| Marka | ROCKWILL |
| Seri | RHD |
| Anma maksimum gerilimi | 362kV |
| Anma maksimum akımı | 3150~5000 A |
| Yıldırım darbesi dayanma gerilimi | 1175/1290 kV |
| Anma kısa devre kesme akımı | 40~63 kA |
| Anma frekansı | 50/60 Hz |
Description
As China's first source factory specializing in GIS tank circuit breakers.225kV, 230kV, 245kV,252kV Outdoor Dead Tank SF6 Circuit Breaker is an outdoor (50Hz) high-voltage power transmission and transformation equipment, which is used to divide and combine rated working current, fault current or conversion lines to achieve protection, control and operation of the power system.
The circuit breaker arc extinguisher adopts the principle of double air chamber and double-action self-energy arc extinguishing, with compact structure, and its technical performance has reached the international level and the domestic advanced level, which is the replacement product of the traditional compressed sulfur hexafluoride circuit breaker. The product is composed of a circuit breaker, a current transformer and an inlet and outlet bushing, and is equipped with a full spring operating mechanism, which can not only carry out split-phase operation, but also realize three-phase electrical linkage.
The product has passed all type tests according to the IEC standards, and has the characteristics of excellent breaking ability, reliable insulation, strong flow capacity, and long electrical and mechanical life.
Main feature
Excellent breaking performance:The self-energy arc extinguishing chamber can meet all terminal short circuits, breaking near area faults, out-of-step faults, out-of-phase grounding faults and line charging currents, etc., with small electrical wear and low arc voltage. The rated short-circuit current can be interrupted 20 times in a row.
Reliable insulation and strong flow capacity:SF6 gas has superior insulation performance and simple and reliable insulation structure. There are few current-carrying contact parts, few contact points, and strong flow capacity.
The structure design is unique:The arc extinguisher has simple structure, few components, light weight, small operating work, high mechanical reliability, and a mechanical life of 10,000 times; The insulation structure of the product has been optimized and designed, which greatly reduces the amount of gas, is conducive to environmental protection, and the structural design is integrated and has strong seismic ability.
Easy to install, maintain and overhaul:The overall commissioning of the factory, rapid on-site assembly, and operation with an integrated spring mechanism, no oil leakage and air leakage, no daily energy storage monitoring requirements, so it is easy to maintain.
Technical specifications
Among these, some SF6 tank circuit breakers cover non-standard voltage levels including 225kV, 230kV, 245kV, 275kV, 330kV, 345kV, 400kV, 756kV, and 800kV, with a rated short-circuit breaking current of 50kA or 63kA, and offer customization services.
Name |
Unit |
Technical Parameters |
|
Rated Voltage |
kV |
252 |
|
Rated Current |
A |
4000 |
|
Rated Frequency |
Hz |
50/60 |
|
First - Pole - To - Clear Factor |
/ |
1.3 |
|
Rated Short - circuit Breaking Current |
kA |
50 |
|
Rated Short - time Withstand Current (Effective Value) |
kA/s |
50/3 |
|
Rated Peak Withstand Current |
kA |
125 |
|
1min Rated Power -frequency Withstand Voltage |
Phase - to - phase/Ground |
kV |
460 |
Break - port |
460(+146) |
||
Rated Lightning ImpulseWithstand (1.2/50μs Peak Value) |
Phase - to - phase/Ground |
1050 |
|
Break - port |
1050(+206) |
||
SF6 Gas (Gauge Pressure, 20 °C |
Rated Gas Pressure |
MPa |
0.60 |
Alarm Gas Pressure |
0.55±0.015 |
||
Lock - out Gas Pressure |
0.50±0.015 |
||
Rated operating sequence |
/ |
O - 0.3s - CO - 180s - CO |
|
Rated out - of - step breaking current |
kA |
12.5 |
|
Short - line - fault breaking current |
kA |
L90:45, L70:35 |
|
Out - of - phase grounding breaking current |
kA |
43.5 |
|
Rated line - charging breaking current |
A |
125 |
|
Number of breaking operations for rated short - circuit breaking current |
times |
20 |
|
Mechanical life |
times |
10000 |
|
Mechanism/operation mode |
/ |
Spring Operating Mechanism/Single - phase Operation |
|
Ambient Temperature:-30℃ ~ +40℃(standard configuration);optional -40℃ ~ +45℃ for extreme cold/hot regions (with special insulation and heating/cooling design).
Altitude:≤ 1000m above sea level(standard);for altitudes 1000m~2000m, insulation performance is enhanced by derating to ensure voltage resistance.
Relative Humidity:Monthly average ≤ 90%(at 25℃);daily average ≤ 95%;no condensation on the tank surface.
Wind Speed:Maximum sustained wind speed ≤ 34m/s(12-level wind);instantaneous gust ≤ 50m/s.
Atmospheric Conditions:Suitable for areas free of severe dust, corrosive gases(such as sulfur dioxide, ammonia), flammable gases, and conductive pollutants;for coastal or industrial areas with salt fog, optional anti-corrosion coating and sealed insulation structure are available.
Seismic Resistance:Seismic intensity ≤ 8 degrees;horizontal acceleration ≤ 0.2g, vertical acceleration ≤ 0.1g(conforms to GB/T 13540 or IEC 60068-2-57 standards).
Rainfall:Maximum rainfall intensity ≤ 100mm/h;no long-term heavy rain erosion on the upper casing.
Tam Tank Yapısı: Kesici aralığındaki körük söndürme odası, yalıtım ortamı ve ilgili bileşenler, bir yalıtım gazı (örneğin, sülfür hekzaflorür) veya yalıtım yağı ile doldurulmuş metal tank içinde mühürlenir. Bu, nispeten bağımsız ve mühürlü bir alan oluşturarak, iç bileşenleri etkileyebilecek dış çevresel faktörleri etkili bir şekilde önler. Bu tasarım, ekipmanın yalıtım performansını ve güvenilirliğini artırır, çeşitli sert dış ortamlara uygun hale getirir.
Körük Söndürme Odası Düzeni: Körük söndürme odası genellikle tankın içinde yerleştirilir. Yapı, sınırlı bir alanda etkili körük söndürmeyi sağlayacak şekilde kompakt olarak tasarlanmıştır. Farklı körük söndürme ilkelerine ve teknolojilerine bağlı olarak, körük söndürme odasının spesifik yapısı değişebilir, ancak genellikle kontaktlar, püskürtücüler ve yalıtım malzemeleri gibi ana bileşenleri içerir. Bu bileşenler, kesici akımı keserken körüğü hızlı ve etkili bir şekilde söndürmek için birlikte çalışır.
İşletme Mekanizması: Yayla çalışan mekanizmalar ve hidrolikle çalışan mekanizmalar yaygın olarak kullanılan mekanizmalardır.
Yayla Çalışan Mekanizma: Bu tür mekanizma yapısal olarak basit, oldukça güvenilir ve bakım kolaydır. Yayların enerji depolama ve serbest bırakma yoluyla kesicinin açma ve kapatma işlemlerini sağlar.
Hidrolikle Çalışan Mekanizma: Bu mekanizma, yüksek çıkış gücü ve düzgün çalışma avantajları sunar, bu nedenle yüksek gerilimli ve yüksek akımlı sınıf kesiciler için uygundur.
SF₆ gazının sızıntı oranı son derece düşük bir seviyede kontrol edilmelidir, genellikle yılda %1'i aşmamalıdır. SF₆ gazi, karbondioksitten 23.900 kat daha güçlü bir sera gazıdır. Sızıntı olması durumunda, bu sadece çevre kirliliğine neden olabilir, aynı zamanda arka söndürme odasındaki gaz basıncını azaltarak anahtarın performansını ve güvenilirliğini etkileyebilir.
SF₆ gazının sızıntısını izlemek için genellikle tank tipi kesici devrelerde gaz sızıntı tespit cihazları monte edilir. Bu cihazlar, herhangi bir sızıntıyı zamanında belirlemeye yardımcı olur böylece sorunu çözmek için uygun önlemler alınabilir.
Bir kesici cihazın normal işletme ve kesme süreçlerinde, SF₆ gazı parçalanabilir ve bu süreçte SF₄, S₂F₂, SOF₂, HF ve SO₂ gibi çeşitli parçalara ayrılabilir. Bu parçalanma ürünleri genellikle aşındırıcı, zehirli veya tahriş edici olabilir ve bu nedenle izlenmesi gereklidir.Eğer bu parçalanma ürünlerinin konsantrasyonu belirli sınırları aşarsa, bu durum ark söndürme odasında anormal boşaltmalar veya diğer hatalar olduğunu gösterebilir. Ekipman üzerindeki daha fazla hasara ve personel sağlığı için zamanında bakım ve müdahale yapılması gerekir.