مفتاح قاطع خارجي بغاز السف الـ 252 كيلوفولت مع خزان غير مكهرب

  • 225kV 220kV 230kV 245kV 252kV Outdoor Dead Tank SF6 Circuit Breaker direct supply

السمات الرئيسية

العلامة التجارية ROCKWILL
سلسلة RHD
الوصف

Description

As China's first source factory specializing in GIS tank circuit breakers.225kV, 230kV, 245kV,252kV Outdoor Dead Tank SF6 Circuit Breaker is an outdoor (50Hz) high-voltage power transmission and transformation equipment, which is used to divide and combine rated working current, fault current or conversion lines to achieve protection, control and operation of the power system.

The circuit breaker arc extinguisher adopts the principle of double air chamber and double-action self-energy arc extinguishing, with compact structure, and its technical performance has reached the international level and the domestic advanced level, which is the replacement product of the traditional compressed sulfur hexafluoride circuit breaker. The product is composed of a circuit breaker, a current transformer and an inlet and outlet bushing, and is equipped with a full spring operating mechanism, which can not only carry out split-phase operation, but also realize three-phase electrical linkage.

The product has passed all type tests according to the IEC standards, and has the characteristics of excellent breaking ability, reliable insulation, strong flow capacity, and long electrical and mechanical life.

Main feature

  • Excellent breaking performance:The self-energy arc extinguishing chamber can meet all terminal short circuits, breaking near area faults, out-of-step faults, out-of-phase grounding faults and line charging currents, etc., with small electrical wear and low arc voltage. The rated short-circuit current can be interrupted 20 times in a row.

  • Reliable insulation and strong flow capacity:SF6 gas has superior insulation performance and simple and reliable insulation structure. There are few current-carrying contact parts, few contact points, and strong flow capacity.

  • The structure design is unique:The arc extinguisher has simple structure, few components, light weight, small operating work, high mechanical reliability, and a mechanical life of 10,000 times; The insulation structure of the product has been optimized and designed, which greatly reduces the amount of gas, is conducive to environmental protection, and the structural design is integrated and has strong seismic ability.

  • Easy to install, maintain and overhaul:The overall commissioning of the factory, rapid on-site assembly, and operation with an integrated spring mechanism, no oil leakage and air leakage, no daily energy storage monitoring requirements, so it is easy to maintain.

Technical specifications

 Among these, some SF6 tank circuit breakers cover non-standard voltage levels including 225kV, 230kV, 245kV, 275kV, 330kV, 345kV, 400kV, 756kV, and 800kV, with a rated short-circuit breaking current of 50kA or 63kA, and offer customization services.

Name

Unit

Technical Parameters

Rated Voltage

kV

252

Rated Current

A

4000

Rated Frequency

Hz

50/60

First - Pole - To - Clear Factor

/

1.3

Rated Short - circuit Breaking Current

kA

50

Rated Short - time Withstand Current (Effective Value)

kA/s

50/3

Rated Peak Withstand Current

kA

125

1min Rated Power -frequency Withstand Voltage

Phase - to - phase/Ground

kV

460

Break - port

460(+146)

Rated Lightning ImpulseWithstand (1.2/50μs Peak Value)

Phase - to - phase/Ground

1050

Break - port

1050(+206)

SF6 Gas (Gauge Pressure, 20

°C


Rated Gas Pressure

MPa

0.60

Alarm Gas Pressure

0.55±0.015

Lock - out Gas Pressure

0.50±0.015

Rated operating sequence

/

O - 0.3s - CO - 180s - CO

Rated out - of - step breaking current

kA

12.5

Short - line - fault breaking current

kA

L90:45, L70:35

Out - of - phase grounding breaking current

kA

43.5

Rated line - charging breaking current

A

125

Number of breaking operations for rated short - circuit breaking current

times

20

Mechanical life

times

10000

Mechanism/operation mode

/

Spring Operating Mechanism/Single - phase Operation

 

225kV/230kV/245kV/252kV Outdoor Dead Tank SF6 Circuit Breaker - Operating Environment Conditions

  • Ambient Temperature:-30℃ ~ +40℃(standard configuration);optional -40℃ ~ +45℃ for extreme cold/hot regions (with special insulation and heating/cooling design).

  • Altitude:≤ 1000m above sea level(standard);for altitudes 1000m~2000m, insulation performance is enhanced by derating to ensure voltage resistance.

  • Relative Humidity:Monthly average ≤ 90%(at 25℃);daily average ≤ 95%;no condensation on the tank surface.

  • Wind Speed:Maximum sustained wind speed ≤ 34m/s(12-level wind);instantaneous gust ≤ 50m/s.

  • Atmospheric Conditions:Suitable for areas free of severe dust, corrosive gases(such as sulfur dioxide, ammonia), flammable gases, and conductive pollutants;for coastal or industrial areas with salt fog, optional anti-corrosion coating and sealed insulation structure are available.

  • Seismic Resistance:Seismic intensity ≤ 8 degrees;horizontal acceleration ≤ 0.2g, vertical acceleration ≤ 0.1g(conforms to GB/T 13540 or IEC 60068-2-57 standards).

  • Rainfall:Maximum rainfall intensity ≤ 100mm/h;no long-term heavy rain erosion on the upper casing.


مكتبة موارد الوثائق Dead Tank Circuit Breaker

Restricted
Dead Tank Circuit Breakers Catalog Dead Tank Circuit Breakers Catalog
Catalogue
English
PDF
Public.
RHD-40.5 Dead tank SF6 gas circuit breaker FLYER RHD-40.5 Dead tank SF6 gas circuit breaker FLYER
Brochure
English
Restricted
2026 RHD Dead tank SF6 gas circuit breaker 2026 RHD Dead tank SF6 gas circuit breaker
Catalogue
English
PDF
Public.
Rockwill Electric Group Profile Rockwill Electric Group Profile
Brochure
English
Public.
RHD-245 SF6 Gas Dead tank Circuit Breaker FLYER RHD-245 SF6 Gas Dead tank Circuit Breaker FLYER
Brochure
English
Public.
RHD-362 SF6 Gas Dead tank Circuit Breaker FLYER RHD-362 SF6 Gas Dead tank Circuit Breaker FLYER
Brochure
English
Public.
RHD-420 SF6 Gas Dead tank Circuit Breaker FLYER RHD-420 SF6 Gas Dead tank Circuit Breaker FLYER
Brochure
English
Public.
RHD-362 SF6 Gas Dead tank Circuit Breaker RHD-362 SF6 Gas Dead tank Circuit Breaker
Drawings
English

الأسئلة الشائعة

الهيكل المتكامل للخزان:

  • الهيكل المتكامل للخزان: يتم تغليف غرفة إخماد القوس الكهربائي، والوسط العازل، والمكونات ذات الصلة داخل خزان معدني مملوء بغاز عازل (مثل سداسي فلوريد الكبريت) أو زيت عازل. هذا يشكل مساحة مستقلة نسبيًا ومغلقة بشكل فعال، مما يمنع العوامل البيئية الخارجية من التأثير على المكونات الداخلية. هذه التصميم يعزز أداء العزل وموثوقية الجهاز، مما يجعله مناسبًا لبيئات خارجية قاسية مختلفة.

تخطيط غرفة إخماد القوس الكهربائي:

  • تخطيط غرفة إخماد القوس الكهربائي: عادة ما يتم تثبيت غرفة إخماد القوس الكهربائي داخل الخزان. يتم تصميم هيكلها ليكون مدمجًا، مما يسمح بإخماد القوس الكهربائي بكفاءة في مساحة محدودة. بناءً على مبادئ وإجراءات إخماد القوس المختلفة، قد تختلف البنية الخاصة لغرفة إخماد القوس الكهربائي، ولكن بشكل عام تتضمن المكونات الرئيسية مثل نقاط الاتصال، والنواظير، والمواد العازلة. تعمل هذه المكونات معًا لضمان إخماد القوس الكهربائي بسرعة وكفاءة عند انقطاع التيار بواسطة القاطع.

آلية التشغيل:

  • آلية التشغيل: تشمل الآليات الشائعة آليات التشغيل باليناصيب وأجهزة التشغيل الهيدروليكية.

  • آلية التشغيل باليناصيب: هذه الآلية بسيطة في تركيبها، وذات موثوقية عالية، وسهلة الصيانة. تقوم بتشغيل عمليات الفتح والإغلاق للقاطع عن طريق تخزين وإطلاق طاقة اليناصيب.

  • آليات التشغيل الهيدروليكية: توفر هذه الآلية مزايا مثل قوة الإخراج العالية والعمل السلس، مما يجعلها مناسبة للقواطع ذات الفئة العالية من الجهد والتيار.

يجب السيطرة على معدل تسرب غاز الSF₆ بحيث يكون في مستوى منخفض للغاية، عادةً لا يتجاوز 1% سنوياً. يعتبر غاز الSF₆ غازاً دفيئاً قوياً، حيث يبلغ تأثيره الدفيئي 23,900 مرة أكثر من ثاني أكسيد الكربون. في حالة حدوث تسرب، يمكن أن يؤدي ذلك ليس فقط إلى تلوث البيئة ولكن أيضاً إلى انخفاض في ضغط الغاز داخل غرفة إخماد القوس الكهربائي، مما يؤثر على أداء وموثوقية القاطع.

لرصد تسرب غاز الSF₆، يتم عادة تركيب أجهزة كشف التسربات على قواطع الدائرة ذات الخزان. هذه الأجهزة تساعد على تحديد أي تسربات بسرعة حتى يمكن اتخاذ الإجراءات المناسبة لحل المشكلة.

خلال عمليات التشغيل العادية وقطع الدائرة للقاطع الكهربائي، يمكن أن يتحلل غاز الSF₆ وينتج عنه منتجات تحلل مختلفة مثل SF₄، S₂F₂، SOF₂، HF، وSO₂. غالباً ما تكون هذه المنتجات التحللية مسببة للتآكل أو سامة أو مهيجة، ولذلك يتطلب الأمر مراقبتها.إذا تجاوزت تركيز هذه المنتجات التحللية حدوداً معينة، فقد يشير ذلك إلى تفريغات غير طبيعية أو أعطال أخرى داخل غرفة إخماد القوس الكهربائي. من الضروري القيام بالصيانة والتعامل المناسب في الوقت المناسب لمنع المزيد من الأضرار للمعدات ولحماية صحة الموظفين.

تعرف على مورّدك

متجر إلكتروني
نسبة التسليم في الوقت المحدد
وقت الاستجابة
100.0%
≤4h
نظرة عامة على الشركة
مكان العمل: 108000m² إجمالي الموظفين: 700+ أعلى قيمة تصدير سنوية (دولار): 150000000
خدمات
نوع العمل: تصميم/تصنيع/المبيعات
الفئات الرئيسية: محول كهربائي/محطات التحويل المجمعة والغرف الكهربائية سابقة التجهيز/العزل الواقي من البرق والحماية من الصواعق/أجهزة كهربائية ذات فولطية عالية/لوحات كهربائية وأجهزة تحكم/محول كهربائي
إرسال الاستفسار
+86
انقر لتحميل الملف
تنزيل
الحصول على تطبيق IEE Business
استخدم تطبيق IEE-Business للعثور على المعدات والحصول على حلول والتواصل مع الخبراء والمشاركة في التعاون الصناعي في أي وقت ومن أي مكان - دعمًا كاملاً لتطوير مشاريعك الكهربائية والأعمال
تسجيل الدخول
أو المتابعة باستخدام
هل أنت جديد هنا؟
تسجيل