Issue Overview
The 10kV air compressor starting system of a company utilizes the ABB vacuum contactor KC2 as the control component for the operating circuit. The dedicated wide-voltage power supply module paired with this contactor presents the following issues:
II. WONE Technical Transformation Plan
Core Approach: Adopt a "functional decomposition" strategy to separate the contactor’s pull-in and holding functions, each powered by different sources.
System Composition:
Working Principle:
III. Implementation Plan
Equipment List:
Name |
Specification Requirements |
Quantity |
Remarks |
DC power supply module |
Input AC220V, Output DC12V |
1 set |
Power must meet coil holding requirements |
Intermediate relay |
Coil voltage AC/DC 220V |
1 unit |
With normally open contacts |
Diode |
Voltage resistance ≥400V, current ≥1A |
2 units |
For power isolation and protection |
Installation accessories |
Compatible |
1 set |
Includes cables, terminals, etc. |
Installation Requirements:
IV. Advantages of the Plan
V. Implementation Results
This plan thoroughly resolves the original design flaws through technical innovation, achieving: