• LMZB1-24 Outdoor Current Transformer
LMZB1-24 Outdoor Current Transformer
discuss personally
Model
LMZB1-24
Basic info
Brand Wone Store
Model NO. LMZB1-24 Outdoor Current Transformer
Rated voltage 24kV
Rated frequency 50/60Hz
Rated current ratio 400/5
Series LMZB
Product Detail

Product Overview

Designed for 24kV outdoor applications, this transformer features IP68 protection, 7000-hour UV resistance, and 2000-hour salt spray tolerance. With dual 0.2S/5P20 windings and adjustable ratio taps (300/5A-600/5A), it delivers high-precision metering and fast fault response in harsh environments. Compliant with IEC 60044-2, it ensures reliable performance in coastal, high-altitude, or extreme temperature conditions.

Key Features

  • Nanocrystalline Alloy Core Technology:The core is made of nanocrystalline alloy material, which, compared with traditional silicon steel sheet cores, increases magnetic permeability by 30% and reduces no-load loss by 40%. Within the range of 5%~120% rated current, the ratio error is controlled within ±0.15% and the phase difference is ≤4', significantly improving measurement accuracy under small current conditions, especially suitable for light-load fluctuation scenarios such as distributed photovoltaic systems.

  • Adaptive Load Regulation Function:Equipped with an intelligent load monitoring module, it can sense changes in primary side current in real-time. When the current is lower than 30% of the rated value, it automatically activates low-power mode to reduce its own energy consumption; when the current suddenly increases to more than 120%, it quickly switches to overload protection status to ensure the safety of secondary side equipment. It can adapt to complex load fluctuations without manual intervention.

  • Integrated Anti-Vibration Installation Structure:The bottom adopts a spring damping design with rubber buffer pads, which can withstand continuous vibration of 10~50Hz, and the vibration acceleration tolerance reaches 10g, far higher than the industry's conventional 5g standard. It is suitable for outdoor installation scenarios close to strong vibration sources such as substation reactors and fans, avoiding wiring looseness or component fatigue caused by long-term vibration.

  • Wide Temperature Range Intelligent Cooling System:Optimized for extreme temperature difference environments, when the winding temperature exceeds 80℃, the built-in micro cooling fan (power consumption ≤5W) is automatically activated. Combined with the shell cooling fins, it can control the winding temperature within 100℃ in +90℃ environment; the fan automatically hibernates in low-temperature environments to reduce energy loss, ensuring stable operation in the full temperature range of -35℃~+90℃.

Technical Data

  • Rated insulation level: 24/50/125 kV

  • Rated frequency: 50/60Hz

  • Installation site:Outdoor

  • Technical standard: IEC 60044-2, IEC 61869-1&3

Specification

Note:Upon request we are glad to offer transformers according to other technical specs. 

Outline Drawing

Know your supplier
Wone Store
Main Categories
High Voltage Electrical Apparatus/Low Voltage Electrical Apparatus/Wire cable/Instrument meters/New energy/Tester/Production equipment/Generator/Electrical fittings/Integrated Electrical Equipment/Instrument Transformer/Equipment Parts
Business Type
Sales
Highest Annual Export (USD)
$300000000
Professional Experience
1 years
Workplace
1000m²
占位
占位
Related Products
Related Knowledges
Analysis of Abnormal Causes of High-Voltage Cable Grounding Circulation and Typical Cases
Analysis of Abnormal Causes of High-Voltage Cable Grounding Circulation and Typical Cases
I. Introduction to Cable Grounding Loop CurrentCables rated 110 kV and above use a single-core structure. The alternating magnetic field generated by the operating current induces a voltage on the metallic sheath. If the sheath forms a closed circuit through the earth, a grounding loop current will flow on the metallic sheath. Excessive grounding loop current (loop current exceeding 50 A, more than 20% of the load current, or a ratio of maximum-to-minimum phase current greater than 3) not only a
Felix Spark
09/03/2025
Considerations and Recommendations for Flame-Retardant Selection of High-Voltage Cables
Considerations and Recommendations for Flame-Retardant Selection of High-Voltage Cables
1.Flame-Retardant Cable Classification StandardsThe flame-retardant standard system is divided into two main categories. The first category follows the "Classification of Burning Behavior for Electric and Optical Fiber Cables" GB 31247. Cables complying with this standard system are widely used in densely populated areas such as high-speed railways and subways. This standard imposes strict requirements on parameters such as smoke density, heat release, and total smoke production, and cables typi
James
09/03/2025
Repair of high-voltage cable metallic sheaths
Repair of high-voltage cable metallic sheaths
I. Functions of Metallic Sheaths and Necessity of RepairThe metallic sheath of high-voltage cables is a metal shielding structure laid outside the insulation layer, including types such as lead sheaths, aluminum sheaths, and steel wire armor. Its core functions include mechanical protection (resisting external impact and compression), electrochemical corrosion protection (isolating moisture and soil pollutants), electromagnetic shielding (reducing electromagnetic interference to the environment)
Felix Spark
09/03/2025
What factors need to be considered when designing a transformer?
What factors need to be considered when designing a transformer?
Transformer design is a complex process that requires consideration of multiple factors to ensure safe and efficient operation. In addition, compliance with international and local regulations is essential to guarantee that transformers meet safety and performance standards. Below are key factors to consider in transformer design and the relevant regulations to follow:Transformer Design Factors: Voltage and Frequency: Determine the input and output voltage levels and the operating frequency. The
Vziman
09/02/2025
What failure modes are possible in a transformer? How to identify and fix these failures?
What failure modes are possible in a transformer? How to identify and fix these failures?
Transformers are critical components in power systems, and various failure modes can affect their operation. Timely identification and resolution of these failure modes are essential to prevent costly downtime and ensure system reliability. Below are some common transformer failure modes, along with methods to identify and address them: Insulation FailureIdentification: Insulation failure leads to decreased insulation resistance, which can be detected through insulation resistance testing (megge
Edwiin
09/02/2025
A hybrid DC circuit breaker
A hybrid DC circuit breaker
Most DC molded-case circuit breakers use natural air arc extinction, and there are typically two arc extinguishing methods: one is conventional opening and closing, where the contacts axially stretch the arc, while the conductive circuit generates a magnetic field that bends and elongates the arc, pulling it lengthwise perpendicular to the arc axis. This not only increases the arc length but also induces lateral motion, enabling air cooling to achieve arc extinction.The other method involves the
Echo
09/02/2025
×
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!