Safe Response to Isolator Mechanical & Electrical Failures

Felix Spark
Field: Failure and maintenance
China

The following are methods for handling accidents and abnormalities related to isolating switches:

(1) If an isolating switch fails to operate (refuses to open or close), take the following steps:

① For mechanically operated isolating switches that fail to open or close, check whether the circuit breaker is open, whether the mechanical interlock of the isolating switch has been released, whether the transmission mechanism is jammed, and whether the contacts are rusted or welded. Gently wiggle the operating handle to assist inspection—but do not force operation until the root cause is identified.

② For electrically operated isolating switches that fail to respond, first determine whether the fault lies in the mechanical transmission system or in the electric operating circuit. If it is an electric control circuit fault, verify that all electrical interlocks have been properly released and that the three-phase voltage of the operating power supply is normal. If the fault is confirmed to be in the electric operating circuit, the switch may be manually operated to open or close. However, if the electrical interlock has not been released, do not forcibly bypass the interlock and operate the switch until the cause is fully investigated.

③ If a support insulator breaks during operation, immediately stop operating the isolating switch and report to the dispatcher. Depending on the system configuration, isolate the faulty switch from the power source by transferring loads to another busbar or de-energizing the affected busbar.

④ If the mechanical transmission part of the isolating switch is defective but the conductive part remains intact and functional, defer repair until the next scheduled outage. However, if overheating occurs in the conductive part, immediately report to the dispatcher, implement load-limiting measures, and de-energize the switch for maintenance if necessary.

(2) During closing of an isolating switch, if poor contact occurs in one phase due to significant three-phase asynchronism, the switch may be opened and reclosed. Alternatively, an insulated operating rod can be used to gently adjust the blade into proper alignment. However, if the three-phase asynchronism is severe, contact maintenance personnel for handling—do not attempt forced operation.

Give a tip and encourage the author!

Recommended

Common Issues and Handling Measures for 145kV Disconnector Control Circuits
The 145 kV disconnector is a critical switching device in substation electrical systems. It is used in conjunction with high-voltage circuit breakers and plays an important role in power grid operation:First, it isolates the power source, separating equipment under maintenance from the power system to ensure personnel and equipment safety;Second, it enables switching operations to change the system operating mode;Third, it is used to interrupt small-current circuits and bypass (loop) currents.Re
11/20/2025
What are the six operating principles of disconnect switches?
1. Operating Principle of the DisconnectorThe operating mechanism of the disconnector is connected to the active pole of the disconnector via a connecting tube. When the main shaft of the mechanism rotates 90°, it drives the insulating pillar of the active pole to rotate 90°. The bevel gears inside the base drive the insulating pillar on the other side to rotate in the opposite direction, thereby achieving opening and closing operations. The active pole, through inter-pole linkage tubes, drives
11/19/2025
36kV Disconnect Switch Selection Guide & Key Parameters
Selection Guidelines for 36 kV Disconnect SwitchesWhen selecting the rated voltage, ensure that the disconnect switch’s rated voltage is equal to or higher than the nominal voltage of the power system at the installation point. For example, in a typical 36 kV power network, the disconnect switch must have a rated voltage of at least 36 kV.For rated current, selection should be based on the actual long-term load current. Generally, the switch’s rated current must be no less than the maximum conti
11/19/2025
Copper Conductor Size vs Temperature Rise in 145kV Disconnectors
The relationship between the temperature-rise current of a 145 kV disconnector and copper conductor size lies in balancing current-carrying capacity and heat dissipation efficiency. The temperature-rise current refers to the maximum continuous current a conductor can carry without exceeding its specified temperature rise limit, and the copper conductor size directly influences this parameter.Understanding this relationship begins with the physical properties of the conductor material. Copper’s c
11/19/2025
Related Products
Send inquiry
+86
Click to upload file

IEE Business will not sell or share your personal information.

Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.