • Coordination: Shut down equipment and disconnect power. Verify absence of voltage and hang "Under Maintenance" signs. For busbar maintenance, install grounding wires, set up warning signs, and assign a dedicated supervisor during work.

II. Internal Maintenance of Low-Voltage Switchgear

Before starting maintenance, open the cabinet door and use a blower to remove accumulated dust inside the cabinet.

III. Maintenance Standards for Main and Control Circuits

  • Inspect busbars and main terminal connections for discoloration or looseness. Ensure no deformation or bending, and that electrical clearances meet standards (phase-to-phase >20mm at 380V, phase-to-enclosure >100mm).

  • Clean cable trenches—ensure no standing water or debris; supports should be intact, secure, and free from corrosion; covers must be complete; rodent-proofing at exits leading outdoors must be effective.

  • Control circuit wiring must be correct, neat, tight, clearly labeled; fuse connections must show no discoloration or looseness.

  • Panel indicators must be intact and reliable. Use a multimeter to test selector switches and push buttons—contact resistance should be less than 0.5Ω. Switches and buttons must operate smoothly without sticking.

  • Inspect primary contacts of drawer-type units for burn marks; spring pressure should be even and contact good. Secondary contacts’ metal spring contacts must not be bent or deformed. Measure contact resistance between secondary plug and socket—must be less than 0.5Ω.

IV. Isolator Switch Maintenance Standards

  • Operating handle should move smoothly and reliably; linkage base must show no burn or discharge marks; open/closed positions must be fully engaged; set screws, pins, and rods must be intact and secure.

  • Insertion depth of moving and fixed contacts must be no less than 2/3 of the blade width; contact area must cover at least 75% of the contact clip.

  • Moving and fixed contact surfaces must be free from burning; contact must be tight. If oxidation is present, clean the oxidized areas and apply a thin layer of Vaseline or conductive grease to prevent further oxidation.

  • Contact pressure: 45–80N for switches below 200A; 75–100N for 250–400A isolators; 150–220N for 500A and above. Adjust if out of range.

V. Air Circuit Breaker Maintenance Standards

Open the breaker housing and check incoming/outgoing lines for discoloration or looseness. Main contacts must show no burn marks. Operate the breaker twice—moving and fixed contacts must engage tightly with even pressure. Measure resistance with a multimeter—should be less than 0.2Ω. Arc chutes must be intact and undamaged.

After reassembly, the operating handle must move freely without obstruction. Pressing the test button should cause immediate tripping.

VI. AC Contactor Maintenance Standards

  • The short-circuit ring on the electromagnetic core must be securely fastened. When energized, the contactor should operate silently. The core surface must be clean and free from oil; coil insulation must be undamaged; coil surface must show no discoloration or overheating.

  • Remove the arc chute and inspect main contacts—they must make tight contact, show no burns, operate smoothly without sticking, and have even pressure. Contact gap must be within acceptable limits.

  • Components inside the arc chute must be intact; smoke residue must be cleaned. Linkage mechanism must have good insulation, with no deformation, displacement, or loosening.

  • Auxiliary contacts must operate smoothly without sticking; normally open and normally closed contacts must make good contact with no arcing damage.

VII. Relay Maintenance Standards

  • Inspect relay appearance—no contact burn marks. Energize the coil at rated voltage—the relay should pull in smoothly without noise or vibration. In the closed position, use a multimeter to confirm all contacts conduct properly.

  • For thermal relays, verify setting values are appropriate for the connected equipment. Press the test button and use a multimeter to confirm auxiliary contact operation is normal.

  • Thermal relays must be calibrated and operate sensitively and reliably.

  • For electromagnetic current relays, error between operating value and scale value must not exceed ±5%.

  • VIII. Post-Maintenance Measurements and Tests

  • After maintenance, count tools and ensure no tools or debris remain inside the cabinet. Measure main circuit insulation resistance: using a 500V megger, readings must be ≥5MΩ for 380V circuits, and ≥0.5MΩ for 36V control circuits. Insulation resistance between breakers, busbars, ground, and phases must exceed 10MΩ.

  • Remove "Under Maintenance" signs, remove grounding wires, close and lock cabinet doors. Set switch to "Test" position, close the breaker to energize, and perform no-load open/close tests. Operate open/close functions twice—switch must operate smoothly and reliably without sticking; indicators must function correctly.

  • Clean the work area thoroughly. Complete maintenance records—collect documentation, and fully record any replaced parts or adjusted components in the equipment logbook. Conclude maintenance and notify operators to test run the equipment.

  • For equipment with replaced control components, measure three-phase operating current for balance and verify normal three-phase voltage. Record results. Observe operation for at least 0.5 hours. Only release for service after confirmation and signature by all three parties (contractor, supervisor, and user).

Give a tip and encourage the author!
Recommended
MVDC: Future of Efficient, Sustainable Power Grids
MVDC: Future of Efficient, Sustainable Power Grids
The Global Energy Landscape Is Undergoing a Fundamental Transformation toward a "fully electrified society," characterized by widespread carbon-neutral energy and the electrification of industry, transportation, and residential loads.In today’s context of high copper prices, critical mineral conflicts, and congested AC power grids, Medium-Voltage Direct Current (MVDC) systems can overcome many limitations of traditional AC networks. MVDC significantly enhances transmission capacity and efficienc
Edwiin
10/21/2025
Grounding Causes of Cable Lines and the Principles of Incident Handling
Grounding Causes of Cable Lines and the Principles of Incident Handling
Our 220 kV substation is located far from the urban center in a remote area, surrounded primarily by industrial zones such as Lanshan, Hebin, and Tasha Industrial Parks. Major high-load consumers in these zones—including silicon carbide, ferroalloy, and calcium carbide plants—account for approximately 83.87% of our bureau’s total load. The substation operates at voltage levels of 220 kV, 110 kV, and 35 kV.The 35 kV low-voltage side mainly supplies feeders to ferroalloy and silicon carbide plants
Felix Spark
10/21/2025
Overhead Power Lines & Towers: Types, Design & Safety
Overhead Power Lines & Towers: Types, Design & Safety
Besides ultra-high voltage AC substations, what we encounter more frequently are power transmission and distribution lines. Tall towers carry conductors that leap across mountains and seas, stretching into the distance before reaching cities and villages. This is also an interesting topic—today, let's explore transmission lines and their supporting towers.Power Transmission and DistributionFirst, let’s understand how electricity is delivered. The electric power industry primarily consists of fou
Encyclopedia
10/21/2025
Automatic Reclosing Modes: Single, Three-Phase & Composite
Automatic Reclosing Modes: Single, Three-Phase & Composite
General Overview of Automatic Reclosing ModesTypically, automatic reclosing devices are categorized into four modes: single-phase reclosing, three-phase reclosing, composite reclosing, and disabled reclosing. The appropriate mode can be selected based on load requirements and system conditions.1. Single-Phase ReclosingMost 110kV and higher transmission lines employ three-phase single-shot reclosing. According to operational experience, over 70% of short-circuit faults in high-voltage overhead li
Edwiin
10/21/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.