Typical alarms in gas insulated switchgear (GIS)

Edwiin
Edwiin
Field: Power switch
China

Gas Leak Indication

A gas density of approximately 90% or lower in each gas compartment and zone indicates the presence of a gas leak. This compromised gas density can gradually undermine the integrity of the insulation and operational performance of the equipment.

Insulation Rating Non - Compliance

When the gas density drops to around 80% or less in every gas compartment and zone, it means that the dielectric ratings of the apparatus can no longer be maintained. This situation poses a significant risk to the electrical insulation properties, potentially leading to electrical failures and safety hazards.

Low Circuit Breaker Operating Mechanism Pressure

A reduction in the pressure of the circuit breaker operating mechanism, whether it is pneumatic, hydraulic, or spring - based, is a critical concern.

When the pressure of the circuit breaker operating mechanism is too low, it indicates that the circuit breaker may no longer be able to open or close successfully. In such cases, the protection scheme is typically designed to prevent any further operation to avoid potential malfunctions or damage. It should be emphasized that, in most puffer - type circuit breakers, the gas not only serves as an insulator but also functions as a damper or cushion for the operating mechanism, highlighting the importance of maintaining proper gas pressure.

Loss of Motor Voltage for Operating Energy Supply

The loss of voltage to the motor of the circuit breaker mechanism, which supplies the necessary operating energy, can severely impact the normal operation of the circuit breaker. Without the proper electrical supply to this motor, the circuit breaker may be unable to perform its essential functions, such as opening or closing the electrical circuit.

Loss of DC Control Voltage for Circuit Breakers

The absence of the DC control voltage or voltages to the circuit breakers can disrupt the control and operation of the circuit breakers. This loss can prevent the circuit breakers from receiving the correct signals to operate, leading to a breakdown in the overall electrical system protection and control.

Loss of DC Control Voltage to the Annunciator

When the DC control voltage to the annunciator in the local control cabinet is lost, it can cause issues with the proper indication and monitoring of the circuit breaker's status. The annunciator plays a crucial role in alerting operators to various operational conditions, and its failure due to voltage loss can lead to delayed or missed detection of potential problems.

Pole Disagreement Operation

Pole disagreement operation occurs when the different poles of the circuit breaker do not operate in unison. This inconsistent operation can result in electrical unbalance, abnormal current flow, and potential damage to the circuit breaker and connected electrical equipment.

Excessive Motor Run - Time

An excessive run - time of the motor that supplies operating energy to the circuit breaker mechanism can be a sign of underlying problems. It may indicate issues such as mechanical jams, excessive friction, or control system malfunctions, which can overheat the motor and reduce its lifespan, as well as potentially affecting the proper operation of the circuit breaker.

Overcurrent in Motor Protection

The overcurrent operation of the protective device for the circuit breaker mechanism's motor is a clear indication of an abnormal electrical condition. This overcurrent can be caused by various factors, such as short circuits, overloads, or faulty components within the motor or its associated circuitry, and it requires immediate attention to prevent damage to the motor and ensure the safe operation of the circuit breaker.

Give a tip and encourage the author!
Recommended
SF6 Leak Detection Methods for GIS Equipment
SF6 Leak Detection Methods for GIS Equipment
For SF6 gas leakage rate detection in GIS equipment, when using the quantitative leak detection method, the initial SF6 gas content in the GIS equipment must be accurately measured. According to relevant standards, the measurement error should be controlled within ±0.5%. The leakage rate is calculated based on changes in gas content after a period of time, thereby evaluating the sealing performance of the equipment.In qualitative leak detection methods, direct visual inspection is commonly used,
Oliver Watts
10/31/2025
Why RMUs Fail? Condensation & Gas Leak Explaine
Why RMUs Fail? Condensation & Gas Leak Explaine
1. IntroductionRing main units (RMUs) are primary power distribution equipment that house load switches and circuit breakers within a metal or non-metal enclosure. Due to their compact size, simple structure, excellent insulation performance, low cost, easy installation, and fully sealed design [1], RMUs are widely used in medium- and low-voltage power systems across China’s grid network [2], especially in 10 kV distribution systems. With economic growth and increasing electricity demand, requir
Felix Spark
10/31/2025
Preventing RMU Insulation Failures: Key Causes
Preventing RMU Insulation Failures: Key Causes
1. Insufficient Creepage Distance or Air ClearanceInadequate creepage distance and air gaps are the main causes of insulation failure and accidents in solid-insulated ring main units (RMUs). Especially in drawer-type cabinets, manufacturers reduce cabinet size by minimizing space for circuit breakers, significantly decreasing isolation distances between plug contacts and ground. Without adequate reinforcement of insulation structure, such designs increase the risk of flashover under overvoltage
Felix Spark
10/31/2025
What Is Discharge Load for Energy Absorption in Power Systems?
What Is Discharge Load for Energy Absorption in Power Systems?
Discharge Load for Energy Absorption: A Key Technology for Power System ControlDischarge load for energy absorption is a power system operation and control technology primarily used to address surplus electrical energy caused by load fluctuations, power source faults, or other disturbances in the grid. Its implementation involves the following key steps:1. Detection and ForecastingFirst, real-time monitoring of the power system is conducted to collect operational data, including load levels and
Echo
10/30/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.