What is the problem with cascading trips in electrical distribution panels?

Felix Spark
Field: Failure and maintenance
China

Very often, the lowest-level circuit breaker does not trip, but the upstream (higher-level) one does! This causes a large-scale power outage! Why does this happen? Today, we’ll discuss this issue.

Main Causes of Cascading (Unintended Upstream) Tripping

  • The main circuit breaker’s load capacity is smaller than the total load capacity of all downstream branch breakers.

  • The main breaker is equipped with a residual current device (RCD), while the branch breakers are not. When appliance leakage current reaches or exceeds 30 mA, the main breaker trips.

  • Mismatched protection coordination between two levels of breakers—use breakers from the same manufacturer whenever possible.

  • Frequently operating the main breaker under load causes contact carbonization, leading to poor contact, increased resistance, higher current, overheating, and eventual tripping.

  • The downstream breaker lacks proper protection settings to correctly identify faults (e.g., single-phase ground fault without zero-sequence protection).

  • Aging breakers result in prolonged shunt-trip operation time; replace them with breakers whose actual tripping time is shorter than that of the upstream breaker.

Solutions for Cascading Tripping

If an upstream circuit breaker trips due to cascading:

  • If a branch protection relay has operated but its breaker did not trip, manually open that branch breaker first, then restore the upstream breaker.

  • If none of the branch protections have operated, inspect all equipment within the affected area for faults. If no fault is found, close the upstream breaker and re-energize each branch circuit one by one. When energizing a particular branch causes the upstream breaker to trip again, that branch breaker is faulty and should be isolated for maintenance or replacement.

For a circuit breaker to trip, two conditions must be met:

  • The fault current must reach the set threshold.

  • The fault current must persist for the set time duration.

Therefore, to prevent cascading trips, both current settings and time settings must be properly coordinated between breaker levels.

For example:

  • The first-level (upstream) breaker has an overcurrent protection setting of 700 A with a time delay of 0.6 seconds.

  • The second-level (downstream) breaker should have a lower current setting (e.g., 630 A) and a shorter time delay (e.g., 0.3 seconds).

In this case, if a fault occurs within the protection zone of the second-level breaker, even if the fault current exceeds the upstream breaker’s threshold, the downstream breaker will clear the fault at 0.3 seconds—before the upstream breaker’s 0.6-second timer completes—thus preventing it from tripping and avoiding cascading.

This leads to several key points:

  • The same principle applies to all fault types—whether short-circuit or ground faults—coordination relies on both current magnitude and time duration.

  • Time coordination is often more critical because fault currents may simultaneously exceed the pickup settings of multiple breakers.

  • Even if settings appear correctly coordinated on paper, real-world performance may still result in cascading trips. Why? Because the total fault-clearing time includes not only the protection relay’s operating time but also the mechanical opening time of the breaker itself. This mechanical time varies by manufacturer and model. Since protection times are in milliseconds, even small differences can disrupt coordination.

For instance, in the above example, the second-level breaker is supposed to clear the fault in 0.3 seconds. But if its mechanical mechanism is slow and takes 0.4 seconds to fully interrupt the current, the upstream breaker may already detect that the fault has lasted 0.6 seconds and trip as well—causing a cascading event.

Therefore, to ensure proper coordination and prevent cascading trips, actual breaker operation times must be verified using relay protection test equipment. Coordination should be based on real measured total clearing times, not just theoretical settings.

Give a tip and encourage the author!
Recommended
Causes and Solutions for High Failure Rate of Distribution Transformers
1. Causes of Failure in Agricultural Distribution Transformers(1) Insulation DamageRural power supply typically utilizes 380/220V mixed supply systems. Due to the high proportion of single-phase loads, distribution transformers often operate under significant three-phase load imbalance. In many cases, the imbalance exceeds the permissible range specified in standards, causing premature aging, deterioration, and failure of transformer winding insulation, ultimately leading to burnout.When distrib
12/23/2025
5 Fault Diagnosis Techniques for Large Power Transformers
Transformer Fault Diagnosis Methods1. Ratio Method for Dissolved Gas AnalysisFor most oil-immersed power transformers, certain combustible gases are produced in the transformer tank under thermal and electrical stress. The combustible gases dissolved in oil can be used to determine the thermal decomposition characteristics of the transformer oil-paper insulation system based on their specific gas content and ratios. This technology was first used for fault diagnosis in oil-immersed transformers.
12/20/2025
Application of Fault Diagnosis Technology for 15kV Outdoor Vacuum Automatic Circuit Reclosers
According to statistics, the vast majority of faults on overhead power lines are transient, with permanent faults accounting for less than 10%. Currently, medium-voltage (MV) distribution networks commonly employ 15 kV outdoor vacuum automatic circuit reclosers in coordination with sectionalizers. This setup enables rapid restoration of power supply after transient faults and isolates faulty line segments in the event of permanent faults. Therefore, it is essential to monitor the operational sta
12/11/2025
In-Depth Analysis of Fault Protection Mechanisms for Generator Circuit Breakers
1.Introduction1.1 Basic Function and Background of GCBThe Generator Circuit Breaker (GCB), as the critical node connecting the generator to the step-up transformer, is responsible for interrupting current under both normal and fault conditions. Unlike conventional substation circuit breakers, the GCB directly withstands the massive short-circuit current from the generator, with rated short-circuit breaking currents reaching hundreds of kiloamperes. In large generating units, the reliable operati