What is Circuit Breaker Maintenance?

Encyclopedia
Field: Encyclopedia
0
China


What is Circuit Breaker Maintenance?


Circuit Breaker Maintenance Definition


Circuit breaker maintenance involves switching off, isolating, and regularly checking and servicing the breaker to ensure reliable operation.


13286e5b1757901385d7813530013028.jpeg


Bulk Oil Circuit Breaker


For bulk oil circuit breaker, we should check contact burning. If burning is very light, remove the burn beads and polish the surface. If burning is quite heavy, replace the tips and arcing ring by new set. We should loose and tight the tips few times before final tightening is done.


Additionally, check the extinguishing chamber. Remove it from the breaker unit, wash it with insulating oil, and keep it upside down. Replace any severely burned or damaged parts.


Next, clean and lubricate the circuit breaker mechanism. Remove rust with non-fluffy cotton cloths and lubricate the mechanism, including the gear wheel, with high-grade grease. Remember to lubricate the friction clutch. For minimum oil circuit breaker (MOCB), clean the insulator and remove any carbon deposits with Trichloroethylene or Acetone. Follow the manufacturer’s manual for detailed instructions.


Check the locking pins of the tie rods and all foundation bolts and electrical terminal connections at the circuit breaker power circuit every six months. Tighten them properly after removing any oxide coating.


The proper adjustment of auxiliary switch by ensuring correct NO NC contacts at breaker OFF and ON condition must be checked half yearly and in addition to that the auxiliary switch’s contacts should be cleaned properly with help of hard brushes.


The spring charging motor and mechanism should also be cleaned and associated bearing should also be lubricated half yearly.


Minimum Oil Circuit Breaker (MOCB) Maintenance


In case of MOCB, the breaker should be checked monthly for oil leakage and oil level. If oil leakage is found it must be attended and for low oil level top up oil up to desire level.


Perform a visual inspection of the circuit breaker, its operating mechanism, painting quality, and mechanism kiosk door gasket every quarter. Take proper action if any damage is found.


The oil dash pot in operating mechanism must be checked for oil leakage quarterly if leakage is found, replace the defective and damaged O – rings.It is also highly recommended to ensure the prescribed duty cycle of operation of the breaker including reclosing annually.


Air Blast Circuit Breaker Maintenance


For air blast circuit breaker there are some special cares to be taken in addition to general instruction for maintenance of operating mechanism. Actually for operating mechanisms and for other some features the maintenance processes and schedules are same for all oil circuit breaker, air circuit breaker, SF6 circuit breaker and vacuum circuit breaker.


In air circuit breaker, the air leakage should be checked as and when it is required. If leakage is found, plug the leakage.


The grading capacitors must be checked for oil leakage monthly. If leakage found plug it.Yearly, dew point of the operating air at the outlet of the air dryer should be measured with the help of Dew Point Meter or Hygro Meters.


SF6 and Vacuum Circuit Breaker


As we said earlier for operating mechanisms and for some other features the maintenance processes and schedules are same for all oil circuit breaker, air circuit breaker, SF6 circuit breaker and vacuum circuit breaker.


In addition to that in SF6 CB some extra care to be taken.SF6 circuit breaker must be checked for SF6 gas leakage, if unwanted SF6 low gas pressure alarm comes. This is efficiently done by gas leakage detector.If the circuit breaker is provided with gradient capacitors, these must be checked for oil leakage monthly. If leakage found plug it.Dew point of SF6 should be checked with the help of dew point meter or hygro meters in every 3 to 4 years interval.

  

 


Give a tip and encourage the author!

Recommended

Rockwill Powers Cambodia’s Battambang Solar-Storage Project
The Battambang Conch PV + Energy Storage Power Station in Cambodia has successfully completed its grid-connected trial operation. The project utilized medium-voltage switchgear supplied by Rockwill Intelligent Electric Co., Ltd. Despite numerous challenges—including an extremely tight delivery schedule—Rockwill Intelligent delivered high-quality products and exceptional service throughout project execution, earning consistent praise from the client.Located in Battambang, Cambodia, the Battambang
12/24/2025
Classification of Equipment Defects for Relay Protection and Safety Automatic Devices in Substations
In daily operations, various equipment defects are inevitably encountered. Whether maintenance personnel, operation and maintenance staff, or specialized management personnel, all must understand the defect classification system and adopt appropriate measures according to different situations.According to Q/GDW 11024-2013 "Operation and Management Guide for Relay Protection and Safety Automatic Devices in Smart Substations," equipment defects are classified into three levels based on severity an
12/15/2025
Under What Conditions Will the Line Circuit Breaker Auto-Reclosing Signal Be Locked Out?
The line circuit breaker auto-reclosing signal will be locked out if any of the following conditions occur:(1) Low SF6 gas pressure in circuit breaker chamber at 0.5MPa(2) Insufficient energy storage in circuit breaker operating mechanism or low oil pressure at 30MPa(3) Busbar protection operation(4) Circuit breaker failure protection operation(5) Line distance protection zone II or zone III operation(6) Short lead protection operation of circuit breaker(7) Presence of remote tripping signal(8)
12/15/2025
Application of Auto-Reclosing Residual Current Protective Devices in Lightning Protection for Communication Power Supplies
1. Power Interruption Problems Caused by RCD False Tripping During Lightning StrikesA typical communication power supply circuit is shown in Figure 1. A residual current device (RCD) is installed at the power supply input terminal. The RCD primarily provides protection against electrical equipment leakage currents to ensure personal safety, while surge protective devices (SPDs) are installed on power supply branches to protect against lightning intrusions. When lightning strikes occur, the senso
12/15/2025
Related Products
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.