35kV erantsiguneko akatsen tratamendua

Leon
Leon
Eremua: Arazo Diagnostika
China

35kV Substation-en operazioan gertatzen diren akatsen analisia eta kudeaketa

1. Akatsen Analisia

1.1 Lerroarekin lotutako akatsak

Energia sistemen eremua oso handia da. Energia emandaritzeko beharrak betetzeko, asko transmisio lerroak instalatu behar dira, hau zailtasun handiak sortzen ditu kudeamenduan. Batez ere espezialitateko lerroetarako, instalazioak bidegabeko kokapenetan, hala nola arrabaldeetan egiten dira, bizi-biziaren eraginak gutxienez posible izateko. Baina horrelako kokapenetan ingurumen konplexua dago, lerroen mantentzea eta inspektatzea zaila da. Inspektion, konponketen eta kudeamenduen praktikak txarrak adierazten dituzte lerroen defektuak ez direla detektatzen, substationen akatsen probabilitatea handituz.

Gainera, lerroek basoetan igotzen badira, zuhaitzengandiko kontaktuak edo ilara-egiturak erraztik akatsak gertatzen dituzte, eta hainbat aldiz sute handiak sor dezakete, energia segurtasunei arrisku handiak emanez.

1.2 Tenperatura baxuko aldeko transformadore nagusiko interruptorren aktibazioa

Horrelako aktibazioak hiru egoeretatik batetik soilik gertatzen da: interruptoreren erabilera okerra, aktibazio gain (aktibazio enilerakorra) edo busbarren akatsak. Arrazoia zehazki jakin daiteke primario eta sekundario tresnak aztertuta.

Transformadore nagusiaren tenperatura baxuko korronte gaineko babesa bakarrik funtzionatzen bada, interruptoreren aktibazio edo erabilera okerra ezaugarri daiteke. Aktibazio gaina eta busbarren akatsen arteko bereizpena tresna guztien azterketa orokorraren bidez egin daiteke.

  • Sekundario tresnetarako, babestuak eta senalak markatu.

  • Primario tresnetarako, korronte gaineko babeseko eremu barruko geroztik geroztik aztertu.

Babestuaren aktibazio senala ("drop card" senala) ez badago, akatsa babestuaren senalaren hutsegiteagatik edo puntu bihurketak asmatu beharreko bi puntuetatik gertatua dela jakin daiteke.

1.3 Hiru aldeko transformadore nagusiko interruptorren aktibazioa

Hiru aldeko aktibazio arruntak hurrengoak dira:

  • Transformadorearen barneko akatsak

  • Tenperatura baxuko busbarren akatsak

  • Tenperatura baxuko busbarretan sartutako itxura laburrak

Akats horiek saihesteko, substation teknikariak hiru aldeko interruptoreak aztertzen dituzte eta gas (Buchholz) babesa implantatzen dute transformadorearen babesa.

Substation Fault Tripping Maintence.jpg

2. Akatsen Kudeaketarako Teknikak

2.1 Lerroaren Aktibazioak Kudeatzeko

35kV substation bat lerro aktibazio bat ondoren, azterketa zuzena egin behar da babestuak egindako ekintzari jarraiki. Azterketa eremua lerroaren irteera eta lerroaren CT aldearen artean definitu behar da, CT circuitu diagrama oinarritzat hartuta.

Azpiego baten ez badago, jarraitu aktibatutako interruptoreren azterketa, hurrengo sekuentziatan:

  • Interruptoreren posizioaren adierazlea

  • Hiru faseko lotura bizkarrekoa

  • Arku-kontsultakoa

Azterketa puntu nagusiak interruptorer mota bakoitzeko desberdinak dira:

  • Spring-operated interruptorerentzat: Springaren energiaren biltegia egiaztatu.

  • Elektromagnetiko interruptorerentzat: Fusetak eta indarraren kontaktu egoera egiaztatu.

Azpiegoa kenduta, lerroa berriro aktibatu behar da.

2.2 Tenperatura baxuko aldeko transformadore nagusiko interruptorren aktibazioa Kudeatzeko

Aktibazio ondoren:

  • Tenperatura baxuko korronte gaineko babesak bakarrik funtzionatu baditu, eta aktibazio senalik ez badago, sekundario zirkuitua aztertu: fusetak botaka edo babestu-relayen esteka falta (pressure plates).

  • Primario tresnetarako, tenperatura baxuko busbarraren eta lerroaren irteera lotutako geroztik geroztik aztertu.

Lerro babesa eta korronte gaineko babesa funtzionatu baditu, baina lerroaren interruptorea ez badu aktibatu, hau lerroaren akatsa adierazten du. Lerro patrullak egin behar dira irteera-tik akats puntu-ra. Soluzioa erraza da: aktibatutako interruptoreren bi aldetan diskonexioak irekitzea, osasuna mantentzen duten tresnek berriz aktibatzeko.

Transformadore nagusia aktibatu badu, baina babestu senalik ez badago, arrazoia hau izan daiteke:

  • Babestuaren hutsegitea (ez funtzionatzea)

  • Puntu bihurketak

  • Interruptoreren mekanismoaren hutsegitea

Kasu horietan, transformadorearen babestu sistema babestu-relayen hutsegitea adieraz dezake. Hona hemen kudeatzeko pausuak:

  • Busbarren interruptore guztiak ireki.

  • Transformadorearen tenperatura baxuko aldea berriro aktibatu saiatu.

  • Beste alimentazio lineak graduan aktibatu.

2.3 Hiru aldeko transformadore nagusiko aktibazioa Kudeatzeko

Akatsa hiru aldeko aktibazio bat jaso duen jakiteko, babestu senalak eta primario tresnak aztertu:

  • Buchholz (gas) babesta funtzionatu badu, akatsa transformadorearen barnean edo sekundario zirkuituan dagoela uste da, ez kanpo sistemaren. Aztertu:

    • Oil spraying from the conservator tank or breather

    • Grounding or short circuits in the secondary circuit

    • Transformer deformation or fire

  • Differential protection indicates inter-turn or phase-to-phase faults in the transformer windings. Inspect:

    • Oil level and color

    • Bushings

    • Gas relay

If gas is present in the relay, analyze its color and flammability to determine fault type.

If no fault is found, the tripping may be due to protection misoperation, which is relatively common and easier to handle. Restore operation according to standard procedures.

3. Preventive Measures for Substation Operation

3.1 Timely Fault Detection and Response

Operators must conduct routine equipment checks, record operational data, and identify early fault signs. After maintenance, proper acceptance testing is critical to ensure safety.

In case of faults, operators should:

  • Isolate faulty equipment

  • Switch to backup systems

  • Apply effective solutions to maintain system stability

Mastering switching operations (isolator operations) significantly reduces fault risks. This requires high technical proficiency and continuous training.

3.2 Enforce Safety Regulations and Accountability

Enhance safety awareness through:

  • Bulletin boards

  • Safety slogans

  • Accident videos

  • Safety bulletins

  • Safety meetings

  • Case studies

Establish a safety responsibility system with clear roles, performance metrics, and reward/punishment mechanisms. Make safety responsibilities quantifiable and traceable to motivate operators and strengthen accountability.

3.3 Improve Technical Management

To ensure grid safety, operators must continuously improve technical skills and equipment management.

  • Conduct training programs, technical lectures, and regulation reviews.

  • Ensure staff understand:

    • Equipment layout

    • System connections

    • Operating procedures

    • Basic maintenance

  • Conduct accident anticipation exercises and anti-accident drills to improve emergency response.

  • Ensure operators fully understand:

    • Operation purpose

    • Pre- and post-operation system states

    • Load changes

    • Critical precautions

4. Conclusion

In modern society, people heavily rely on electricity for production and daily life, demanding higher reliability from power systems. Therefore, enhancing attention to substation operation, mastering tripping fault mechanisms, and responding promptly are essential tasks for the power industry to minimize system disruptions.

Ordaintza ematea eta egilea bermatzea
Gomendioa
Analisiaren Subestazio Barrutia Desagertze Akatsak eta Horien Soluzioak
Analisiaren Subestazio Barrutia Desagertze Akatsak eta Horien Soluzioak
1. Barra deko erakarpena detektatzeko metodoak1.1 Isulagarraren erraztestu-erresistentzia probaIsulagarraren erraztestu-erresistentzia probak elektrikoki isulagarriak probatzeko erabili ohi den metodo sinplea da. Oso sentibila da igurketa-mota insulazio akatsengatik, gisa osoko eguzkitasun ondorioz eta gainazal kontsultuta—egoiten dituen egoeretan erresistentzia-balioak askoz gutxitu egiten dira. Hala ere, ez da oso efiziente kokapen zaharretan edo erakarpenei partzialak detektatzeko.Gailuaren i
Edwiin
10/31/2025
Gaitzaren Ezkutatzeko Kudeaketa: Urrats-urratsako Gida
Gaitzaren Ezkutatzeko Kudeaketa: Urrats-urratsako Gida
1. Totala subestazio itzalaren kudeaketaren helburua220 kV edo gehiagoko subestazio batean gertatzen den totala itzala, harrapen elektriko orokorrak, pertsona ekonomiko handiak eta sarrera-irteera sisteman instabilitateak eragin ditzake, sistema zatitzailea sortu baitaiteke. Prozedura honek 220 kV edo gehiagoko tensioarekin dagoen subestazio nagusietan tensiorik gabeko egoera saihesteko dator.2. Totala subestazio itzalak kudeatzeko oinarrizko printzipioak Zerbitzu-komandoarekin kontaktuan jarri
Felix Spark
10/31/2025
110 kV erantsoko energia bidearen barruko bus lineazio konfigurazioen eволюция
110 kV erantsoko energia bidearen barruko bus lineazio konfigurazioen eволюция
Lehen 110 kV transformatorioetan ohikoa zen "barneko barruko konexio" iturriaren aldetik, non iturburua arrakasta "barneko zubia konexio" metodoa erabiltzen duen. Hona hemen adibide bat 220 kV transformatorioetako batzuk 110 kV barruak beste biratzaile baten ondorioz "barruko bi-iturri" konfigurazioan ematen dituztela. Egoera honetan, bi biratzaile daude, 10 kV aldetan barrutegi bakar batekin segmentatuta.Avantazioak dira: konexio sinpleak, maneio errazak, automatikoki aldaketarako eginkizuna et
Vziman
08/08/2025
Estatu Zeharrakoa
Estatu Zeharrakoa
Errepideko subestazioa da 55 KVtik 765 KVra bitarteko tensio mailu guztiak onartzen dituen. Subestazio mota hau, era orokorrez, eraikuntza denborarik gutxiago behar du, baina espazio gehiago hartzen du. Errepideko subestazioak bi motetan sailkatzen dira: makila gainean kokatutako subestazioak eta oinarri gainean kokatutako subestazioak.Makila gainean kokatutako subestazioaMakila gainean kokatutako subestazioak, 250 KVAra arteko kapasitateko banaketa transformadoreak sustatzeko erabiltzen dira. T
Edwiin
05/12/2025
Eskaera bidali
Jeitsi
IEE Business aplikazioa lortu
IEE-Business aplikazioa erabili ekipamendua bilatzeko, soluzioak lortzeko, adituekin konektatzeko eta industria lankidetzan parte hartzeko edonon eta edonoiz — zure energia proiektu eta negozioen garapenerako laguntza osoa ematen du.