What are the Low Voltage Fuses?

05/19/2025

A fuse is a current-interrupting device that breaks or opens a circuit by melting its element when the current in the circuit surpasses a specific value. Fuses are predominantly categorized into two types: high-voltage fuses and low-voltage fuses. Low-voltage fuses can be further divided into two subtypes: semi-enclosed or rewirable fuses, and fully enclosed cartridge fuses.
Rewirable Fuses
Rewirable fuses, commonly referred to as kit-kat fuses, are widely utilized in residential wiring and small-current circuits. These fuses feature a porcelain base with fixed contacts, through which live wires are connected. The fuse carrier, an independent component, can be easily inserted into or removed from the base.
The fuse element is typically crafted from lead, tin, copper, or a tin-lead alloy. The current required to melt the fusing element is usually twice the normal operating current. When multiple (more than two or three) fuse elements are employed, they must be adequately spaced apart. The de-rating factor of the fuse element ranges from 0.7 to 0.8. In the event of a fault, the fuse element melts, interrupting the circuit.
Once the fuse element has melted, it can be removed and replaced with a new one. By reinserting the fuse into the base, the electrical supply can be restored. Rewirable fuses offer the advantage of safe fuse element replacement at a minimal cost.
However, rewirable fuses also have several drawbacks:
  • Unreliable Operation: Selecting an appropriately sized element is crucial for the fuse's proper functioning. The element can deteriorate due to oxidation, which occurs as a result of continuous heating.
  • Low Rupturing Capacity: The breaking capacity of rewirable fuses is limited. For instance, a fuse with a normal current capacity of 16A may have a breaking capacity of 2kA, while a 200A fuse might have a breaking capacity of 4kA.
  • Slow Operation Speed: These fuses have a relatively long arcing time, and they lack additional means for arc extinction.
  • Flame and Fire Risk: The rewirable feature may lead to the use of inexpensive wires for protecting devices against short circuits and overloads, increasing the risk of fire.
Enclosed or Cartridge Type Fuses
In enclosed or cartridge type fuses, the fuse element is housed within a sealed container, held in place by metal contacts. These fuses are further classified into D-types and link types. Link type cartridge fuses can be sub - categorized into knife blade or bolted designs.
D - Types Cartridge Fuse
D - types cartridge fuses are non - interchangeable. The main components of this fuse include the fuse base, adapter ring, cartridge, and fuse cap. The cartridge slides into the fuse cap, which is then attached to the fuse base. The fuse element makes contact with the tip of the fuse base, completing the circuit via the fuse link.
The standard ratings of fuses include 6, 16, 32, and 63 amperes. The breaking capacity of fuse elements is 4kA for 2A and 4A fuses, and 16kA for 6A or 63A fuses. This type of fuse has no reported disadvantages and offers highly reliable operation.
Link Type Cartridge or High Rupturing Capacity (HRC) Fuses
The fuse frame is constructed from steatite (a powdered mineral) or ceramic materials, chosen for their excellent mechanical strength. Brass caps secure the fuse element within the ceramic body, fastened with specialized force to withstand high internal pressure during fault conditions.
End contacts are welded to the metallic caps, ensuring robust electrical connectivity. The space between the fuse element and the cartridge body is filled with quartz powder, which serves as an arc-extinguishing medium. This powder absorbs heat generated by short-circuit currents, converting into a high-resistance state that suppresses restriking voltage and rapidly quenches arcs, enhancing the fuse’s rupturing capability and reliability.
The fuse element is constructed from silver or copper and connected via a tin joint, which regulates the fuse’s temperature during short-circuit events. Silver has a melting point of 980°C, while tin melts at 240°C. During a system fault, short-circuit current first passes through the tin joint, which restricts current flow through the silver element.
The fusing factor of the link fuse is 1.45, though some specialized fuses may have a lower fusing factor of 1.2. Common types include knife-blade and bolted designs.

The Electricity Encyclopedia is dedicated to accelerating the dissemination and application of electricity knowledge and adding impetus to the development and innovation of the electricity industry.

What is the difference between a dielectric and an insulator?
What is the difference between a dielectric and an insulator?
Dielectrics and insulators are distinguished primarily by their applications. One of the main differences is that a dielectric can store electrical energy by becoming polarized in an electric field, whereas an insulator resists the flow of electrons to prevent current conduction. Other key differences between them are outlined in the comparison chart below.Definition of DielectricA dielectric material is a type of insulator that contains few or no free electrons. When subjected to an electric fi
08/30/2025
Transformer Connection Sections
Transformer Connection Sections
Transformer Connection DesignationsThe transformer connection designation indicates the winding connection method and the phase relationship between the line voltages of the primary and secondary windings. It consists of two parts: letters and a number. The letters on the left denote the connection configurations of the high-voltage and low-voltage windings, while the number on the right is an integer from 0 to 11.This number represents the phase shift of the low-voltage winding's line voltage r
08/15/2025
Automatic Reclosing Scheme in Transmission Systems
Automatic Reclosing Scheme in Transmission Systems
Automatic Reclosing Scheme for Transmission SystemsThe automatic reclosing system is a series-connected network designed to reduce operating costs and enhance network reliability. Extra-high voltage (EHV) transmission lines are used to transmit large amounts of power, on the order of thousands of megawatts (MW), and therefore should not be interrupted at all costs. Although faults on these overhead lines are common, the power transmitted through them should not be interrupted for long periods du
08/07/2025
Transformer operation and maintenance
Transformer operation and maintenance
Transformer Operating TemperatureDuring operation, transformers generate copper losses and iron losses, both of which are converted into heat, causing the transformer’s temperature to rise. Most transformers in China use Class A insulation. Due to heat transfer characteristics, significant temperature differences exist between different components during operation: winding temperature is the highest, followed by the core, and then the temperature of the insulating oil (with upper-layer oil being
07/31/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!