Maintenance and Diagnostic Analysis of Current Transformers in GIS Equipment

07/07/2025

I'm Oliver, with 8 years of experience in current transformer testing. These are all practical experiences, shared with you
1 Maintenance of Current Transformers
Having been in the business of current transformer testing for 8 years, I know a thing or two about their maintenance! The maintenance of current transformers is divided into minor repairs, intermediate repairs, and major overhauls.
Minor repairs mainly involve opening the cover (if necessary) and changing the oil, usually carried out once a year. Intermediate repairs include inspecting the transformer body, cleaning, drying, and all the items of minor repairs. Typically, the transformer needs to be disassembled and sent back to the manufacturer for inspection, done once every five to ten years. A major overhaul means replacing some or all of the windings, including all the items of minor and intermediate repairs, scheduled once every fifteen to twenty years.
(1) Overview of Minor Repairs
Minor repairs are further divided into two types: without opening the cover and with opening the cover.
  • Minor repair without opening the cover: Use a clean cloth or cotton to wipe the porcelain bushing. If it's really dirty, you can use alcohol or gasoline. Then check if the porcelain bushing has cracks, damage, or enamel peeling. See if all the bolts are loose; if so, tighten them evenly. Check if the oil level is normal; the oil level shouldn't be lower than the specified minimum. Inspect if the base is rusted; if it is, clean it and apply paint. If the V - type oil level glass tube is cracked or leaking oil, replace it immediately. Check for oil leakage in all parts. Also, check if the connection between the breather and the upper cover is firm and well - sealed, and ensure the wiring is tight and has good contact.
  • Minor repair with opening the cover is applicable in the following situations:
    • The oil level is lower than the minimum, and oil needs to be replenished.
    • The oil gauge glass tube is broken and leaking oil.
    • The waterproof plug sealing ring is damaged and needs replacement due to oil leakage.
    • The upper cover sealing ring of the oil conservator is damaged and needs replacement.
    • The oil fails the laboratory test and needs to be changed.
(2) Overview of Intermediate Repairs
It's best to carry out intermediate repairs indoors, and the room should be clean. If the repair takes a long time and can't be finished in a day, the transformer body should be sealed in qualified oil. Additionally, the lifting equipment must be able to support the entire weight of the current transformer. Before disassembling, take an oil sample from the lower drain plug for testing.
(3) Overview of Major Overhauls
A major overhaul is a thorough repair. If your unit can't handle it, hire a professional maintenance team. A major overhaul includes all the items of minor and intermediate repairs. The equipment is completely disassembled and inspected, and unqualified parts are replaced to restore the equipment's performance. If necessary, technical modifications are made to improve the mechanical performance.
2 Fault Analysis and Diagnosis of Current Transformers
When a current transformer fails, analyze the cause and location based on fault status and parameter changes. Amid numerous state parameters, extract characteristic info for diagnosis. The abnormal equipment condition from a fault is a “fault symptom”. Diagnosis, a form of state recognition, judges fault type and location via these symptoms.
Current transformer diagnosis has four steps:
  • Preventive tests: Follow Regulations for Preventive Tests of Power Equipment to measure winding/end - shield insulation resistance, dielectric loss factor, capacitance, and conduct oil - dissolved gas chromatography. Analyzing results reveals issues like water ingress, moisture, or poor manufacturing.
  • Partial discharge measurement: Routine methods miss discharge defects, but discharge tests clearly identify defect types with good results.

  • Online monitoring & infrared thermometry: Combined with internal structure and operating status, it effectively checks for loose joints.
  • Visual inspection: A running transformer’s “buzzing” often stems from a secondary circuit open/poor terminal contact (with spark discharge). Open secondary circuits cause terminal overvoltage, risking insulation breakdown and harm—so they’re strictly prohibited! If the “buzz” comes from loose iron - core screws, the sound grows with load, overheating the transformer, aging insulation, and causing grounding/breakdown. Surface dirt/dust - caused sounds turn to “cracking” discharges on rainy/foggy days (possibly leading to corona); severe discharges need enhanced monitoring and outage requests.
3 Conclusion
We've detailed the maintenance and diagnosis of GIS current transformers. Current transformers are transformer - type devices based on electromagnetic principles and are commonly used in power systems. Mastering their maintenance and diagnosis methods is crucial for maintaining the normal operation of equipment and ensuring the smooth progress of power work! 

Hey there! I'm an electrical engineer specializing in Failure and Maintenance. I've dedicated my career to ensuring the seamless operation of electrical systems. I excel at diagnosing complex electrical failures, from malfunctioning industrial motors to glitchy power distribution networks. Using state - of - the - art diagnostic tools and my in - depth knowledge, I pinpoint issues quickly. On this platform, I'm eager to share my insights, exchange ideas, and collaborate with fellow experts. Let's work together to enhance the reliability of electrical setups.

Transformer Detection, Testing, Maintenance and Servicing
Transformer Detection, Testing, Maintenance and Servicing
Transformer testing, inspection, and maintenance are essential tasks to ensure normal operation and extend the service life of transformers. Below are some recommended steps:Visual Inspection: Regularly inspect the transformer's exterior, including the enclosure, cooling system, and oil tank. Ensure the enclosure is intact, free from corrosion, damage, or leakage.Insulation Resistance Testing: Use an insulation resistance tester to check the transformer's insulation system. Verify that the insul
Vziman
08/29/2025
What are the Common Operation Faults of Indoor Load Switches?
What are the Common Operation Faults of Indoor Load Switches?
Common operational faults of indoor load switches primarily concentrate on three core aspects: mechanical operation, electrical performance, insulation, and arc extinguishing. These issues can be broadly categorized as follows and are often related to component aging, environmental influences, or improper operation.1.Mechanical Faults The most typical issue is abnormal operation during opening and closing. This includes excessive resistance, jamming, or even refusal to operate when manually turn
08/27/2025
What should be done if the fuse element on the high-voltage side of the transformer melts?
What should be done if the fuse element on the high-voltage side of the transformer melts?
If the fuse element on the high-voltage side of the transformer blows or the circuit trips, the first step is to determine whether one phase, two phases, or all three phases are interrupted. This can be determined according to the fault symptoms as shown in the following table:When a fuse element blows, first check whether the high-voltage side fuse or the lightning arrester gap has short-circuited to ground. If no abnormalities are found during external inspection, it can be concluded that an i
08/26/2025
Usage and Maintenance of Fuses
Usage and Maintenance of Fuses
Use and MaintenanceIn low-voltage power distribution systems, fuses are protective electrical devices. Widely used for power grid and electrical equipment protection, fuses automatically cut off circuits when short circuits or overloads occur in the grid or equipment, preventing damage to electrical devices and preventing accidents from spreading.A fuse consists of an insulating base (or support), contacts, and a fuse element. The fuse element is the primary working component, acting like a spec
08/26/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!