Isolation operating mechanism under 12kV environmental protection cabinet (air insulated without SF6 gas)

  • Isolation operating mechanism under 12kV environmental protection cabinet (air insulated without SF6 gas)

Key attributes

Brand Switchgear parts
Model NO. Isolation operating mechanism under 12kV environmental protection cabinet (air insulated without SF6 gas)
Rated voltage 12kV
Rated normal current 630A
Rated frequency 50/60Hz
Series VHK-J12

Product descriptions from the supplier

Description

The isolation operating mechanism under the VHK-J12 environmental protection cabinet is equipped with a VHK-J12 circuit breaker reclosing spring operating mechanism, and the isolation part is equipped with a RNHSG-07 compression spring isolation operating mechanism. The isolation machinery is a forward type, and the V operating mechanism is an inverted type, using a single rod mechanical structure to achieve interlocking with the lower door. Only when the main circuit is in the open state and reliably grounded can the interlocking return position open the lower door. The overall structure of the mechanism is compact, and the operation interlocking meets the five prevention requirements.
The operating mechanism complies with the relevant requirements of standards such as GB1984-2014, GB/T1022-2020, GB3804-2017, GB3906-2020, etc.

Operation of opening and closing the mechanism

Power transmission operation:
①. Close the door; ②. Insert the handle into the grounding operation hole of the G mechanism and operate counterclockwise to separate the locking/grounding of the lower door; ③. Insert the handle into the isolation operation hole of the G mechanism and operate counterclockwise to close the isolation switch; ④. Insert the handle into the energy storage operation hole of the V mechanism and operate clockwise to store energy in the circuit breaker; ⑤. Press the green button on the V mechanism to close the circuit breaker switch,
Power outage operation:
①. Press the red button on the V mechanism to open the circuit breaker switch; ②. Insert the handle into the isolation operation hole of the G mechanism and operate clockwise to open the isolation switch; ③. Insert the handle into the grounding operation hole of the G mechanism and operate clockwise to close the grounding switch; Only after the power outage and grounding are completed, can the lower door be opened.

Product Parameters

Serial Number

Item

Unit

Parameter

1

Voltage Level

V

AC/DC220; AC/DC110; DC48; DC24

2

Rated Power

W

40

3

Operating Environment

-40~+40

4

Power Frequency Withstand Voltage

kV

2/1min

5

Normal Operating Voltage Range of Closing Coil

UL

85%~110%

6

Normal Operating Voltage Range of Opening Coil

UL

65%~110%

7

Low Voltage Operating Range

UL

≤30% (no operation for 3 times of closing and opening)

8

Salt Spray Resistance Grade

h

96

Installation dimensions

FAQ
Q: What is the main function of the isolation operation mechanism?
A:

The main functions include four key points: ① Reliable isolation: Establishing a visible insulation gap between the maintenance part and the live part to ensure maintenance safety. ② Safety interlocking: Interlocking with cabinet doors, main switches, and grounding switches to prevent misoperation such as live isolation. ③ Circuit switching: It can open and close small current circuits such as voltage transformers excitation current under no-load conditions. ④ Environmental insulation: relying on air insulation, not using SF6 gas, no greenhouse effect or toxic decomposition products, in line with global low-carbon policies.)

Q: What is the core difference between the bottom mounted isolation operating mechanism and the top mounted isolation operating mechanism?
A:

The core differences are reflected in three aspects: ① Installation location: The lower isolation type is installed at the lower part of the cabinet, making on-site maintenance more convenient and not occupying space on the upper busbar; ② Force transmission method: using vertical downward transmission, mechanical operation is more stable, and the failure rate of jamming is lower; ③ Space adaptation: Especially suitable for compact environmental cabinets, the upper space can be reserved for other functional modules. Consistent with the upper isolation type in terms of core functions such as isolation, interlocking, and environmental protection, both meet the operational requirements of 12kV systems

Know your supplier
Online store
On-time delivery rate
Response time
100.0%
≤4h
Company overview
Workplace: 1000m² Total staff: Highest Annual Export(usD): 300000000
Workplace: 1000m²
Total staff:
Highest Annual Export(usD): 300000000
Services
Business Type: Sales
Main Categories: Low Voltage Electrical Apparatus/Instrument meters/Production equipment/Tester/High Voltage Electrical Apparatus/Electrical fittings/Equipment Parts
Whole life care manager
Whole-life care management services for equipment procurement, use, maintenance, and after-sales, ensuring safe operation of electrical equipment, continuous control, and worry-free electricity consumption.
The equipment supplier has passed platform qualification certification and technical evaluation, ensuring compliance, professionalism, and reliability from the source.

Related Products

Related Knowledges

  • Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
    Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
    01/30/2026
  • Neutral point grounding operation mode for 110kV~220kV power grid transformers
    The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
    01/29/2026
  • Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
    Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
    01/29/2026
  • Why Must a Transformer Core Be Grounded at Only One Point? Isn't Multi-Point Grounding More Reliable?
    Why Does the Transformer Core Need to Be Grounded?During operation, the transformer core, along with the metal structures, parts, and components that fix the core and windings, are all situated in a strong electric field. Under the influence of this electric field, they acquire a relatively high potential with respect to ground. If the core is not grounded, a potential difference will exist between the core and the grounded clamping structures and tank, which may lead to intermittent discharge.I
    01/29/2026
  • Understanding Transformer Neutral Grounding
    I. What is a Neutral Point?In transformers and generators, the neutral point is a specific point in the winding where the absolute voltage between this point and each external terminal is equal. In the diagram below, pointOrepresents the neutral point.II. Why Does the Neutral Point Need Grounding?The electrical connection method between the neutral point and earth in a three-phase AC power system is called theneutral grounding method. This grounding method directly affects:The safety, reliabilit
    01/29/2026
  • What’s the Difference Between Rectifier Transformers and Power Transformers?
    What is a Rectifier Transformer?"Power conversion" is a general term encompassing rectification, inversion, and frequency conversion, with rectification being the most widely used among them. Rectifier equipment converts input AC power into DC output through rectification and filtering. A rectifier transformer serves as the power supply transformer for such rectifier equipment. In industrial applications, most DC power supplies are obtained by combining a rectifier transformer with rectifier equ
    01/29/2026
Haven't found the right supplier yet? Let matching verified suppliers find you. Get Quotation Now
Haven't found the right supplier yet? Let matching verified suppliers find you.
Get Quotation Now
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.