
Ania nga solusyon nagfokus sa usa ka ultra-fast short-circuit current limiting device, gihimo aron matubag ang kasagaran nga problema sa pagdako sa short-circuit currents ug matiyak ang kalambigitan sa power grids ug equipment.
1.1 Core Features
1.2 Core Advantages
|
No. |
Key Question |
Core Answer |
|
1 |
Unsa ang peak short-circuit current? |
Ang maximum instantaneous value human sa unang cycle human sa short-circuit fault, resulta sa superposition sa periodic ug non-periodic components. Igihiusa kini og dako nga electromagnetic forces (testing dynamic stability) ug heat (testing thermal stability). |
|
2 |
Bakit limitahan ang peak short-circuit current? |
Ang peak currents nga mas taas sa rated withstand parameters sa equipment mahimong moguba sa switchgear, circuit breakers, current transformers, ug cable connectors pinaagi sa dako nga electromagnetic forces. |
|
3 |
Pamuno kung unsaon pag-adapt sa parallel operation of multiple transformers? |
Para sa switchgear nga may withstand capability nga 2Ik, sa usa ka system nga adunay apat ka transformers (4Ik) sa parallel, makaya ang perfect adaptation pinaagi sa pag-install og fast current limiters sa gitas nga bus sections (e.g., sa pagitan sa sections 1-2 ug 3-4). |
|
4 |
Unsa ang tripping criteria? Unsaon pag-iwas sa false trips? |
Ang control unit nag-monitor sa instantaneous current (I) ug rate of current rise (di/dt). Ang trip mag-trigger lang kung parehas sila mag-exceed sa set thresholds. Kini nga dual criterion siguro nga ang tikang nga short-circuit currents lang ang gi-interrupt, ang general faults gibahin sa downstream circuit breakers. |
|
5 |
Unsaon ang maintenance human sa operation? |
Ang core operating component (conductive bridge) may modular design ug mahimong ibalik sa repair. Ang kinahanglan ra i-replace mao ang internal conductive core, inductive filler, ug parallel fuses; ang uban pang mga komponent reusable, makapahinayog sa kaayo ka gamay nga maintenance costs. |
3.1 Core Function
Nag-detekta ug nagsugyot sa sayop sa initial rising stage of short-circuit current (within 1ms), efektibo nga natigom ang damage sa power equipment tungod sa insufficient dynamic ug thermal stability. Perfectly nag-compensate sa inherent limitations sa traditional circuit breakers—"slow to act and unable to suppress the first half-wave peak current."
3.2 Comparative Advantages
|
Comparison Object |
Advantage Details |
|
Traditional Circuit Breakers |
Ang breakers mag-operate sa tens of milliseconds aron interrupt, dili makaputli sa impact sa unang peak current. Kini nga limiter nag-responde sa 1ms, nagsugyot sa actual peak short-circuit current sa mas gamay nga level. |
|
Current-Limiting Reactors |
Nag-iwas sa voltage drop, active losses (copper losses), ug reactive losses associated sa reactors sa continuous operation. Ug nag-iwas usab sa generator regulation issues resulta sa integration sa reactor. |
3.3 Applicable Scenarios
4.1 Overall Composition
Ang three-phase AC system fast current limiter gisangpot sa:
4.2 Key Component Details
|
Component Name |
Composition / Features |
Key Parameters / Rules |
|
Conductive Bridge Base |
Includes mounting plate, insulators, pulse transformer, ug connectors with quick couplings |
- Rated current ≥2500A ug voltage 12/17.5kV: Bolted connections. |
|
Conductive Bridge |
Conductive core ug inductive filler encapsulated in an insulating cover |
Upon tripping, ang inductive filler mag-trigger, driving the conductive core to break rapidly at its pre-cut; current then transfers to the parallel fuse. |
|
Matching Current Transformer |
Bushing or block type, series-connected in the main circuit |
Features a gapped core (high overcurrent factor, low remanence) ug shielded primary/secondary windings (low impedance) to ensure measurement accuracy ug speed. |
|
Control Unit |
Includes power supply, control, indication, ug anti-interference units |
- Dimensions: 600mm (W) × 1450mm (H) × 300mm (D); weight: 100kg. |
5.1 Core Composition
Ang device essentially an intelligent parallel combination of two components:
5.2 Operation Sequence
5.3 Auxiliary Units
6.1 Testing Requirements
Regular functional testing is required, which can be executed by users or ABB service engineers.
6.2 Dedicated Equipment
7.1 Supply Models
|
Model Type |
Applicable Scenarios |
Core Configuration |
|
Discrete Components |
For installation in existing switchgear |
3 bases + 3 conductive bridges + 3 CTs + 1 control unit |
|
Drawout Cabinet |
For metal-clad switchgear |
Conductive bridges mounted on withdrawable carts (with isolating switch function); CTs fixed; control unit installed in the low-voltage compartment |
|
Fixed Cabinet |
- For 12/17.5/24kV systems |
All components fixed inside the cabinet. For 36/40.5kV systems, the control unit is often installed in a separate control box. |
7.2 Key Technical Parameters (Example: Discrete Components)
Note: ¹ indicates forced air cooling is required; compatible with 50/60Hz frequency.
|
Technical Parameter |
Unit |
12kV |
17.5kV |
24kV |
36/40.5kV |
|
Rated Voltage |
V |
12000 |
17500 |
24000 |
36000/40500 |
|
Rated Current |
A |
1250-5000¹ |
1250-4000¹ |
2500-4000¹ |
1250-3000¹ |
|
Rated Short-Circuit Breaking Current (Max.) |
kA RMS |
210 |
210 |
210 |
140 |
|
Application Scenario |
Core Issue |
Solution Value |
|
Parallel System Operation |
Short-circuit current from multiple transformers in parallel exceeds switchgear ratings |
1. Allows reduced system impedance, minimizing voltage drop. |
|
Grid-Captive Power Interconnection |
Captive generator operation causes excessive short-circuit current at the common coupling point |
The only rational solution. Can be equipped with directional tripping (requires CT at generator neutral) to ensure operation only for grid-side faults. |
|
Bypassing Current-Limiting Reactors |
Reactors in continuous operation cause losses ug voltage drop |
Bypasses reactors during normal operation (zero loss, zero voltage drop); rapidly interrupts during short circuits, diverting current to the reactor for limiting. |
|
Selective Application of Multiple Units |
Selective operation required when multiple limiters are installed on multi-section buses |
Uses "current vector sum" criterion to ensure only the limiter closest to the fault operates. Supports up to 5 transformers in parallel (using 4 limiters). |