Safe Response to Isolator Mechanical & Electrical Failures

Felix Spark
Felix Spark
Field: Failure and maintenance
China

The following are methods for handling accidents and abnormalities related to isolating switches:

(1) If an isolating switch fails to operate (refuses to open or close), take the following steps:

① For mechanically operated isolating switches that fail to open or close, check whether the circuit breaker is open, whether the mechanical interlock of the isolating switch has been released, whether the transmission mechanism is jammed, and whether the contacts are rusted or welded. Gently wiggle the operating handle to assist inspection—but do not force operation until the root cause is identified.

② For electrically operated isolating switches that fail to respond, first determine whether the fault lies in the mechanical transmission system or in the electric operating circuit. If it is an electric control circuit fault, verify that all electrical interlocks have been properly released and that the three-phase voltage of the operating power supply is normal. If the fault is confirmed to be in the electric operating circuit, the switch may be manually operated to open or close. However, if the electrical interlock has not been released, do not forcibly bypass the interlock and operate the switch until the cause is fully investigated.

③ If a support insulator breaks during operation, immediately stop operating the isolating switch and report to the dispatcher. Depending on the system configuration, isolate the faulty switch from the power source by transferring loads to another busbar or de-energizing the affected busbar.

④ If the mechanical transmission part of the isolating switch is defective but the conductive part remains intact and functional, defer repair until the next scheduled outage. However, if overheating occurs in the conductive part, immediately report to the dispatcher, implement load-limiting measures, and de-energize the switch for maintenance if necessary.

(2) During closing of an isolating switch, if poor contact occurs in one phase due to significant three-phase asynchronism, the switch may be opened and reclosed. Alternatively, an insulated operating rod can be used to gently adjust the blade into proper alignment. However, if the three-phase asynchronism is severe, contact maintenance personnel for handling—do not attempt forced operation.

Give a tip and encourage the author!
Recommended
Preventing & Resolving Catenary Switch Failures in Rail
Preventing & Resolving Catenary Switch Failures in Rail
"Faults of catenary isolating switches" are common failures in current traction power supply operations. These faults frequently result from mechanical failures of the switch itself, control circuit malfunctions, or remote control function failures, leading to refusal-to-operate or unintended operation of the isolating switch. Therefore, this paper discusses common faults of catenary isolating switches during current operations and the corresponding handling methods after fault occurrence.1.Comm
Felix Spark
11/10/2025
Main Application Scenarios of the GW8 Isolating Switch
Main Application Scenarios of the GW8 Isolating Switch
The GW8 isolating switch is a critical piece of equipment in power systems and is primarily used in the following applications:Applications in Power Systems:The GW8 isolating switch is widely employed in power plants, substations, and transmission and distribution lines. In power plants, it isolates the connection between generators and busbars or transformers, facilitating generator startup, shutdown, and maintenance. In substations, it isolates busbars or transformers operating at different vo
Echo
11/10/2025
Precautions for Installing Four-Pole Isolating Switches
Precautions for Installing Four-Pole Isolating Switches
Installation Requirements for Isolating SwitchesBefore installing an isolating switch, a thorough visual inspection must be carried out. The main items to check include:(1) Verify that the model and specifications of the isolating switch match the design requirements.(2) Inspect all components for damage and check whether the blade or contacts are deformed. If deformation is found, it should be corrected.(3) Examine the contact condition between the movable blade and the contacts. Any copper oxi
James
11/10/2025
What is the function of a transformer neutral grounding disconnector?
What is the function of a transformer neutral grounding disconnector?
Transformer Neutral Grounding Disconnector: Function, Principle, Structure, Operation, and MaintenanceA transformer neutral grounding disconnector is an electrical device used to isolate the neutral point of a power transformer. Its primary purpose is to protect both the transformer and the overall power system, ensuring safe and stable operation.I. Functions of the Transformer Neutral Grounding DisconnectorTransformer ProtectionOne of the key roles of the neutral grounding disconnector is to sa
Echo
11/10/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.