What is Automatic Voltage Regulator?

Edwiin
Edwiin
Field: Power switch
China

An automatic voltage regulator is employed to regulate voltage, converting fluctuating voltages into a constant one. Voltage fluctuations mainly stem from variations in the load on the supply system. Such voltage variations can damage the equipment within the power system. These fluctuations can be mitigated by installing voltage - control equipment at various locations, such as near transformers, generators, and feeders. Multiple voltage regulators are often placed throughout the power system to manage voltage variations effectively.

In a DC supply system, for feeders of equal length, over - compound generators can be used to control voltage. However, for feeders of different lengths, feeder boosters are utilized to maintain a constant voltage at the end of each feeder. In an AC system, various methods, including booster transformers, induction regulators, and shunt condensers, can be employed to control voltage.

Working Principle of Voltage Regulator

It operates based on the principle of error detection. The output voltage of an AC generator is obtained via a potential transformer, then rectified, filtered, and compared with a reference voltage. The difference between the actual voltage and the reference voltage is called the error voltage. This error voltage is amplified by an amplifier and subsequently supplied to the main exciter or pilot exciter.

Consequently, the amplified error signals regulate the excitation of the main or pilot exciter through a buck or boost action (i.e., they manage voltage fluctuations). Controlling the exciter output in turn regulates the terminal voltage of the main alternator.

Application of the Automatic Voltage Regulator

  • The key functions of an Automatic Voltage Regulator (AVR) are as follows:

  • It regulates the system voltage and helps keep the machine's operation closer to steady - state stability.

  • It distributes the reactive load among parallel - operating alternators.

  • AVRs mitigate overvoltages that result from sudden load loss in the system.

  • Under fault conditions, it increases the system's excitation to ensure maximum synchronizing power when the fault is cleared.

  • When there is a sudden load change in the alternator, the excitation system needs to adjust to maintain the same voltage under the new load conditions. The AVR enables this adjustment. The AVR equipment acts on the exciter field, altering the exciter output voltage and field current. However, during severe voltage fluctuations, the AVR may not respond rapidly.

To achieve a quicker response, fast - acting voltage regulators based on the overshooting - the - mark principle are utilized. In this principle, when the load increases, the system's excitation also increases. But before the voltage rises to the level corresponding to the increased excitation, the regulator reduces the excitation to an appropriate value.

Give a tip and encourage the author!
Recommended
PT Fuse Slow Blow: Causes, Detection & Prevention
PT Fuse Slow Blow: Causes, Detection & Prevention
I. Fuse Structure and Root Cause AnalysisSlow Fuse Blowing:From the design principle of fuses, when a large fault current passes through the fuse element, due to the metal effect (certain refractory metals become fusible under specific alloy conditions), the fuse first melts at the soldered tin ball. The arc then rapidly vaporizes the entire fuse element. The resulting arc is quickly extinguished by quartz sand.However, due to harsh operating environments, the fuse element may age under the comb
Edwiin
10/24/2025
Why Fuses Blow: Overload, Short Circuit & Surge Causes
Why Fuses Blow: Overload, Short Circuit & Surge Causes
Common Causes of Fuse BlowingCommon reasons for fuse blowing include voltage fluctuations, short circuits, lightning strikes during storms, and current overloads. These conditions can easily cause the fuse element to melt.A fuse is an electrical device that interrupts the circuit by melting its fusible element due to heat generated when current exceeds a specified value. It operates on the principle that, after an overcurrent persists for a certain period, the heat produced by the current melts
Echo
10/24/2025
Fuse Maintenance & Replacement: Safety and Best Practices
Fuse Maintenance & Replacement: Safety and Best Practices
1. Fuse MaintenanceFuses in service should be regularly inspected. The inspection includes the following items: Load current should be compatible with the rated current of the fuse element. For fuses equipped with a fuse blown indicator, check whether the indicator has actuated. Check the conductors, connection points, and the fuse itself for overheating; ensure connections are tight and making good contact. Inspect the fuse exterior for cracks, contamination, or signs of arcing/discharge. Liste
James
10/24/2025
Maintenance and Repair Items for 10kV High-Voltage Switchgear
Maintenance and Repair Items for 10kV High-Voltage Switchgear
I. Routine Maintenance and Inspection(1) Visual Inspection of Switchgear Enclosure No deformation or physical damage to the enclosure. Protective paint coating shows no severe rust, peeling, or flaking. Cabinet is securely installed, clean on the surface, and free of foreign objects. Nameplates and identification labels are neatly affixed and not falling off.(2) Check of Switchgear Operating Parameters Instruments and meters indicate normal values (comparable to typical operating data, with no s
Edwiin
10/24/2025