SF6 Gas Density Monitoring System Components and Failure Modes

The SF6 gas density monitoring system comprises three main components:

  • Gas Density Monitor
  • Gas Pipes with Manifold (if applicable)
  • Pressure (or Density) Gauge

Each of these components can experience different types of failure modes.

Gas Density Monitor

Gas density monitors are susceptible to several failure modes:

• Mechanical Disturbances: The operational density values at which the switch operates can change due to mechanical settings being disturbed by vibrations.
• Corrosion of Contacts: Inadequate environmental protection can lead to contact corrosion. This could result from poor design or improper installation of enclosures.
• Temperature Sensitivity: For low-temperature applications, selecting the appropriate density monitor is crucial. Liquefaction in the reference gas volume can cause incorrect signals. General-purpose solutions may not provide sufficient accuracy for temperature compensation across the entire working range of the equipment.
• Brazing Defects: Poor brazing of bourdon tubes can lead to SF6 gas leakage. Environmental factors can also cause joints to corrode, leading to leaks.

Gas Pipes and Manifolds

Gas pipes and manifolds introduce multiple joints into the system, often made on-site and not as reliable as factory-made joints. These joints are exposed to external environments, making them susceptible to:

• Corrosion: Deterioration due to environmental exposure.
• Thermal Cycling: Stress from temperature fluctuations can weaken joints over time, eventually causing leaks.

Pressure Gauges

Pressure gauges are installed to confirm the presence of SF6 gas and monitor its pressure. Key considerations include:
• Environmental Exposure: Gauges are typically mounted outdoors and face harsh conditions. They are connected through pipes and manifolds that are prone to leakage.
• Calibration Drift: Over time, the calibration of the gauges can be disturbed, leading to incorrect pressure readings.
• Reduced Joints: To minimize potential leak points, it is desirable to use indicators designed with fewer joints. Such indicators are available as part of integrated density monitors, reducing the risk of leakage.

Summary

In summary, the SF6 gas density monitoring system's reliability depends on the proper functioning of its three main components: gas density monitors, gas pipes with manifolds, and pressure gauges. Each component has specific failure modes that must be addressed through careful selection, installation, and maintenance practices. Ensuring robust design and minimizing joint counts can significantly reduce the likelihood of failures and improve overall system performance.

Edwiin

Online condition monitoring device (OLM2) on high voltage Circuit Breakers
Online condition monitoring device (OLM2) on high voltage Circuit Breakers
This device is capable of monitoring and detecting various parameters according to the specifications outlined:SF6 Gas Monitoring:Utilizes a specialized sensor for measuring SF6 gas density.Capabilities include measuring gas temperature, monitoring SF6 leak rates, and calculating the optimal date for refilling.Mechanical Operation Analysis:Measures operational times for closing and opening cycles.Evaluates primary contacts separation speed, damping, and contact overtravel.Identifies signs of mec
Edwiin
02/13/2025
Anti pumping function in circuit breakers operating mechanism
Anti pumping function in circuit breakers operating mechanism
The anti - pumping function stands as a crucial characteristic of control circuits. In the absence of this anti - pumping function, assume that a user connects a maintained contact within the closing circuit. When the circuit breaker is closed onto a fault current, the protective relays will promptly trigger a tripping action. However, the maintained contact in the closing circuit will attempt to close the breaker (once again) onto the fault. This repetitive and dangerous process is referred to
Edwiin
02/12/2025
Ageing phenomena of current pass blades in high voltage disconnector switch
Ageing phenomena of current pass blades in high voltage disconnector switch
This failure mode has three primary origins:Electrical Causes: The switching of currents, such as loop currents, can lead to localized wear. At higher currents, an electric arc may burn at a specific spot, increasing the local resistance. As more switching operations occur, the contact surface wears down further, causing an increase in resistance.Mechanical Causes: Vibrations, often due to wind, are the main contributors to mechanical aging. These vibrations cause abrasion over time, leading to
Edwiin
02/11/2025
Initial Transient Recovery Voltage (ITRV) for high voltage circuit breakers
Initial Transient Recovery Voltage (ITRV) for high voltage circuit breakers
Transient Recovery Voltage (TRV) stress similar to that encountered during a short-line fault can also occur due to the busbar connections on the supply side of a circuit breaker. This specific TRV stress is known as Initial Transient Recovery Voltage (ITRV). Given the relatively short distances involved, the time to reach the first peak of ITRV is typically less than 1 microsecond. The surge impedance of the busbars within a substation is generally lower compared to that of overhead lines.The f
Edwiin
02/08/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!