
Hoc solutionem focus ponit in dispositivo ultra-veloci limitationis currentis circuitus brevis, designatum ut fundamentaliter respondeat crescenti difficultati excedentis currentis circuitus brevis et securitatem reticulorum electricorum et apparatorum tueatur.
1.1 Characteristica principalia
1.2 Principalia praestantia
| 
 No.  | 
 Key Question  | 
 Core Answer  | 
| 
 1  | 
 Quid est maximus currentus circuitus brevis?  | 
 Maximum instantaneum post primam cyclos post eventum defectus circuitus brevis, resultans ex superpositione componentum periodicarum et non-periodicarum. Generat enormes vires electromagneticas (testando stabilitatem dynamicam) et calorem (testando stabilitatem thermicam).  | 
| 
 2  | 
 Cur limitare debet maximus currentus circuitus brevis?  | 
 Currentus maximi excedentes parametra tolerabiles aequipamentorum possunt laedere commutatoria, interruptores circuitus, transformatores currentis, et conectoria cableum per vires electromagneticas potentes.  | 
| 
 3  | 
 Quomodo adaptari ad operationem parallelam plurium transformatorum?  | 
 Pro commutatoriis cum capacitate tolerantiae 2Ik, in systemate cum quatuor transformatoribus (4Ik) in parallelo, perfecta adaptatio potest assequi per installationem celerum limitatorum currentis inter sectiones bus (exempli gratia, inter sectiones 1-2 et 3-4).  | 
| 
 4  | 
 Quae sunt criteria trip? Quomodo evitare falsa tripping?  | 
 Unitas controlis simul monitorat currentem instantaneam (I) et gradum incrementi currentis (di/dt). Trip initium capitur tantum quando ambo excedunt limina setta. Hoc duplex criterium solum certificat interruptio currentus circuitus brevis periculosi, dum defectus generales tractantur ab interruptoribus circuitus inferioribus.  | 
| 
 5  | 
 Quomodo maintinere post operationem?  | 
 Nucleus operativus (pons conductivus) designatur modulariter et potest reparari. Solum nucleum conductivum internum, repletum inductivum, et fusibilia parallela requirunt substitutionem; alia componentia reutilizabilia, certificans valde parva costes maintenance.  | 
3.1 Nucleus function
Detectat et limitat defectus in initiali stagione ascensionis currentis circuitus brevis (intra 1ms), efficaciter praeveniens damna aequipamentorum electricorum propter insufficiens stabilitatem dynamicam et thermicam. Perfecte compensat inherentia limitationes tradicionalium interruptorum circuitus—“lenta ad agendum et non-capax suppressioni semicyclus peak currentis.”
3.2 Comparativa praestantia
| 
 Comparatio objecti  | 
 Detail praestantia  | 
| 
 Tradicionales interruptores circuitus  | 
 Interruptores tollunt decem millisecondes ad interruptum, nonque evitant impactum primi currentis peak. Hic limitator respondet intra 1ms, restrictus actualis maximus currentus circuitus brevis ad minus nivellum.  | 
| 
 Reactores limitationis currentis  | 
 Avoids voltage drop, active losses (copper losses), and reactive losses associated with reactors in continuous operation. Also eliminates the need to address generator regulation issues caused by reactor integration.  | 
3.3 Scenaria applicabili
4.1 Compositio totalis
Systema AC triphase rapidum limitator currentis constat:
4.2 Detail principalium componentium
| 
 Nomen componentis  | 
 Compositio / Charactera  | 
 Parametri clavi / Regulae  | 
| 
 Base pons conductivus  | 
 Includit plateam montandi, insulators, transformator pulsus, et connectors cum quick couplings  | 
 - Currentus nominatus ≥2500A et tensio 12/17.5kV: Connectiones boltae.  | 
| 
 Pons conductivus  | 
 Nucleus conductivus et repletum inductivum encapsulatum in cover insulans  | 
 Post trip, repletum inductivum triggeratur, impellens nucleus conductivus ad rupturam rapidam in suo praeciso; currentus tunc transferatur ad fusibile parallellum.  | 
| 
 Transformator currentis matching  | 
 Tipo bushing aut block, series-connected in circuitu principali  | 
 Feature core gapped (high overcurrent factor, low remanence) et shielded primary/secondary windings (low impedance) ad certificandam accurate et velocitatem mensurationis.  | 
| 
 Unitas controlis  | 
 Includit supply power, control, indication, et anti-interference units  | 
 - Dimensions: 600mm (W) × 1450mm (H) × 300mm (D); weight: 100kg.  | 
5.1 Nucleus compositio
Dispositivum est essentia parallel combination intelligentia duorum componentium:
5.2 Sequencia operationis
5.3 Unitates auxiliariae
6.1 Testing Requirements
Regular functional testing is required, which can be executed by users or ABB service engineers.
6.2 Dedicated Equipment
7.1 Supply Models
| 
 Model Type  | 
 Applicable Scenarios  | 
 Core Configuration  | 
| 
 Discrete Components  | 
 For installation in existing switchgear  | 
 3 bases + 3 conductive bridges + 3 CTs + 1 control unit  | 
| 
 Drawout Cabinet  | 
 For metal-clad switchgear  | 
 Conductive bridges mounted on withdrawable carts (with isolating switch function); CTs fixed; control unit installed in the low-voltage compartment  | 
| 
 Fixed Cabinet  | 
 - For 12/17.5/24kV systems  | 
 All components fixed inside the cabinet. For 36/40.5kV systems, the control unit is often installed in a separate control box.  | 
7.2 Key Technical Parameters (Example: Discrete Components)
Note: ¹ indicates forced air cooling is required; compatible with 50/60Hz frequency.
| 
 Technical Parameter  | 
 Unit  | 
 12kV  | 
 17.5kV  | 
 24kV  | 
 36/40.5kV  | 
| 
 Rated Voltage  | 
 V  | 
 12000  | 
 17500  | 
 24000  | 
 36000/40500  | 
| 
 Rated Current  | 
 A  | 
 1250-5000¹  | 
 1250-4000¹  | 
 2500-4000¹  | 
 1250-3000¹  | 
| 
 Rated Short-Circuit Breaking Current (Max.)  | 
 kA RMS  | 
 210  | 
 210  | 
 210  | 
 140  | 
| 
 Application Scenario  | 
 Core Issue  | 
 Solution Value  | 
| 
 Parallel System Operation  | 
 Short-circuit current from multiple transformers in parallel exceeds switchgear ratings  | 
 1. Allows reduced system impedance, minimizing voltage drop.  | 
| 
 Grid-Captive Power Interconnection  | 
 Captive generator operation causes excessive short-circuit current at the common coupling point  | 
 The only rational solution. Can be equipped with directional tripping (requires CT at generator neutral) to ensure operation only for grid-side faults.  | 
| 
 Bypassing Current-Limiting Reactors  | 
 Reactors in continuous operation cause losses and voltage drop  | 
 Bypasses reactors during normal operation (zero loss, zero voltage drop); rapidly interrupts during short circuits, diverting current to the reactor for limiting.  | 
| 
 Selective Application of Multiple Units  | 
 Selective operation required when multiple limiters are installed on multi-section buses  | 
 Uses "current vector sum" criterion to ensure only the limiter closest to the fault operates. Supports up to 5 transformers in parallel (using 4 limiters).  |