
Din is-soluzzjoni tikkonsentra fuq d-dispożitiv limitatur tal-kurtkit ġdid, disegnat biex jindirizza l-isfida li qed tisilġa ta’ kurtkit eċċessivi u tassegura s-sigurtà tal-grids tal-enerġija u tal-equipament.
1.1 Atributi Korni
1.2 Vantaggi Korni
|
Nru. |
Domanġa Korni |
Risposta Korni |
|
1 |
X’hu l-kurrent massimu tal-kurtkit? |
|
|
2 |
Perché limitu l-kurrent massimu tal-kurtkit? |
Il-kurrenti massimi li jisghuvu l-parametri ta’ resistenza tas-silġa jistgħu jidamaġġjaw switchgear, circuit breakers, current transformers, u konnektör tal-kable permezz ta’ forzi elettromagnetiku potenti. |
|
3 |
Kif adattar għal operazzjoni parallel ta’ multipli transformers? |
Għal switchgear b’restituenza ta’ 2Ik, fis-sistema b’quddiem transformers (4Ik) parallel, tintiġieħ l-adattazzjoni perfetta mill-installazzjoni ta’ limitaturi tal-kurrent rapidi bejn bus sections (pereżempju, bejn sections 1-2 u 3-4). |
|
4 |
Xi huma l-kriterji ta’ tripping? Kif evita l-falsi tripping? |
kurrent instantaneu (I) u l-taqsima tal-kurrent (di/dt). It-tripping jiġi attivat biss meta tkun l-ewwel u l-ħanut jisghuvu l-limiti settati. Dan ikriterju doppju jassigura biss li l-kurrenti tal-kurtkit perikoluż jiġu interrotti, mentri l-erori ġenerali jiġu amministrati mill-circuit breakers downstream. |
|
5 |
Kif manutenzjoni wara l-operazzjoni? |
|
3.1 Funzjoni Korni
Jiddeċkja u jlimita l-erori wara l-faza inizjali tal-kurrent tal-kurtkit (fil-1ms), efettivament prevenend id-damage tal-equipament tal-enerġija minħabba l-istabilità dinamika u termika insufficenti. Jkompenża perfettament l-limiti inherenti tal-circuit breakers tradizzjonali - "slow to act and unable to suppress the first half-wave peak current."
3.2 Vantaggi Konfrontati
|
Oggett ta’ Konfront |
Dettagli tal-Vantaggi |
|
Circuit Breakers Tradizzjonali |
Il-breakers jagħmlu decine ta’ millisecondi biex jinterrompu, mhux jistgħu jivitan l-impat tal-pik kurrent primu. Dan il-limitatur irrispondi fil-1ms, restringend il-kurrent massimu tal-kurtkit għal livell inferjuri. |
|
Current-Limiting Reactors |
Avoids voltage drop, active losses (copper losses), and reactive losses associated with reactors in continuous operation. Also eliminates the need to address generator regulation issues caused by reactor integration. |
3.3 Skenari Applicabbli
4.1 Komposizzjoni Korni
4.2 Dettagli tal-Komponenti Korni
|
Isem tal-Komponent |
Komposizzjoni / Karatteristiki |
Parametri Korni / Regoli |
|
Base tal-bridge konduċtiv |
Inkludi pjan ta’ montaġġ, isolatori, pulse transformer, u konekturi b’quick couplings |
- Kurrent nominal ≥2500A u votaġġ 12/17.5kV: konnessjonijiet bolted. |
|
Bridge konduċtiv |
Nuċel konduċtiv u ripleniment induttiv encapsulated in an insulating cover |
|
|
Matching Current Transformer |
Bushing or block type, series-connected in the main circuit |
Features a gapped core (high overcurrent factor, low remanence) and shielded primary/secondary windings (low impedance) to ensure measurement accuracy and speed. |
|
Control Unit |
Includes power supply, control, indication, and anti-interference units |
- Dimensions: 600mm (W) × 1450mm (H) × 300mm (D); weight: 100kg. |
5.1 Komposizzjoni Korni
5.2 Sequenza ta’ Operazzjoni
5.3 Auxiliary Units
6.1 Testing Requirements
Regular functional testing is required, which can be executed by users or ABB service engineers.
6.2 Dedicated Equipment
7.1 Supply Models
|
Model Type |
Applicable Scenarios |
Core Configuration |
|
Discrete Components |
For installation in existing switchgear |
3 bases + 3 conductive bridges + 3 CTs + 1 control unit |
|
Drawout Cabinet |
For metal-clad switchgear |
Conductive bridges mounted on withdrawable carts (with isolating switch function); CTs fixed; control unit installed in the low-voltage compartment |
|
Fixed Cabinet |
- For 12/17.5/24kV systems |
All components fixed inside the cabinet. For 36/40.5kV systems, the control unit is often installed in a separate control box. |
7.2 Key Technical Parameters (Example: Discrete Components)
Note: ¹ indicates forced air cooling is required; compatible with 50/60Hz frequency.
|
Technical Parameter |
Unit |
12kV |
17.5kV |
24kV |
36/40.5kV |
|
Rated Voltage |
V |
12000 |
17500 |
24000 |
36000/40500 |
|
Rated Current |
A |
1250-5000¹ |
1250-4000¹ |
2500-4000¹ |
1250-3000¹ |
|
Rated Short-Circuit Breaking Current (Max.) |
kA RMS |
210 |
210 |
210 |
140 |
|
Application Scenario |
Core Issue |
Solution Value |
|
Parallel System Operation |
Short-circuit current from multiple transformers in parallel exceeds switchgear ratings |
1. Allows reduced system impedance, minimizing voltage drop. |
|
Grid-Captive Power Interconnection |
Captive generator operation causes excessive short-circuit current at the common coupling point |
The only rational solution. Can be equipped with directional tripping (requires CT at generator neutral) to ensure operation only for grid-side faults. |
|
Bypassing Current-Limiting Reactors |
Reactors in continuous operation cause losses and voltage drop |
Bypasses reactors during normal operation (zero loss, zero voltage drop); rapidly interrupts during short circuits, diverting current to the reactor for limiting. |
|
Selective Application of Multiple Units |
Selective operation required when multiple limiters are installed on multi-section buses |
Uses "current vector sum" criterion to ensure only the limiter closest to the fault operates. Supports up to 5 transformers in parallel (using 4 limiters). |