• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Standard Procedures for Substation Fault and Defect Handling

Felix Spark
Felix Spark
Field: Failure and maintenance
China

I. Fault Management

(1) Basic Principles of Fault Handling

  • Rapidly restrict the development of the fault, eliminate the root cause, and remove threats to personnel, power grid, and equipment safety.

  • Adjust and restore normal power grid operation modes. If the grid has split, quickly restore synchronization.

  • Maintain operation of healthy equipment and ensure continuous power supply to critical users, plant service loads, and substation auxiliary power.

  • Restore power supply to de-energized users and equipment as soon as possible.

(2) Fault Handling Procedures

  • Operation and maintenance (O&M) personnel shall promptly arrive at the site for preliminary inspection and judgment, and report weather conditions, monitoring information, and a brief summary of protective relay actions to dispatch and control personnel.

  • If work is ongoing at the site, notify personnel to stop work and preserve the scene; determine whether the work is related to the fault.

  • When a substation’s auxiliary power is lost or the system loses its neutral grounding point, change the operating mode and adjust relay protection settings according to dispatch instructions.

  • Conduct a detailed inspection of protective relay and automatic safety device signals, including fault phase, fault location, and other fault data. Reset signals, comprehensively analyze the fault nature, location, and affected power outage range, then inspect equipment within the protection zone. Report findings to dispatch and superior management.

  • After identifying the faulty equipment, isolate the fault point as instructed by dispatch and restore power to unaffected equipment.

(3) Fault Reporting Requirements

Immediate Reporting:

When a system fault occurs, relevant O&M units shall immediately report to the corresponding dispatch center:

  • Fault occurrence time;

  • Changes in the status of primary equipment at the substation after the fault;

  • Whether any equipment parameters (voltage, current, power) exceed limits, and whether any equipment requires emergency control;

  • Weather conditions and other directly observable phenomena.

Manned Substations:

  • Within 5 minutes: Report protective relay and automatic safety (referred to as "safety control") device actions, fault type, circuit breaker tripping, and reclosing operation status.

  • Within 15 minutes: Provide a preliminary inspection of primary and secondary equipment, confirm whether protection and safety control devices operated correctly, and determine if test energization is feasible.

  • Within 30 minutes: Report all protective relay actions, fault location results, and transmit event records, fault oscillography, fault reports, and on-site photos as required by dispatch.

  • Unmanned Substations:

  • Within 10 minutes (Monitoring Center): Report protective relay and safety control actions, fault type, circuit breaker tripping and reclosing status, and notify O&M personnel to proceed to the site.

  • Within 20 minutes (Monitoring Center): Report all protective relay actions and fault location results; confirm whether all protection and safety control devices operated correctly; determine if remote test energization is feasible based on conditions.

  • Within 20 minutes after O&M personnel arrive on site: Provide a preliminary inspection of primary and secondary equipment. If the faulty equipment remains out of service, on-site personnel shall confirm test energization feasibility, supplement the report on all protective actions and fault location, and transmit event records, fault oscillography, fault reports, and on-site photos as required.
    Note: Reporting time requirements may vary slightly among different dispatching authorities; always follow the specific requirements of the responsible dispatch center.

II. Defect Management

(1) Defect Classification

Critical Defects
Defects that directly threaten safe operation and must be handled immediately; otherwise, they may lead to equipment damage, personal injury, widespread blackouts, or fire at any moment.

Serious Defects
Defects posing serious threats to personnel or equipment that can temporarily remain in service but must be addressed as soon as possible.

General Defects
All other defects not classified as critical or serious—typically minor in nature, with limited impact on safe operation.

(2) Defect Identification, Documentation, and Reporting

  • Defects identified by maintenance or testing personnel shall be promptly communicated to O&M personnel.

  • After discovery, the O&M team shall classify the defect according to established standards and initiate the defect management process promptly.

  • When registering defects in the PMS (Production Management System), entries must strictly follow the defect standard library and actual field conditions, including: main equipment, component, component type, defect location, description, and classification basis.

  • For defects not covered in the standard library, classification shall be based on actual conditions, with clear documentation of the defect details.

  • For defects that cannot be clearly classified, the higher-level unit shall organize a review to determine the classification.

  • Critical or serious defects that may affect the operation mode of primary/secondary equipment or centralized monitoring shall be reported to the corresponding dispatch personnel. Until resolved, O&M personnel shall increase inspection frequency.

(3) Defect Handling

  • Defect Handling Timeframes:

    • Critical defects: resolved within 24 hours;

    • Serious defects: resolved within 1 month;

    • General defects requiring outage: resolved within one maintenance cycle;

    • General defects not requiring outage: resolved within 3 months (in principle).

  • Upon discovering a critical defect, immediately notify dispatch personnel to take emergency measures.

  • Before critical or serious defects are resolved, the O&M unit shall develop preventive measures and emergency response plans based on the defect condition.

  • For defects affecting remote control operations, prompt handling is required. Both before and after resolution, the dispatch center must be informed, and records maintained. Remote control tests may be conducted in coordination with the dispatch center if necessary.

(4) Defect Resolution Verification (Acceptance)

  • After defect handling, O&M personnel shall conduct on-site verification to confirm the defect has been eliminated.

  • Upon successful acceptance, after maintenance personnel have recorded the handling details in the PMS, O&M personnel shall enter the acceptance comments into the PMS to complete the closed-loop management process.

Give a tip and encourage the author!
Recommended
PT Fuse Slow Blow: Causes, Detection & Prevention
PT Fuse Slow Blow: Causes, Detection & Prevention
I. Fuse Structure and Root Cause AnalysisSlow Fuse Blowing:From the design principle of fuses, when a large fault current passes through the fuse element, due to the metal effect (certain refractory metals become fusible under specific alloy conditions), the fuse first melts at the soldered tin ball. The arc then rapidly vaporizes the entire fuse element. The resulting arc is quickly extinguished by quartz sand.However, due to harsh operating environments, the fuse element may age under the comb
Edwiin
10/24/2025
Why Fuses Blow: Overload, Short Circuit & Surge Causes
Why Fuses Blow: Overload, Short Circuit & Surge Causes
Common Causes of Fuse BlowingCommon reasons for fuse blowing include voltage fluctuations, short circuits, lightning strikes during storms, and current overloads. These conditions can easily cause the fuse element to melt.A fuse is an electrical device that interrupts the circuit by melting its fusible element due to heat generated when current exceeds a specified value. It operates on the principle that, after an overcurrent persists for a certain period, the heat produced by the current melts
Echo
10/24/2025
Fuse Maintenance & Replacement: Safety and Best Practices
Fuse Maintenance & Replacement: Safety and Best Practices
1. Fuse MaintenanceFuses in service should be regularly inspected. The inspection includes the following items: Load current should be compatible with the rated current of the fuse element. For fuses equipped with a fuse blown indicator, check whether the indicator has actuated. Check the conductors, connection points, and the fuse itself for overheating; ensure connections are tight and making good contact. Inspect the fuse exterior for cracks, contamination, or signs of arcing/discharge. Liste
James
10/24/2025
Maintenance and Repair Items for 10kV High-Voltage Switchgear
Maintenance and Repair Items for 10kV High-Voltage Switchgear
I. Routine Maintenance and Inspection(1) Visual Inspection of Switchgear Enclosure No deformation or physical damage to the enclosure. Protective paint coating shows no severe rust, peeling, or flaking. Cabinet is securely installed, clean on the surface, and free of foreign objects. Nameplates and identification labels are neatly affixed and not falling off.(2) Check of Switchgear Operating Parameters Instruments and meters indicate normal values (comparable to typical operating data, with no s
Edwiin
10/24/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.