Copper Conductor Size vs Temperature Rise in 145kV Disconnectors

Echo
Echo
Field: Transformer Analysis
China

The relationship between the temperature-rise current of a 145 kV disconnector and copper conductor size lies in balancing current-carrying capacity and heat dissipation efficiency. The temperature-rise current refers to the maximum continuous current a conductor can carry without exceeding its specified temperature rise limit, and the copper conductor size directly influences this parameter.

Understanding this relationship begins with the physical properties of the conductor material. Copper’s conductivity, resistivity, and thermal expansion coefficient determine both heat generation under load and heat dissipation rate. Larger cross-sectional areas reduce resistance per unit length, thereby generating less heat at the same current. For example, a 2.5 mm² copper wire exhibits lower temperature rise than a 1.5 mm² wire when carrying 20 A.

When selecting conductor size, three key factors must be evaluated holistically:

  • Load characteristics, including current fluctuation magnitude and duration. Equipment with frequent starts/stops or short-term overloads requires consideration of transient temperature rise effects on insulation.

  • Ambient temperature: Higher ambient temperatures necessitate larger conductors to offset additional thermal stress.

  • Installation method: Enclosed conduits offer poor heat dissipation; conductor size should be increased by at least 20% compared to open installations.

Critical thresholds can be estimated using the formula:
ΔT = (I² · R · t) / (m · c)
where I is current, R is resistance per unit length, t is time, m is conductor mass, and c is specific heat capacity. In practice, quick-reference tables are commonly used—for instance, at 40°C ambient temperature, standard BV wires have the following ampacities: 1.5 mm² → 16 A, 2.5 mm² → 25 A, 4 mm² → 32 A.

Common misconceptions must be avoided. Some assume that simply increasing conductor size solves overheating—but poor terminal contact, oxidation at joints, or loose connections can cause localized hotspots. In one case, a poorly crimped 4 mm² copper connection reached 120°C at just 15 A, far exceeding the conductor’s bulk temperature rise of 65°C.

DS4 40.5kV 126kV 145kV 252kV 330kV High voltage disconnect switch Chinese Factory

Copper purity significantly affects temperature rise. Oxygen-free copper (99.9% Cu) has 8–12% lower resistivity than recycled copper, enabling ~10% higher current capacity at the same size. It is recommended to use copper wire complying with GB/T 395 standards for electrical applications.

Practical application strategies can be structured into three tiers:

  • Tier 1 (Basic Matching): Select conductor size based on 1.2× the rated current.

  • Tier 2 (Dynamic Compensation): Adjust for power factor—inductive loads require 5–8% larger conductors.

  • Tier 3 (Redundancy Design): Reserve 20% current margin on critical circuits for unexpected surges.

Heat dissipation can be enhanced through structural and material improvements:

  • Stranded conductors offer >30% more surface area than solid-core wires.

  • Tin-plating reduces contact resistance by 15–20%.

  • In enclosed switchgear, replacing bundled cables with copper busbars improves heat dissipation by 40% while reducing connection points.

Maintenance intervals impact long-term stability. Inspect connection tightness every 500 operating hours, use thermal imaging to monitor temperature distribution, and replace oxidized terminals promptly. In humid environments, apply anti-corrosion coatings to prevent electrochemical degradation that increases resistance.

Special scenarios demand tailored approaches:

  • High-frequency equipment (>1 kHz): Skin effect becomes significant; use multiple parallel fine strands instead of a single thick conductor.

  • Unbalanced three-phase systems: Size conductors based on the highest phase current; neutral conductors should be no smaller than phase conductors.

Experimental validation is essential. Build a test rig and run at 1.5× rated current for 2 hours, recording temperature-rise curves at critical points. Acceptance criteria: Ambient temp + Conductor temp rise ≤ Insulation thermal rating (e.g., ≤70°C for PVC).

Cable layout geometry affects cooling:

  • Maintain spacing ≥2× cable diameter for parallel runs.

  • Vertical installation dissipates heat 15–20% better than horizontal routing—prefer for high-current lines.

  • Minimum bend radius should be ≥6× conductor diameter to avoid localized heat trapping.

Monitor conductor aging dynamically: under normal use, copper resistance increases ~0.5% annually. After five years, re-evaluate ampacity. Install temperature sensors at critical nodes and implement real-time warning thresholds.

Copper-aluminum transition joints require special attention. Galvanic corrosion occurs at dissimilar metal interfaces—always use certified bi-metallic connectors and apply antioxidant grease. One substation failure analysis showed unprotected Cu-Al joints in humid conditions tripled contact resistance within three months, leading to meltdown.

Voltage drop must also be considered, especially in long-distance runs. Ensure terminal voltage remains ≥95% of nominal value. When both temperature rise and voltage drop constraints apply, select the conductor size dictated by the stricter requirement.

Insulation thermal resistance matters significantly. Thermal conductivity varies widely—e.g., silicone rubber is twice that of PVC, allowing 8–12% higher current at the same size. For high-temperature applications, use XLPE (cross-linked polyethylene) insulation, rated for continuous operation up to 90°C.

Finally, electromagnetic effects—skin effect and proximity effect—reduce effective conductor area in AC systems. For large single-core conductors, using multiple smaller parallel conductors is more effective for temperature control than a single oversized one.
We offer a professional calculator—please visit the Calculator section on our website if you need it!

Give a tip and encourage the author!
Recommended
Common Issues and Handling Measures for 145kV Disconnector Control Circuits
Common Issues and Handling Measures for 145kV Disconnector Control Circuits
The 145 kV disconnector is a critical switching device in substation electrical systems. It is used in conjunction with high-voltage circuit breakers and plays an important role in power grid operation:First, it isolates the power source, separating equipment under maintenance from the power system to ensure personnel and equipment safety;Second, it enables switching operations to change the system operating mode;Third, it is used to interrupt small-current circuits and bypass (loop) currents.Re
Felix Spark
11/20/2025
What are the six operating principles of disconnect switches?
What are the six operating principles of disconnect switches?
1. Operating Principle of the DisconnectorThe operating mechanism of the disconnector is connected to the active pole of the disconnector via a connecting tube. When the main shaft of the mechanism rotates 90°, it drives the insulating pillar of the active pole to rotate 90°. The bevel gears inside the base drive the insulating pillar on the other side to rotate in the opposite direction, thereby achieving opening and closing operations. The active pole, through inter-pole linkage tubes, drives
Echo
11/19/2025
36kV Disconnect Switch Selection Guide & Key Parameters
36kV Disconnect Switch Selection Guide & Key Parameters
Selection Guidelines for 36 kV Disconnect SwitchesWhen selecting the rated voltage, ensure that the disconnect switch’s rated voltage is equal to or higher than the nominal voltage of the power system at the installation point. For example, in a typical 36 kV power network, the disconnect switch must have a rated voltage of at least 36 kV.For rated current, selection should be based on the actual long-term load current. Generally, the switch’s rated current must be no less than the maximum conti
James
11/19/2025
Design of an Intelligent Control System for Fully Enclosed Disconnectors in Distribution Lines
Design of an Intelligent Control System for Fully Enclosed Disconnectors in Distribution Lines
Intelligentization has become an important development direction for power systems. As a critical component of the power system, the stability and safety of 10 kV distribution network lines are vital to the overall operation of the power grid. The fully enclosed disconnector, as one of the key devices in distribution networks, plays a significant role; thus, achieving its intelligent control and optimized design is of great importance for enhancing the performance of distribution lines.This pape
Dyson
11/17/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.