| Бренд | ROCKWILL |
| Серия | RHD |
| Номинальное наибольшее напряжение | 362kV |
| Номинальный наибольший ток | 3150~5000 A |
| Номинальное выдерживаемое напряжение грозового импульса | 1175/1290 kV |
| Номинальный ток отключения короткого замыкания | 40~63 kA |
| Номинальная частота | 50/60 Hz |
Description
As China's first source factory specializing in GIS tank circuit breakers.225kV, 230kV, 245kV,252kV Outdoor Dead Tank SF6 Circuit Breaker is an outdoor (50Hz) high-voltage power transmission and transformation equipment, which is used to divide and combine rated working current, fault current or conversion lines to achieve protection, control and operation of the power system.
The circuit breaker arc extinguisher adopts the principle of double air chamber and double-action self-energy arc extinguishing, with compact structure, and its technical performance has reached the international level and the domestic advanced level, which is the replacement product of the traditional compressed sulfur hexafluoride circuit breaker. The product is composed of a circuit breaker, a current transformer and an inlet and outlet bushing, and is equipped with a full spring operating mechanism, which can not only carry out split-phase operation, but also realize three-phase electrical linkage.
The product has passed all type tests according to the IEC standards, and has the characteristics of excellent breaking ability, reliable insulation, strong flow capacity, and long electrical and mechanical life.
Main feature
Excellent breaking performance:The self-energy arc extinguishing chamber can meet all terminal short circuits, breaking near area faults, out-of-step faults, out-of-phase grounding faults and line charging currents, etc., with small electrical wear and low arc voltage. The rated short-circuit current can be interrupted 20 times in a row.
Reliable insulation and strong flow capacity:SF6 gas has superior insulation performance and simple and reliable insulation structure. There are few current-carrying contact parts, few contact points, and strong flow capacity.
The structure design is unique:The arc extinguisher has simple structure, few components, light weight, small operating work, high mechanical reliability, and a mechanical life of 10,000 times; The insulation structure of the product has been optimized and designed, which greatly reduces the amount of gas, is conducive to environmental protection, and the structural design is integrated and has strong seismic ability.
Easy to install, maintain and overhaul:The overall commissioning of the factory, rapid on-site assembly, and operation with an integrated spring mechanism, no oil leakage and air leakage, no daily energy storage monitoring requirements, so it is easy to maintain.
Technical specifications
Among these, some SF6 tank circuit breakers cover non-standard voltage levels including 225kV, 230kV, 245kV, 275kV, 330kV, 345kV, 400kV, 756kV, and 800kV, with a rated short-circuit breaking current of 50kA or 63kA, and offer customization services.
Name |
Unit |
Technical Parameters |
|
Rated Voltage |
kV |
252 |
|
Rated Current |
A |
4000 |
|
Rated Frequency |
Hz |
50/60 |
|
First - Pole - To - Clear Factor |
/ |
1.3 |
|
Rated Short - circuit Breaking Current |
kA |
50 |
|
Rated Short - time Withstand Current (Effective Value) |
kA/s |
50/3 |
|
Rated Peak Withstand Current |
kA |
125 |
|
1min Rated Power -frequency Withstand Voltage |
Phase - to - phase/Ground |
kV |
460 |
Break - port |
460(+146) |
||
Rated Lightning ImpulseWithstand (1.2/50μs Peak Value) |
Phase - to - phase/Ground |
1050 |
|
Break - port |
1050(+206) |
||
SF6 Gas (Gauge Pressure, 20 °C |
Rated Gas Pressure |
MPa |
0.60 |
Alarm Gas Pressure |
0.55±0.015 |
||
Lock - out Gas Pressure |
0.50±0.015 |
||
Rated operating sequence |
/ |
O - 0.3s - CO - 180s - CO |
|
Rated out - of - step breaking current |
kA |
12.5 |
|
Short - line - fault breaking current |
kA |
L90:45, L70:35 |
|
Out - of - phase grounding breaking current |
kA |
43.5 |
|
Rated line - charging breaking current |
A |
125 |
|
Number of breaking operations for rated short - circuit breaking current |
times |
20 |
|
Mechanical life |
times |
10000 |
|
Mechanism/operation mode |
/ |
Spring Operating Mechanism/Single - phase Operation |
|
Ambient Temperature:-30℃ ~ +40℃(standard configuration);optional -40℃ ~ +45℃ for extreme cold/hot regions (with special insulation and heating/cooling design).
Altitude:≤ 1000m above sea level(standard);for altitudes 1000m~2000m, insulation performance is enhanced by derating to ensure voltage resistance.
Relative Humidity:Monthly average ≤ 90%(at 25℃);daily average ≤ 95%;no condensation on the tank surface.
Wind Speed:Maximum sustained wind speed ≤ 34m/s(12-level wind);instantaneous gust ≤ 50m/s.
Atmospheric Conditions:Suitable for areas free of severe dust, corrosive gases(such as sulfur dioxide, ammonia), flammable gases, and conductive pollutants;for coastal or industrial areas with salt fog, optional anti-corrosion coating and sealed insulation structure are available.
Seismic Resistance:Seismic intensity ≤ 8 degrees;horizontal acceleration ≤ 0.2g, vertical acceleration ≤ 0.1g(conforms to GB/T 13540 or IEC 60068-2-57 standards).
Rainfall:Maximum rainfall intensity ≤ 100mm/h;no long-term heavy rain erosion on the upper casing.
Монолитная конструкция резервуара: Камера гашения дуги, изоляционная среда и связанные компоненты заключены в металлический резервуар, заполненный изоляционным газом (например, гексафторидом серы) или изоляционным маслом. Это образует относительно независимое и герметичное пространство, эффективно предотвращая влияние внешних факторов на внутренние компоненты. Такой дизайн улучшает изоляционные характеристики и надежность оборудования, делая его пригодным для различных суровых условий окружающей среды.
Расположение камеры гашения дуги: Камера гашения дуги обычно устанавливается внутри резервуара. Её конструкция разработана таким образом, чтобы быть компактной, обеспечивая эффективное гашение дуги в ограниченном пространстве. В зависимости от различных принципов и технологий гашения дуги, конкретная конструкция камеры гашения дуги может различаться, но, как правило, включает ключевые компоненты, такие как контакты, сопла и изоляционные материалы. Эти компоненты работают вместе, чтобы обеспечить быстрое и эффективное гашение дуги при прерывании тока выключателем.
Механизм управления: Общие механизмы управления включают пружинные механизмы и гидравлические механизмы.
Пружинный механизм: Этот тип механизма прост в конструкции, высоко надежен и легко обслуживается. Он осуществляет операции открытия и закрытия выключателя за счет накопления и высвобождения энергии пружин.
Гидравлический механизм: Этот механизм обладает преимуществами, такими как высокая выходная мощность и плавность работы, что делает его подходящим для выключателей высокого напряжения и больших токов.
Скорость утечки газа SF₆ должна быть контролируемой на крайне низком уровне, обычно не превышающем 1% в год. Газ SF₆ является мощным парниковым газом, с эффектом потепления, в 23 900 раз превышающим эффект углекислого газа. В случае утечки это может не только вызвать环境污染, но и привести к снижению давления газа в камере дугогашения, что влияет на производительность и надежность выключателя.
Для контроля утечек газа SF₆, как правило, на баковых выключателях устанавливаются устройства для обнаружения утечек газа. Эти устройства помогают своевременно определить наличие утечек, чтобы можно было принять соответствующие меры по их устранению.
В процессе нормальной работы и прерывания выключателя SF₆ газ может разлагаться, образуя различные продукты разложения, такие как SF₄, S₂F₂, SOF₂, HF и SO₂. Эти продукты разложения часто являются коррозионно-активными, токсичными или раздражающими, поэтому их необходимо контролировать.Если концентрация этих продуктов разложения превышает определенные пределы, это может указывать на аномальные разряды или другие неисправности в камере гашения дуги. Необходимо своевременно проводить техническое обслуживание и устранение неисправностей, чтобы предотвратить дальнейшее повреждение оборудования и обеспечить безопасность персонала.