AC contactors (with the electrical schematic code KM) are core electrical devices used to control the connection/disconnection between power supplies and loads in circuits, and they are also common equipment that electricians need to work with regularly. In practice, it is not uncommon to find that some peers make mistakes in selecting AC contactors, leading to improper sizing and subsequent persistent issues. Here, four of the most typical common mistakes are highlighted for reference.

I. Over-Reliance on Rated Current for Sizing

When selecting a suitable AC contactor based on the load, some electricians often only refer to the load’s rated current. This results in frequent burnout or melting of the AC contactor’s main contacts during actual operation.

The root cause of this fault is that the method of selecting an AC contactor (based on main contact capacity) using only the rated current is only applicable to purely resistive loads such as electric heating wires. For inductive loads like three-phase asynchronous motors, the starting current—affected by factors such as the starting method, type of driven load, and starting frequency—typically ranges from 4 to 7 times the rated current during the start-up phase (before stable operation). Therefore, it is crucial and necessary to take the load’s starting current into account when selecting an AC contactor.

II. Neglecting Coil Voltage Selection (Priority for Safe Voltage)

With the growing awareness of safe electricity use and compliance with safe operation standards, and to reduce unnecessary electric shock accidents, it has become a general trend to prioritize safe voltage levels (AC36V) for AC contactor coil voltages.

AC contactor.jpg

Thus, during the design, selection, and assembly of AC contactors, priority should be given to products with a coil voltage rating of AC36V. Every effort should be made to avoid situations where multiple coil voltage levels (such as AC380V and AC220V) coexist in the circuit.

III. Ignoring Auxiliary Contact Requirements

To reduce the number of other auxiliary devices (e.g., intermediate relays) and minimize the size of the electrical control system, the type of AC contactor should also be comprehensively determined based on the number of auxiliary contacts required for the contactor in the circuit.

For example, if the circuit requires a large number of auxiliary contacts for the AC contactor, it is more sensible to select CJX series AC contactors (which can be equipped with 2 or 4 additional auxiliary contacts) rather than CJT series AC contactors.

IV. Improper Control Connection with PLCs

Beyond the three factors mentioned above, a supplementary note concerns the control method of the AC contactor (coil). Currently, industrial control devices such as PLCs (Programmable Logic Controllers)—which facilitate centralized control—are increasingly widely used. However, many peers have directly connected AC contactor coils to PLC output terminals, leading to damage to internal PLC output components (relays, transistors, thyristors).

The cause of this fault is simply that the current during the contactor coil’s pull-in process exceeds the current-carrying capacity of the PLC’s output components. Therefore, when using a PLC to control an AC contactor, a relay should be used as an intermediate control link between the two.

Give a tip and encourage the author!
Recommended
How to Design 10kV Overhead Line Poles
How to Design 10kV Overhead Line Poles
This article combines practical examples to refine the selection logic for 10kV steel tubular poles, discussing clear general rules, design procedures, and specific requirements for use in 10kV overhead line design and construction.Special conditions (such as long spans or heavy ice zones) require additional specialized verifications based on this foundation to ensure safe and reliable tower operation.General Rules for Overhead Transmission Line Tower SelectionThe rational selection of overhead
James
10/20/2025
How to select a dry-type transformer?
How to select a dry-type transformer?
1. Temperature Control SystemOne of the main causes of transformer failure is insulation damage, and the greatest threat to insulation comes from exceeding the allowable temperature limit of the windings. Therefore, monitoring temperature and implementing alarm systems for transformers in operation are essential. The following introduces the temperature control system using the TTC-300 as an example.1.1 Automatic Cooling FansA thermistor is pre-embedded at the hottest spot of the low-voltage win
James
10/18/2025
How to Choose the Right Transformer?
How to Choose the Right Transformer?
Transformer Selection and Configuration Standards1. Importance of Transformer Selection and ConfigurationTransformers play a critical role in power systems. They adjust voltage levels to suit different requirements, enabling electricity generated at power plants to be efficiently transmitted and distributed. Improper transformer selection or configuration can lead to serious issues. For example, if the capacity is too small, the transformer may not support the connected load, causing voltage dro
James
10/18/2025
How to Choose Vacuum Circuit Breakers Correctly?
How to Choose Vacuum Circuit Breakers Correctly?
01 PrefaceIn medium-voltage systems, circuit breakers are indispensable primary components. Vacuum circuit breakers dominate the domestic market. Therefore, correct electrical design is inseparable from the proper selection of vacuum circuit breakers. In this section, we will discuss how to correctly select vacuum circuit breakers and common misconceptions in their selection.02 Interrupting Capacity for Short-Circuit Current Need Not Be Excessively HighThe short-circuit interrupting capacity of
James
10/18/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.