| Thương hiệu | ROCKWILL |
| Chuỗi | RHD |
| Điện áp tối đa định mức | 362kV |
| Dòng điện tối đa định mức | 3150~5000 A |
| Điện áp chịu đựng xung sét | 1175/1290 kV |
| Dòng điện cắt ngắn mạch định mức | 40~63 kA |
| Tần số định mức | 50/60 Hz |
Description
As China's first source factory specializing in GIS tank circuit breakers.225kV, 230kV, 245kV,252kV Outdoor Dead Tank SF6 Circuit Breaker is an outdoor (50Hz) high-voltage power transmission and transformation equipment, which is used to divide and combine rated working current, fault current or conversion lines to achieve protection, control and operation of the power system.
The circuit breaker arc extinguisher adopts the principle of double air chamber and double-action self-energy arc extinguishing, with compact structure, and its technical performance has reached the international level and the domestic advanced level, which is the replacement product of the traditional compressed sulfur hexafluoride circuit breaker. The product is composed of a circuit breaker, a current transformer and an inlet and outlet bushing, and is equipped with a full spring operating mechanism, which can not only carry out split-phase operation, but also realize three-phase electrical linkage.
The product has passed all type tests according to the IEC standards, and has the characteristics of excellent breaking ability, reliable insulation, strong flow capacity, and long electrical and mechanical life.
Main feature
Excellent breaking performance:The self-energy arc extinguishing chamber can meet all terminal short circuits, breaking near area faults, out-of-step faults, out-of-phase grounding faults and line charging currents, etc., with small electrical wear and low arc voltage. The rated short-circuit current can be interrupted 20 times in a row.
Reliable insulation and strong flow capacity:SF6 gas has superior insulation performance and simple and reliable insulation structure. There are few current-carrying contact parts, few contact points, and strong flow capacity.
The structure design is unique:The arc extinguisher has simple structure, few components, light weight, small operating work, high mechanical reliability, and a mechanical life of 10,000 times; The insulation structure of the product has been optimized and designed, which greatly reduces the amount of gas, is conducive to environmental protection, and the structural design is integrated and has strong seismic ability.
Easy to install, maintain and overhaul:The overall commissioning of the factory, rapid on-site assembly, and operation with an integrated spring mechanism, no oil leakage and air leakage, no daily energy storage monitoring requirements, so it is easy to maintain.
Technical specifications
Among these, some SF6 tank circuit breakers cover non-standard voltage levels including 225kV, 230kV, 245kV, 275kV, 330kV, 345kV, 400kV, 756kV, and 800kV, with a rated short-circuit breaking current of 50kA or 63kA, and offer customization services.
Name |
Unit |
Technical Parameters |
|
Rated Voltage |
kV |
252 |
|
Rated Current |
A |
4000 |
|
Rated Frequency |
Hz |
50/60 |
|
First - Pole - To - Clear Factor |
/ |
1.3 |
|
Rated Short - circuit Breaking Current |
kA |
50 |
|
Rated Short - time Withstand Current (Effective Value) |
kA/s |
50/3 |
|
Rated Peak Withstand Current |
kA |
125 |
|
1min Rated Power -frequency Withstand Voltage |
Phase - to - phase/Ground |
kV |
460 |
Break - port |
460(+146) |
||
Rated Lightning ImpulseWithstand (1.2/50μs Peak Value) |
Phase - to - phase/Ground |
1050 |
|
Break - port |
1050(+206) |
||
SF6 Gas (Gauge Pressure, 20 °C |
Rated Gas Pressure |
MPa |
0.60 |
Alarm Gas Pressure |
0.55±0.015 |
||
Lock - out Gas Pressure |
0.50±0.015 |
||
Rated operating sequence |
/ |
O - 0.3s - CO - 180s - CO |
|
Rated out - of - step breaking current |
kA |
12.5 |
|
Short - line - fault breaking current |
kA |
L90:45, L70:35 |
|
Out - of - phase grounding breaking current |
kA |
43.5 |
|
Rated line - charging breaking current |
A |
125 |
|
Number of breaking operations for rated short - circuit breaking current |
times |
20 |
|
Mechanical life |
times |
10000 |
|
Mechanism/operation mode |
/ |
Spring Operating Mechanism/Single - phase Operation |
|
Ambient Temperature:-30℃ ~ +40℃(standard configuration);optional -40℃ ~ +45℃ for extreme cold/hot regions (with special insulation and heating/cooling design).
Altitude:≤ 1000m above sea level(standard);for altitudes 1000m~2000m, insulation performance is enhanced by derating to ensure voltage resistance.
Relative Humidity:Monthly average ≤ 90%(at 25℃);daily average ≤ 95%;no condensation on the tank surface.
Wind Speed:Maximum sustained wind speed ≤ 34m/s(12-level wind);instantaneous gust ≤ 50m/s.
Atmospheric Conditions:Suitable for areas free of severe dust, corrosive gases(such as sulfur dioxide, ammonia), flammable gases, and conductive pollutants;for coastal or industrial areas with salt fog, optional anti-corrosion coating and sealed insulation structure are available.
Seismic Resistance:Seismic intensity ≤ 8 degrees;horizontal acceleration ≤ 0.2g, vertical acceleration ≤ 0.1g(conforms to GB/T 13540 or IEC 60068-2-57 standards).
Rainfall:Maximum rainfall intensity ≤ 100mm/h;no long-term heavy rain erosion on the upper casing.
Cấu trúc Thùng Tích hợp: Phòng dập hồ quang, môi trường cách điện và các thành phần liên quan được niêm phong bên trong một thùng kim loại chứa khí cách điện (như hexafluorua sunfur) hoặc dầu cách điện. Điều này tạo thành một không gian tương đối độc lập và kín, ngăn chặn hiệu quả các yếu tố môi trường bên ngoài ảnh hưởng đến các thành phần bên trong. Thiết kế này tăng cường hiệu suất cách điện và độ tin cậy của thiết bị, phù hợp cho nhiều môi trường ngoài trời khắc nghiệt.
Bố cục Phòng Dập Hồ Quang: Phòng dập hồ quang thường được lắp đặt bên trong thùng. Cấu trúc của nó được thiết kế để gọn gàng, cho phép dập hồ quang hiệu quả trong không gian hạn chế. Tuỳ thuộc vào các nguyên lý và công nghệ dập hồ quang khác nhau, cấu trúc cụ thể của phòng dập hồ quang có thể thay đổi, nhưng nói chung bao gồm các thành phần chính như tiếp điểm, vòi phun và vật liệu cách điện. Các thành phần này cùng làm việc để đảm bảo hồ quang được dập nhanh chóng và hiệu quả khi cầu chì ngắt dòng điện.
Mechanism Hoạt động: Các cơ chế hoạt động phổ biến bao gồm cơ chế hoạt động bằng lò xo và cơ chế hoạt động bằng thủy lực.
Cơ chế Hoạt động Bằng Lò Xo: Cơ chế này có cấu trúc đơn giản, độ tin cậy cao và dễ bảo trì. Nó điều khiển các hoạt động đóng và mở của cầu chì thông qua việc lưu trữ và giải phóng năng lượng từ lò xo.
Cơ chế Hoạt động Bằng Thủy Lực: Cơ chế này mang lại lợi ích như công suất đầu ra cao và hoạt động mượt mà, phù hợp cho các cầu chì có điện áp và dòng điện lớn.
Tỷ lệ rò rỉ của khí SF₆ phải được kiểm soát ở mức cực kỳ thấp, thường không vượt quá 1% mỗi năm. Khí SF₆ là một loại khí nhà kính mạnh, có hiệu ứng nhà kính cao gấp 23.900 lần so với carbon dioxide. Nếu xảy ra rò rỉ, nó không chỉ gây ô nhiễm môi trường mà còn dẫn đến giảm áp suất khí bên trong buồng dập hồ quang, ảnh hưởng đến hiệu suất và độ tin cậy của cầu chì.
Để theo dõi sự rò rỉ của khí SF₆, các thiết bị phát hiện rò rỉ khí thường được lắp đặt trên các cầu chì dạng thùng. Các thiết bị này giúp xác định kịp thời bất kỳ rò rỉ nào để có thể thực hiện các biện pháp phù hợp nhằm giải quyết vấn đề.
Trong quá trình hoạt động bình thường và ngắt mạch của cầu chì, khí SF₆ có thể phân hủy, tạo ra các sản phẩm phân hủy như SF₄, S₂F₂, SOF₂, HF và SO₂. Các sản phẩm phân hủy này thường có tính ăn mòn, độc hại hoặc gây kích ứng, do đó cần phải giám sát.Nếu nồng độ của các sản phẩm phân hủy này vượt quá giới hạn nhất định, điều đó có thể cho thấy sự phóng điện bất thường hoặc các lỗi khác bên trong buồng dập hồ quang. Cần phải bảo dưỡng và xử lý kịp thời để ngăn chặn thiệt hại thêm cho thiết bị và bảo vệ sức khỏe của nhân viên.