Technical analysis report on transformer burn-out due to oil loss in Madagascar: root causes, failure mechanisms, and prevention strategies.
On April 25, 2026, the customer reported that after a local grid power outage and restoration, a QM unit in an SM66 cabinet failed to activate, and two internal fuse tubes were blown. Subsequent inspection revealed red oil level alarms on both Transformer 1 and Transformer 2, along with relay abnormalities. After venting, testing, and disassembly, it was confirmed that Transformer 1 was damaged due to oil loss causing switch burn-out, while Transformer 2 remained operational.



Oil loss reduced insulation capability. Under the overvoltage or lightning surge that occurred during grid restoration, insulation breakdown intensified, causing switch burn-out and ground fault, ultimately leading to fuse blowing and trip protection activation. Disassembly directly confirmed that oil loss caused the switch burn-out.


No oil leakage was found on site, yet the oil level continued to drop. Based on operation and maintenance records, the root cause of oil loss is determined as follows:
Venting without reseating the vent → tiny gap in seal → Breathing effect (hot: oil-gas mixture expelled; cold: air drawn in) → Continuous oil vapor loss → Slow oil level decline (no visible leakage) → Critically low oil level → Reduced insulation strength → Grid restoration / overvoltage / lightning surge → Insulation breakdown → Switch burn-out, ground fault → Fuse blowing, trip protection activation → Transformer 1 permanently damaged
Prepared by: Technical Analysis Team
Reviewed by:Noah
Date: June 10, 2026