• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Transformer Operating Temperature, Voltage Variation, and Parallel Operation Requirements

Encyclopedia
Encyclopedia
Field: Encyclopedia
0
China

Transformer Operating Temperature

During operation, transformers generate copper losses and iron losses, both of which are converted into heat, causing the transformer’s temperature to rise. Most transformers in China use Class A insulation. Due to heat transfer characteristics, significant temperature differences exist between different components during operation: winding temperature is the highest, followed by the core, and then the temperature of the insulating oil (with upper-layer oil being hotter than lower-layer oil). The allowable operating temperature of a transformer is determined by the temperature of its upper-layer oil. For Class A insulated transformers, under normal operating conditions with an ambient temperature of 40°C, the maximum temperature of the upper-layer oil must not exceed 85°C.

Temperature Rise During Transformer Operation

The temperature difference between the transformer and its surrounding medium is referred to as the transformer’s temperature rise. Due to the notable temperature variations across different components, this can impact the transformer’s insulation. Additionally, as the transformer’s temperature increases, winding losses also rise. Therefore, it is necessary to specify allowable temperature rises for each component under rated load conditions. For Class A insulated transformers, when the ambient temperature is 40°C, the allowable temperature rise for upper-layer oil is 55°C, and for windings, it is 65°C.

Transformer.jpg

Voltage Variation Range During Transformer Operation

In power systems, fluctuations in grid voltage cause corresponding variations in the voltage applied to transformer windings. If the grid voltage is lower than the rated voltage of the transformer’s used tap, no damage to the transformer occurs. However, if the grid voltage exceeds the rated voltage of the used tap, it will lead to increased winding temperatures, higher reactive power consumption by the transformer, and waveform distortion in the secondary coil. Thus, the transformer’s supply voltage should generally not exceed 5% of the tap’s rated voltage.

Requirements for Transformer Parallel Operation

Transformer parallel operation involves connecting the primary windings of two or more transformers to a common power source and their secondary windings in parallel to supply a shared load. In modern power systems, as system capacity grows, parallel operation of transformers has become essential.Power transformers operating in parallel must meet the following requirements:

  • Their transformation ratios must be equal, with an allowable deviation of ±0.5%.

  • Their short-circuit voltages must be equal, with an allowable deviation of ±10%.

  • Their connection groups must be identical.

Give a tip and encourage the author!
Recommended
Adjustment and Precautions for H61 Oil Power 26kV Electric Transformer Tap Changers
Adjustment and Precautions for H61 Oil Power 26kV Electric Transformer Tap Changers
Preparatory Work Before Adjusting the Tap Changer of H61 Oil Power 26kV Electric Transformer Apply for and issue a work permit; carefully fill out the operation ticket; conduct a simulation board operation test to ensure the operation is error-free; confirm the personnel who will carry out and supervise the operation; if load reduction is required, notify affected users in advance. Before construction, power must be disconnected to take the transformer out of service, and voltage testing must be
James
12/08/2025
H59/H61 Transformer Failure Analysis and Protection Measures
H59/H61 Transformer Failure Analysis and Protection Measures
1.Causes of Damage to Agricultural H59/H61 Oil-Immersed Distribution Transformers1.1 Insulation DamageRural power supply commonly uses a 380/220V mixed system. Due to the high proportion of single-phase loads, H59/H61 oil-immersed distribution transformers often operate under significant three-phase load imbalance. In many cases, the degree of three-phase load imbalance far exceeds the limits permitted by operational regulations, causing premature aging, deterioration, and eventual failure of th
Felix Spark
12/08/2025
Top 5 Faults Found in H61 Distribution Transformers
Top 5 Faults Found in H61 Distribution Transformers
Five Common Defects of H61 Distribution Transformers1.Lead Wire DefectsInspection Method: The three-phase DC resistance imbalance rate significantly exceeds 4%, or one phase is essentially open-circuited.Remedial Measures: The core should be lifted for inspection to locate the defective area. For poor contacts, re-polish and tighten the connection. Poorly welded joints should be re-welded. If the welding surface area is insufficient, it should be enlarged. If the lead wire cross-section is inade
Felix Spark
12/08/2025
How Voltage Harmonics Affect H59 Distribution Transformer Heating?
How Voltage Harmonics Affect H59 Distribution Transformer Heating?
The Impact of Voltage Harmonics on Temperature Rise in H59 Distribution TransformersH59 distribution transformers are among the most critical equipment in power systems, primarily functioning to convert high-voltage electricity from the power grid into low-voltage electricity required by end users. However, power systems contain numerous nonlinear loads and sources, which introduce voltage harmonics that adversely affect the operation of H59 distribution transformers. This article will discuss i
Echo
12/08/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.