12kV environmental protection cabinet (air insulated without SF6 gas) PT isolation operating mechanism

  • 12kV environmental protection cabinet (air insulated without SF6 gas) PT isolation operating mechanism

Key attributes

Brand Switchgear parts
Model NO. 12kV environmental protection cabinet (air insulated without SF6 gas) PT isolation operating mechanism
Rated voltage 12kV
Rated normal current 630A
Series NHK-J12

Product descriptions from the supplier

Description

The NHK-J12 environmental protection cabinet PT isolation operating mechanism is suitable for the 5.2 series environmental protection cabinet PT isolation unit. The mechanism adopts the principle of compression spring releasing energy through the middle. The isolation operating shaft is located on the right side of the mechanism, and the grounding operating shaft is located on the left side of the mechanism. It adopts a single rod mechanical interlocking structure, and the overall structure of the mechanism is compact and easy to install. The mechanism interlocking meets the five prevention requirements. The operating mechanism complies with the relevant requirements of standards such as GB1984-2014, GB/T1022-2020, GB3804-2017, GB3906-2020, etc.

Operation of opening and closing the mechanism

Power transmission operation:
①. Close the door; ②. Insert the handle into the grounding operation hole of the G mechanism and operate counterclockwise to separate the locking/grounding of the lower door; ③. Insert the handle into the isolation operation hole of the G mechanism and operate counterclockwise to close the isolation switch; Power transmission completed.
Power outage operation:
①. Insert the handle into the isolation operation hole of the G mechanism and operate clockwise to open the isolation switch; ②. Insert the handle into the grounding operation hole of the G mechanism, operate clockwise to close the grounding switch, power off and complete the grounding operation (at this time, the lower door can be opened).

Product Parameters

Serial Number

Item

Unit

Parameter

1

Voltage Level

V

AC/DC220; AC/DC110; DC48; DC24

2

Rated Power

W

/

3

Operating Environment

-40~+40

4

Power Frequency Withstand Voltage

kv

2/1min

5

Normal Operating Voltage Range of Closing Coil

UL

/

6

Normal Operating Voltage Range of Opening Coil

UL

/

7

Low Voltage Operating Range

UL

/

8

Salt Spray Resistance Grade

h

96

Installation dimensions

 

FAQ
Q: What are the routine maintenance requirements of the PT isolation operating mechanism?
A:
Routine maintenance focuses on "simple inspection + periodic maintenance" to ensure long-term reliable operation: ① Monthly inspection: Check the position indicator of the isolation switch (consistent with the actual position), check the interlocking function (no misoperation), and clean the surface of the mechanism with dry cloth; ② Quarterly maintenance: Check the tightness of the terminal connection (no looseness), check the lubrication of the operating mechanism (supplement lubricating grease if necessary), and check the protection level of the mechanism box (no water or dust intrusion); ③ Annual maintenance: Conduct mechanical operation test (≥100 times of opening and closing without jamming), check the insulation performance of the isolation fracture (power frequency withstand voltage test), and record the maintenance data for traceability, ④ Special maintenance: In humid, high-pollution or high-altitude areas, increase the inspection frequency, and check the anti-corrosion performance of the mechanism and cabinet body regularly.
Q: What is the core function of the 12kV SF6-free air-insulated cabinet PT isolation operating mechanism?
A:
Its core functions include three key aspects: ① PT loop isolation: realize reliable opening/closing of the PT (voltage transformer) primary loop to ensure safe maintenance of PT components; ② Safety interlocking: match the "five-prevention" interlocking requirement of the switch cabinet, and it can only operate when the main loop is opened and reliably grounded to prevent misoperation such as live isolation; ③ Environmental protection and insulation: adopt air insulation without SF6 gas, which has no greenhouse effect and toxic decomposition products, and meets global environmental protection policies. It is mainly used to ensure the safe operation of the PT loop in the 12kV eco-friendly cabinet and provide accurate voltage signal support for measurement and protection.
Know your supplier
Online store
On-time delivery rate
Response time
100.0%
≤4h
Company overview
Workplace: 1000m² Total staff: Highest Annual Export(usD): 300000000
Workplace: 1000m²
Total staff:
Highest Annual Export(usD): 300000000
Services
Business Type: Sales
Main Categories: Low Voltage Electrical Apparatus/Instrument meters/Production equipment/Tester/High Voltage Electrical Apparatus/Electrical fittings/Equipment Parts
Whole life care manager
Whole-life care management services for equipment procurement, use, maintenance, and after-sales, ensuring safe operation of electrical equipment, continuous control, and worry-free electricity consumption.
The equipment supplier has passed platform qualification certification and technical evaluation, ensuring compliance, professionalism, and reliability from the source.

Related Products

Related Knowledges

  • Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
    Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
    01/30/2026
  • Neutral point grounding operation mode for 110kV~220kV power grid transformers
    The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
    01/29/2026
  • Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
    Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
    01/29/2026
  • Why Must a Transformer Core Be Grounded at Only One Point? Isn't Multi-Point Grounding More Reliable?
    Why Does the Transformer Core Need to Be Grounded?During operation, the transformer core, along with the metal structures, parts, and components that fix the core and windings, are all situated in a strong electric field. Under the influence of this electric field, they acquire a relatively high potential with respect to ground. If the core is not grounded, a potential difference will exist between the core and the grounded clamping structures and tank, which may lead to intermittent discharge.I
    01/29/2026
  • Understanding Transformer Neutral Grounding
    I. What is a Neutral Point?In transformers and generators, the neutral point is a specific point in the winding where the absolute voltage between this point and each external terminal is equal. In the diagram below, pointOrepresents the neutral point.II. Why Does the Neutral Point Need Grounding?The electrical connection method between the neutral point and earth in a three-phase AC power system is called theneutral grounding method. This grounding method directly affects:The safety, reliabilit
    01/29/2026
  • What’s the Difference Between Rectifier Transformers and Power Transformers?
    What is a Rectifier Transformer?"Power conversion" is a general term encompassing rectification, inversion, and frequency conversion, with rectification being the most widely used among them. Rectifier equipment converts input AC power into DC output through rectification and filtering. A rectifier transformer serves as the power supply transformer for such rectifier equipment. In industrial applications, most DC power supplies are obtained by combining a rectifier transformer with rectifier equ
    01/29/2026
Haven't found the right supplier yet? Let matching verified suppliers find you. Get Quotation Now
Haven't found the right supplier yet? Let matching verified suppliers find you.
Get Quotation Now
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.