12KV environmentally friendly (air insulated without SF6 gas) vacuum circuit breaker switch under isolation

  • 12KV environmentally friendly (air insulated without SF6 gas) vacuum circuit breaker switch under isolation

Key attributes

Brand Switchgear parts
Model NO. 12KV environmentally friendly (air insulated without SF6 gas) vacuum circuit breaker switch under isolation
Rated voltage 12kV
Rated normal current 630A
Rated short circuit breaking current 25kA
Series VHK-12

Product descriptions from the supplier

Description

The isolation circuit breaker switch on VHK-12 environmental protection cabinet adopts a semi sealed structure, which has the advantages of uniform electric field, reliable disconnection, long service life, maintenance free and easy installation. This product is mainly used for isolation unit solutions on environmentally friendly air insulated ring main units. As the main component inside the cabinet, it undertakes the functions of closing and opening the main circuit, and has functions such as closing and opening rated load current and closing and breaking short-circuit current.
Environmental conditions for use:
1) Environmental temperature: maximum temperature+40 ℃, minimum temperature -15 ℃ (storage and transportation allowed at -30 ℃);
2) Altitude: ≤ 2000 meters;
3) Environmental humidity: Daily average relative humidity<95%, monthly average relative humidity<90%;
4) Seismic intensity: not exceeding 8 degrees: 5) Place of use: no flammable or explosive hazards, no water vaporization, corrosive gases, and severe vibration phenomena; For special usage scenarios that differ from normal operating conditions, the product user must agree with the manufacturer. For example, when electrical equipment is installed at an altitude of over 2000 meters, special instructions must be made for the manufacturer to adjust the product during production.

Model description

Product Parameters

Serial Number

Item

Unit

Parameter

Remark

1

Rated Voltage

KV

12


2

Rated Current

A

630


3

Rated Breaking Current / Thermal Stability Time

KA/S

20/4; 25/3


4

Rated Peak Withstand Current

KA

50/63


5

Rated Short-circuit Making Current

KA

50/63


6

Short-circuit Making Times

times

30


7

Power Frequency Withstand Voltage: Phase-to-Ground / Phase-to-Phase

KV

42

In Dry Air or N₂

8

Power Frequency Withstand Voltage: Break

KV

48

In Dry Air or N₂

9

Lightning Impulse: Phase-to-Ground / Phase-to-Phase

KV

75

In Dry Air or N₂

10

Lightning Impulse: Break

KV

85

In Dry Air or N₂

11

Main Circuit Resistance

μΩ

≤60

Vacuum Arc Extinguishing Chamber + Disconnector

12

Mechanical Life of Arc Extinguishing Chamber

times

10000


13

Mechanical Life of Isolation / Earthing Switch

times

5000


14

Gas Tank Pressure

bar

1.25


Installation dimensions

FAQ
Q: What key parameters should be paid attention to when selecting eco-cabinet top-mounted isolation circuit breakers?
A:
Focus on three categories of parameters: system matching, performance indicators and cabinet/PT adaptation: ① System matching parameters: Rated voltage (10kV/12kV), rated current (630A/1250A), rated short-circuit breaking current (≥25kA/31.5kA), which must be consistent with the distribution system and PT parameters; ② Core performance indicators: Insulation level (power frequency withstand voltage ≥42kV), mechanical life (≥10000 operations), electrical life (≥2000 operations), isolation gap (≥125mm for 12kV level); ③ Cabinet/PT adaptation parameters: Installation hole size, transmission rod length, interlock interface type (matching PT isolation switch interlock system), and overall height (adapting to eco-cabinet upper space). For high-altitude (≥1000m) and high-pollution areas, select products with enhanced insulation and anti-corrosion structures.
Q: What is an eco-cabinet top-mounted isolation circuit breaker switch and its core functions?
A:
It is an integrated medium-voltage electrical component installed on the upper part of SF6-free air-insulated eco-cabinets, combining the dual functions of an isolation switch and a circuit breaker. Its core functions include 4 key points: ① Dual protection & isolation: Cut off normal load current and short-circuit fault current, and form a visible insulation gap after opening to ensure maintenance safety; ② Space optimization: Top-mounted installation is close to the main busbar, shortening busbar connection length and reducing power loss, which is compatible with PT (potential transformer) and its dedicated isolation switch layout; ③ Safety interlocking: Realize mechanical interlock with cabinet door, earthing switch and PT isolation switch to avoid misoperations; ④ Environmental compliance: Adopt air insulation without SF6 gas, in line with global low-carbon policies. It is widely used in 10kV/12kV medium-voltage distribution systems.
Know your supplier
Online store
On-time delivery rate
Response time
100.0%
≤4h
Company overview
Workplace: 1000m² Total staff: Highest Annual Export(usD): 300000000
Workplace: 1000m²
Total staff:
Highest Annual Export(usD): 300000000
Services
Business Type: Sales
Main Categories: Low Voltage Electrical Apparatus/Instrument meters/Production equipment/Tester/High Voltage Electrical Apparatus/Electrical fittings/Equipment Parts
Whole life care manager
Whole-life care management services for equipment procurement, use, maintenance, and after-sales, ensuring safe operation of electrical equipment, continuous control, and worry-free electricity consumption.
The equipment supplier has passed platform qualification certification and technical evaluation, ensuring compliance, professionalism, and reliability from the source.

Related Products

Related Knowledges

  • Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
    Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
    01/30/2026
  • Neutral point grounding operation mode for 110kV~220kV power grid transformers
    The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
    01/29/2026
  • Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
    Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
    01/29/2026
  • Why Must a Transformer Core Be Grounded at Only One Point? Isn't Multi-Point Grounding More Reliable?
    Why Does the Transformer Core Need to Be Grounded?During operation, the transformer core, along with the metal structures, parts, and components that fix the core and windings, are all situated in a strong electric field. Under the influence of this electric field, they acquire a relatively high potential with respect to ground. If the core is not grounded, a potential difference will exist between the core and the grounded clamping structures and tank, which may lead to intermittent discharge.I
    01/29/2026
  • Understanding Transformer Neutral Grounding
    I. What is a Neutral Point?In transformers and generators, the neutral point is a specific point in the winding where the absolute voltage between this point and each external terminal is equal. In the diagram below, pointOrepresents the neutral point.II. Why Does the Neutral Point Need Grounding?The electrical connection method between the neutral point and earth in a three-phase AC power system is called theneutral grounding method. This grounding method directly affects:The safety, reliabilit
    01/29/2026
  • What’s the Difference Between Rectifier Transformers and Power Transformers?
    What is a Rectifier Transformer?"Power conversion" is a general term encompassing rectification, inversion, and frequency conversion, with rectification being the most widely used among them. Rectifier equipment converts input AC power into DC output through rectification and filtering. A rectifier transformer serves as the power supply transformer for such rectifier equipment. In industrial applications, most DC power supplies are obtained by combining a rectifier transformer with rectifier equ
    01/29/2026
Haven't found the right supplier yet? Let matching verified suppliers find you. Get Quotation Now
Haven't found the right supplier yet? Let matching verified suppliers find you.
Get Quotation Now
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.