Pamahalaan ug Analisis sa Pagsiguro sa mga Current Transformers sa GIS Equipment

Oliver Watts
Oliver Watts
Larangan: Pagsusi ug Paghunahuna
China

Si Oliver kini, may 8 ka tuig na kalihukan sa pagsulay sa current transformer. Kini mao ang tanang praktikal nga kalandangan, gipasabot nimo
1 Pagsulay sa Current Transformers

Ang akong pagkalihukan sa pagsulay sa current transformer adunay 8 ka tuig, ug naka-iskedyar na ang ilang maintenance! Ang pagsulay sa current transformers mahimong minor repairs, intermediate repairs, o major overhauls.

Ang minor repairs kasagaran maglakip sa pagbukas sa cover (kung kinahanglan) ug pagbag-o sa oil, kasagaran gibuhat isip taon. Ang intermediate repairs naglakip sa pag-sulay sa lawas sa transformer, paglinis, pag-dry, ug tanan nga items sa minor repairs. Kasagaran, ang transformer kinahanglan i-disassemble ug ibalik sa manufacturer aron masulayan, gibuhat isip lima hangtod sa sampel ka tuig. Ang major overhaul nagsulti sa pagbag-o sa uban o tanan nga windings, kasama ang tanan nga items sa minor ug intermediate repairs, gisuon isip labindala hangtod sa duol ka tuig.

(1) Overview of Minor Repairs

Ang minor repairs nahimong duha ka klase: walay pagbukas sa cover ug may pagbukas sa cover.

  • Minor repair walay pagbukas sa cover: Gamiton ang clean nga cloth o cotton aron maputli ang porcelain bushing. Kon dili maayo, pwede gamiton ang alcohol o gasoline. Pagkatapos, sulayi kung adunay cracks, damage, o enamel peeling sa porcelain bushing. Sulayi kung ang tanan nga bolts adunay loose; kon usa, tight even. Sulayi kung ang oil level normal; ang oil level dili dapat mas baba sa minimum nga gi-specify. Sulayi kung adunay rust sa base; kon usa, linisin ug i-paint. Kon ang V - type oil level glass tube adunay crack o leaking oil, palitan agad. Sulayi kung adunay oil leakage sa tanan nga bahin. Sulayi usab kung ang connection sa breather ug upper cover firm ug well-sealed, ug sigurado kung ang wiring tight ug maayo ang contact.

  • Minor repair may pagbukas sa cover applicable sa sumala nga sitwasyon:

    • Ang oil level mas baba sa minimum, ug kailangan og additional nga oil.

    • Ang oil gauge glass tube broken ug leaking oil.

    • Ang waterproof plug sealing ring damaged ug kailangan og replacement tungod sa oil leakage.

    • Ang upper cover sealing ring sa oil conservator damaged ug kailangan og replacement.

    • Ang oil failed sa laboratory test ug kailangan og change.

(2) Overview of Intermediate Repairs

Mas maayo nga i-carry out ang intermediate repairs sa indoor, ug ang kwarto dapat clean. Kon ang repair mahimong matagamtam ug dili makatapos sa usa ka adlaw, ang lawas sa transformer dapat seal sa qualified nga oil. Usab, ang lifting equipment dapat maka-support sa buhata nga weight sa current transformer. Bago i-disassemble, kuhaa ang sample sa oil gikan sa lower drain plug aron masulayan.

(3) Overview of Major Overhauls

Ang major overhaul usa ka thorough nga repair. Kon ang imong unit dili makaya, hirea ang professional nga maintenance team. Ang major overhaul naglakip sa tanan nga items sa minor ug intermediate repairs. Ang equipment completely i-disassemble ug i-inspect, ug ang dili qualified nga parts palitan aron maisulbad ang performance sa equipment. Kon necessary, technical modifications gihimo aron mapadako ang mechanical performance.

2 Fault Analysis and Diagnosis of Current Transformers

Kon ang current transformer fail, analyze ang cause ug location batasan sa fault status ug parameter changes. Sa daghang state parameters, extract ang characteristic info para sa diagnosis. Ang abnormal nga condition sa equipment gikan sa fault usa ka “fault symptom”. Ang diagnosis, usa ka form sa state recognition, judge ang fault type ug location pinaagi niining symptoms.

Ang current transformer diagnosis adunay apat ka steps:

  • Preventive tests: Follow ang Regulations for Preventive Tests of Power Equipment aron masulayan ang winding/end - shield insulation resistance, dielectric loss factor, capacitance, ug conduct oil - dissolved gas chromatography. Analyzing results reveals issues like water ingress, moisture, o poor manufacturing.

  • Partial discharge measurement: Ang routine methods miss discharge defects, pero ang discharge tests clearly identify defect types with good results.

  • Online monitoring & infrared thermometry: Combined with internal structure and operating status, it effectively checks for loose joints.

  • Visual inspection: A running transformer’s “buzzing” often stems from a secondary circuit open/poor terminal contact (with spark discharge). Open secondary circuits cause terminal overvoltage, risking insulation breakdown and harm—so they’re strictly prohibited! If the “buzz” comes from loose iron - core screws, the sound grows with load, overheating the transformer, aging insulation, and causing grounding/breakdown. Surface dirt/dust - caused sounds turn to “cracking” discharges on rainy/foggy days (possibly leading to corona); severe discharges need enhanced monitoring and outage requests.

3 Conclusion

Gi-detail nami ang maintenance ug diagnosis sa GIS current transformers. Ang current transformers mao ang mga device nga based sa electromagnetic principles ug commonly used sa power systems. Mahimong crucial ang pag-master sa ilang maintenance ug diagnosis methods aron maprotektahan ang normal nga operasyon sa equipment ug ensure ang smooth progress sa power work! 

Maghatag og tip ug pagsalig sa author
Gipareserbado
10kV RMU Common Faults & Solutions Guide

Gidagway sa mga Karaniwang Sayop ug Solusyon alang sa 10kV RMU
10kV RMU Common Faults & Solutions Guide Gidagway sa mga Karaniwang Sayop ug Solusyon alang sa 10kV RMU
Mga Isyu sa Pag-apply ug mga Pamaagi sa Pag-handle para sa 10kV Ring Main Units (RMUs)Ang 10kV ring main unit (RMU) usa ka kasagaran nga pananglitan sa elektrikal nga distribusyon sa urban nga mga network sa kuryente, gamiton sa paghatag ug distribusyon sa medium-voltage nga kuryente. Sa aktwal nga operasyon, mahimong madungog ang uban pang mga isyu. Ania ang mga kasagaran nga problema ug ang naka-corresponding nga mga pamaagi sa pag-handle.I. Mga Electrical Faults Internal Short Circuit o Pobre
Echo
10/20/2025
Mga Tipo sa High-Voltage Circuit Breaker ug Guide sa Mga Pagsayop
Mga Tipo sa High-Voltage Circuit Breaker ug Guide sa Mga Pagsayop
High-Voltage Circuit Breakers: Classification and Fault DiagnosisAng mga high-voltage circuit breakers mao ang mga kritikal nga protective devices sa mga power systems. Sila nag-intererrupt sa current ngadto sa pag-occur og fault, nang maprevent ang pag-damage sa equipment gikan sa overloads o short circuits. Sa wala pa, tungod sa long-term operation ug uban pang factors, ang mga circuit breakers mahimong mag-develop og faults nga angay nga i-diagnose ug troubleshoot niadtong maayo nga panahon.I
Felix Spark
10/20/2025
10 Prohibitions para sa Pag-install ug Paggamit sa Transformer!
10 Prohibitions para sa Pag-install ug Paggamit sa Transformer!
10 Prohibitions for Transformer Installation and Operation! Dili ang pag-install sa transformer nang labi ka layo—ayaw ihatag kini sa mga remote nga bukid o wilderness. Ang labi ka dako nga distansya wala lang magwasto sa cables apan adunay mas daghan pa nga line losses, ug mahadlok usab ang pag-manage ug maintenance. Dili ang pagpili sa capacity sa transformer nang random. Importante nga ang tama nga capacity. Kon ang capacity mubo, ang transformer mahimong mag-overload ug madaling mapuslan—ang
James
10/20/2025
Paunsa ang mga Transformer nga walay Lanas sa Maayo nga Paraan?
Paunsa ang mga Transformer nga walay Lanas sa Maayo nga Paraan?
Ang mga Prosidyur sa Pagmamaintain sa Dry-Type Transformers Ibutang ang standby transformer sa operasyon, buksan ang circuit breaker sa low-voltage side sa transformer nga gi-maintain, tangtangon ang control power fuse, ug ihapad ang "DO NOT CLOSE" sign sa switch handle. Buksan ang high-voltage side circuit breaker sa transformer nga gi-maintain, isara ang grounding switch, fully discharge ang transformer, lock ang high-voltage cabinet, ug ihapad ang "DO NOT CLOSE" sign sa switch handle. Para sa
Felix Spark
10/20/2025
Inquiry
Pangutana
Pangutana sa IEE-Business Application
Pangita og mga equipment gamit ang IEE-Business app asa asa ug kailan man sugad og pagkuha og solusyon pagsulay sa mga eksperto ug pagpadayon sa industriya nga pakisayran suportahan ang imong proyekto sa kuryente ug negosyo