Winter Maintenance Essentials for GW5-Type Disconnectors

Felix Spark
Felix Spark
Field: Failure and maintenance
China

In substations with voltage levels of 110 kV and below, the GW5-type disconnector is widely used due to its simple structure, reliable contact performance, and self-cleaning contact function. Every winter, the failure rate of abnormal heating in GW5-type disconnectors shows an upward trend. Therefore, improving winter maintenance practices for GW5-type disconnectors (hereinafter referred to as “disconnectors”) and promptly detecting and addressing overheating faults are of critical importance to the safe and stable operation of the power grid.

1. Common Fault Types

1.1 Incomplete Closing

As temperatures drop in winter, the viscosity of lubricating oils and greases increases, raising friction in the transmission components of the disconnector’s operating mechanism. Additionally, rain and snow significantly increase the likelihood of corrosion in mechanical parts. These combined effects can alter the total operating stroke of the disconnector. If the disconnector fails to close fully, contact resistance rises, leading to abnormal heating once energized. Moreover, thick winter clothing worn by maintenance personnel can hinder precise manual operation, potentially causing incomplete closing.

1.2 Cracking of Conductive Clamping Plates

Compared to pure copper, brass contains more zinc, has a higher coefficient of thermal expansion, and greater resistance to deformation. Under large diurnal temperature variations in winter, conductive clamping plates, conductive tubes, and fastening bolts undergo varying degrees of thermal expansion and contraction. Brass clamping plates experience significant deformation stress, making them prone to cracking. This increases contact resistance and causes localized overheating. According to statistics from a power supply company, six overheating incidents caused by brass clamping plates occurred between November and December 2021.

1.3 Fracture of Copper-Aluminum Transition Clamps

When connecting copper conductive rods to aluminum conductors, copper-aluminum transition clamps—welded joints of copper and aluminum—are required. Traditional clamps use a transverse butt-weld design. Due to differences in material properties and thermal expansion coefficients, the weld zone becomes the weakest point under thermal cycling. Combined with frequent conductor swinging in windy winter conditions, this leads to metal fatigue, damage, overheating, and even fracture at the weld.

1.4 Damage to Tension Springs

Low winter temperatures reduce the elasticity of tension springs in disconnector contacts. Springs that are already corroded or damaged suffer particularly severe loss of tension. Uneven spring force reduces contact pressure between left and right contacts, decreasing effective contact area. In severe cases, the springs may inadvertently carry current. Since iron (common spring material) has high resistivity, this causes additional heating and further spring degradation, ultimately resulting in serious disconnector overheating.

1.5 Formation of Contaminant Layers

Winter air is dry and often polluted, especially in heavily contaminated areas with high dust levels. If excessive petroleum jelly (Vaseline) is applied to disconnector contacts, it readily adsorbs dust. Upon drying, this forms a hardened contaminant layer—a poor conductor—that causes significant overheating. During maintenance, aggressive grinding to remove such layers can damage the underlying silver plating, artificially increasing contact resistance and creating new overheating risks.

2. Key Winter Maintenance Practices for Disconnectors

2.1 Enhanced Operational Patrols

Early detection of overheating through regular patrols is essential:

  • Apply temperature-indicating labels (thermochromic stickers) to main current-carrying parts; inspect for melting or discoloration during patrols to identify overheating.

  • Conduct inspections during or after rain/snow: overheated areas will show steam, melted snow, or dry spots. Rising heat plumes above contact points are more visible in colder ambient temperatures.

  • Perform nighttime “lights-off” patrols to detect glowing or arcing at contact points.

  • Observe color changes and odors: abnormally heated aluminum turns whitish, copper becomes purplish-red, phase-color paint cracks or peels, and a burnt smell may be noticeable in severe cases.

2.2 Improve Maintenance Quality and Adopt Advanced Materials & Technologies

Promote the use of upgraded materials and techniques during maintenance:

  • Replace brass clamping plates with pure copper ones.

  • Use longitudinally crimped copper-aluminum transition clamps instead of transverse welded types.

  • Apply low-temperature-resistant lubricants.

  • Install improved contact designs featuring pressure springs or spring plates.

  • Strictly follow maintenance procedures: replace tension springs showing significant loss of elasticity or severe coating damage.

  • When cleaning contaminant layers from main contacts, avoid grinding to protect the silver plating. Instead, soak contacts in gasoline to soften deposits, then gently clean with lint-free cotton cloths.

Give a tip and encourage the author!
Recommended
Common Issues and Handling Measures for 145kV Disconnector Control Circuits
Common Issues and Handling Measures for 145kV Disconnector Control Circuits
The 145 kV disconnector is a critical switching device in substation electrical systems. It is used in conjunction with high-voltage circuit breakers and plays an important role in power grid operation:First, it isolates the power source, separating equipment under maintenance from the power system to ensure personnel and equipment safety;Second, it enables switching operations to change the system operating mode;Third, it is used to interrupt small-current circuits and bypass (loop) currents.Re
Felix Spark
11/20/2025
What are the six operating principles of disconnect switches?
What are the six operating principles of disconnect switches?
1. Operating Principle of the DisconnectorThe operating mechanism of the disconnector is connected to the active pole of the disconnector via a connecting tube. When the main shaft of the mechanism rotates 90°, it drives the insulating pillar of the active pole to rotate 90°. The bevel gears inside the base drive the insulating pillar on the other side to rotate in the opposite direction, thereby achieving opening and closing operations. The active pole, through inter-pole linkage tubes, drives
Echo
11/19/2025
36kV Disconnect Switch Selection Guide & Key Parameters
36kV Disconnect Switch Selection Guide & Key Parameters
Selection Guidelines for 36 kV Disconnect SwitchesWhen selecting the rated voltage, ensure that the disconnect switch’s rated voltage is equal to or higher than the nominal voltage of the power system at the installation point. For example, in a typical 36 kV power network, the disconnect switch must have a rated voltage of at least 36 kV.For rated current, selection should be based on the actual long-term load current. Generally, the switch’s rated current must be no less than the maximum conti
James
11/19/2025
Copper Conductor Size vs Temperature Rise in 145kV Disconnectors
Copper Conductor Size vs Temperature Rise in 145kV Disconnectors
The relationship between the temperature-rise current of a 145 kV disconnector and copper conductor size lies in balancing current-carrying capacity and heat dissipation efficiency. The temperature-rise current refers to the maximum continuous current a conductor can carry without exceeding its specified temperature rise limit, and the copper conductor size directly influences this parameter.Understanding this relationship begins with the physical properties of the conductor material. Copper’s c
Echo
11/19/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.