Lightning Arrester Fault Rapid On-Site Disposal Solution

Wone Store
2yrs + staff 1000+m² US$300,000,000+ China

I. Disposal Objectives
Upon detecting a lightning arrester fault, conduct rapid, safe, and effective on-site disposal to isolate the faulty equipment. Minimize threats to power grid operation, equipment safety, buildings, and personnel. Create conditions for subsequent detailed maintenance or replacement.

II. Handling Principles

  1. Safety First:​ Always prioritize personal safety; strictly adhere to electrical safety regulations.
  2. Rapid Response:​ Initiate the disposal procedure immediately upon detecting fault indications or confirming a fault.
  3. Accurate Diagnosis:​ Quickly identify the fault type to provide the basis for targeted disposal.
  4. Effective Isolation:​ Ensure the faulty arrester is reliably disconnected from the operating system.
  5. Prevent Secondary Disasters:​ Take measures during disposal to avoid risks such as electric shock, fire, and escalation of equipment damage.

III. Fault Rapid Diagnosis Process (Preliminary On-Site)

  1. Safety Perimeter:​ Establish safety barriers or warning signs to restrict access by unauthorized personnel. Observe the site for obvious abnormalities (e.g., unusual sounds, odors, arcing, insulation gas leakage, contaminant splatter).
  2. Visual Inspection:​ (From a safe distance or after confirming equipment isolation)
    • Structure:​ Check the housing/sheds for cracks, breakage, scorch marks, heavy contamination, or icing.
    • Mechanical Components:​ Check mounting bolts, brackets for looseness, detachment, or corrosion; check grading rings for deformation, displacement, or damage.
    • Leads/Connections:​ Check leads (primary connections) for broken strands, burn marks, excessive slack or tension; check connection terminals, clamps for overheating (discoloration), melting, looseness, or corrosion.
    • Pressure Relief/Action Indicator:​ Check if the arrester body or base pressure relief device has operated (e.g., vent opened); observe counter or action indicator status (e.g., if the indicator flag has popped up).
    • Discharge Marks:​ Check the ground below the arrester or surrounding equipment for metallic dust or foreign objects caused by discharge.
  3. Condition Inference:​ (Correlate with patrol records, online monitoring data like leakage current, operation counts, etc., if available) to assist in judging aging or performance degradation.

IV. Fault-Specific Disposal Measures (Core of On-Site Rapid Disposal)

Fault Type

Specific Manifestations

On-Site Rapid Disposal Measures

Notes/Precautions

Mechanical Failure

* Loose/detached fasteners
* Shattered/cracked housing
* Deformed/displaced grading rings
* Abnormal pressure relief device

1. ​After De-energization!​ If loose, re-tighten with a torque wrench to specification.
2. If severe shattering, deformation, pressure relief device operation, or displacement posing a safety threat: ​Isolate power​ and recommend immediate replacement of that phase or all phases.
3. Clean up detached fragments to prevent secondary injury or short circuits.

* Minor surface scratches can be monitored; do not affect immediate operation safety.
* Severe mechanical damage is irreparable; requires replacement.

Deterioration/Damage Failure

* Heavily contaminated/iced housing (risk of flashover)
* Obvious scorch marks, tracking
* Severe acid erosion, chalking, cracking (aging)
* Pressure relief operation
* Frequent counter operation (possible valve block degradation)

1. For severe contamination/icing: If safely possible, attempt de-energized cleaning; otherwise, request an outage.
2. For scorching, tracking, severe aging, pressure relief operation, signs of valve block degradation: ​Isolate power immediately​ (open disconnector or breaker), remove the faulty arrester from service. Recommend replacement ASAP.
3. Record fault phenomena (photograph).

* Such faults usually indicate internal component damage; cannot be repaired on-site.
* Key target for on-site isolation.

Lead/Connection Fault

* Lead strands broken/burned through
* Melted/discolored/loose connection terminals/clamps
* Lead detached, causing ground short
* Lead too close to ground/other parts causing discharge

1. ​Isolate Power!
2. Inspect short-circuit point, disconnect the faulty connection.
3. Replace burned, broken leads and damaged clamps/terminals.
4. Remake reliable, tight electrical connections (ensure good contact surfaces, proper crimping or bolt torque).
5. Adjust leads to ensure sufficient safety clearances (phase-to-phase, phase-to-ground).

* This fault easily causes short-circuit trips or even fire; requires fastest isolation.
* ​Must​ check connection quality post-repair.

V. Emergency Response (Throughout the Process)

  1. Mandatory De-energization:​ Before any work, confirm the circuit powering the arrester is reliably disconnected (open relevant disconnectors/switches), verify de-energization (test for voltage), and install temporary grounding leads (or close grounding switches)! Strictly implement the switching operation ticket system.
  2. Personal Protection:
    • Wear full set of qualified insulating PPE (insulating gloves, boots, safety glasses, insulating clothing if necessary).
    • Use qualified insulated tools (voltage detector, grounding stick, hot stick, etc.).
    • Maintain safe working distance from live parts and grounded objects (based on voltage level).
  3. Fire Preparedness:​ Have appropriate fire extinguishers (e.g., dry powder, CO2) available onsite.
  4. Gas Leakage:​ For GIS or tank-type arresters, if internal fault suspected causing gas leakage: Immediately evacuate personnel to a safe area and notify specialized personnel. Avoid staying below the leak point.
  5. Information Reporting:​ Immediately report the fault situation, disposal progress, and required support to the superior dispatcher/management department.

VI. Post-Disposal Check & Restoration

  1. Work Completion Confirmation:​ Clear the work site, remove all temporary safety measures (except isolation devices), account for personnel and tools.
  2. Functional Test:​ (If restored after lead repair/simple tightening)
    • Use a qualified insulation resistance tester (megohmmeter) to measure arrester insulation resistance (terminal-to-terminal, terminal-to-ground); check if acceptable.
    • Check lead connection security and contact integrity.
    • Confirm grading rings/components are unimpeded.
  3. Energization Trial:​ (Upon confirmation)
    • Remove safety isolation measures (e.g., remove grounding leads).
    • Report to dispatcher and restore power as per instructions.
    • Closely monitor arrester status post-energization (e.g., temperature rise, sound, online leakage current data).

VII. Key Precautions

  • No Live Work:​ All work involving the arrester body must only occur ​after​ confirming de-energization and implementing safety measures.
  • Determine Fault Nature:​ Clearly determine before, during, and after disposal whether it's an arrester internal fault or damage caused by external factors (e.g., bird streamers, tree contact, foreign object short circuits).
  • Thorough Documentation:​ Detail fault phenomena, preliminary judgment, disposal actions, replaced parts, test data, restoration time, personnel involved, etc., to support later analysis (include photos/video).
  • Replacement Criteria:​ Arresters with internal damage (pressure relief operation, severe aging, flashover), severe mechanical damage, or valve block failure (e.g., abnormal frequent counter operation + abnormal leakage current) ​must be replaced entirely​ as internal repairs are impossible on-site.
  • Qualified Personnel Only:​ Disposal work must be performed by qualified, experienced personnel familiar with the equipment.
08/01/2025
Recommended
Smart Meter Solution: Analysis of Core Functions and Application Scenarios
I. Solution OverviewAs a core terminal device for grid digitalization, smart meters integrate high-precision metering, bidirectional communication, and intelligent analysis to provide real-time data support for power systems.This solution, developed in accordance with international and domestic standards and integrated with advanced communication technologies, builds a secure and reliable smart metering system. It is designed to meet diverse needs across residential, commercial, industrial, and
Beyond Metering: How Smart Meters Create Multidimensional Value for the Grid, Enterprises, and Households
Amid the digital transformation of power grids and the construction of new power systems, smart meters have evolved from traditional electricity metering tools into intelligent terminal nodes integrating metering, communication, control, and analytics. This solution provides an in-depth analysis of the core functions, technical pathways, and diverse applications of smart meters, offering comprehensive value reference for various users.​I. Core Technological Foundation: High-Precision Metering an
Smart Meter Full-Scope Solution: Precise Cost Reduction and Efficiency Enhancement, Empowering Energy Digital Upgrade
Overview​With the deep integration of energy transition and the digital economy, traditional electricity management models can no longer meet the demands for precision, intelligence, and low-carbon development. This solution leverages advanced smart meters and IoT technologies to build a smart electricity management system covering various scenarios such as residential, commercial and industrial, distributed energy, and electric vehicle charging. It aims to improve energy efficiency, ensure safe
Big Data Analysis of Smart Meters: Value, Benefits, and Application Prospects
I.Introduction​​Background of Energy and Smart Grids​Since the 21st century, the increasing depletion of non-renewable energy sources and worsening ecological environmental pollution have made energy issues a critical constraint on the development of human society. As an efficient and clean secondary energy source, electricity holds a significant position in the energy structure. To meet the growing demand for electricity and adapt to the diverse requirements of power development, building a saf
Seed Inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.