Analisis sa Konsetrasyon sa Gas sa mga Mataas na Kuryente Reactor sa Large-Scale Hydroelectric Generator Sets

Oliver Watts
Oliver Watts
Larangan: Pagsusi ug Paghunahuna
China

1. Prinsip Pagkagenera ug Analisis sa Gas sa High - Voltage Reactors

Ang mga high - voltage reactors gigamit og langis ug insulating paper isip insulation. Sa normal nga operasyon, mahimong adunay lokal nga pag-init o discharge (e.g., problema sa iron core/winding, inter - turn short circuits), kasagaran nagresulta sa pagcrack sa insulation ug pagprodyus sa mga gas sama sa hydrocarbons (methane, etc.), CO, CO2, H2). Ang mga gas kini nagpakita sa internal insulation status, makapahimo og real - time monitoring.

Para sa mga closed oil - filled reactors, ang insulation aging ug oil oxidation nagpadayon sa paggenerate og (CO)/(CO2). Ang ilang concentration mosaka sa panahon tungod sa accumulation, kini way makapaghukom sa fault. Apan ang gas production rate (average daily gas output) makatubag sa pagdistinguish sa normal aging gikan sa faults:

Ania: γa = absolute gas production rate (mL/d); (Ci,2)/(Ci,1) = gas concentrations sa ikaduha/ikaduhang sampling (μL/L); Δt = aktwal nga operasyon interval (d); m = total nga volume sa langis (t); ρ = density sa langis (t/m3).

1.2 Pamaagi sa Analisis sa Concentration sa Gas sa High - Voltage Reactors

Ang regular nga oil chromatography tests nagtrack sa long - term sa concentration sa oil - gas, nagpakita sa insulation aging/deterioration. Gamiton ang three - phase reactor data para sa scientific analysis. Ang continuous monitoring ug gas production rate calculation makatabang sa accurate nga pag-identify sa insulation status ug pre - warn sa faults.

2. Aktual nga Kaso

Sa regular nga inspection sa usa ka high - voltage reactor (model: BKD - 16700/550 - 66) sa usa ka power station, ang CO three - phase concentrations mao ang 1089.08 μL/L (A), 1152.71 μL/L (B), 1338.24 μL/L (C); CO₂ three - phase data: 4955.73 μL/L (A), 5431.25 μL/L (B), 6736.33 μL/L (C). Ang pipila sa mga balore nagsobra sa alarm threshold (CO: 850 μL/L; CO₂: 5000 μL/L). Ang normal nga paper insulation aging ug fault - induced cracking parehas nagprodyus og CO/CO₂. Ang solid insulation aging nagpakita sa oil - dissolved CO/CO₂, wala klaro nga boundaries/patterns. Aron masabtan kon unsa ang mga alarm - level concentrations kay normal, gianalisa ang historical dissolved gas test reports aron matumbong ang gas production trends ug assess ang current state sa reactor.

2.1 Analisis sa Production Rate sa CO & CO₂ sa Langis sa Reactor

Ang annual absolute production rates sa CO nasa Table 1, ang trends nasa Figure 1. Ang annual rates sa CO₂ nasa Table 2, ang trends nasa Figure 2.

2.2 Analisis sa Ratio sa Increment sa Gas sa Langis sa usa ka High - Voltage Reactor sa usa ka Power Station

Batasan sa judgment sa CO ug CO2 sa section 10.3 sa DL/T722 standard, kon suspekto sa aging sa solid insulation material sa equipment, kasagaran CO2/CO > 7; kon suspekto nga ang fault involve ang solid insulation material, CO2/CO < 3.

Gibutangan og calculations ang data sa mga tuig, wala adunay lisud nga less than 3 o greater than 7. Wala usab adunay sudden change sa growth trend, nagpakita nga wala adunay fault o aging nga involve ang solid materials. Ang curve sa ratio sa offline data sa CO2/CO gas sa previous times nasa Figure 3.

Sumala sa Guidelines for Analysis and Judgment of Dissolved Gases in Transformer Oil (DL/T722), ang calculated incremental ratios sa CO₂ ug CO sa mga tuig ug ang gas production rates parehas gi-maintain sa standard ranges. Wala adunay occurrence sa solid insulation faults o aging phenomena (ang standard para sa absolute gas production rate sa CO₂ mao ang 200 mL/d, ug para sa CO mao ang 100 mL/d).

2.3 Data Analysis

  • Trend sa Gas Content
    Since commissioning, ang CO/CO₂ sa reactor nagpakita og overall upward trend. Ang mga fluctuations relate sa measurement errors ug temperature changes; wala adunay sudden spikes, stable ang gas - production curve slope.

  • CO Production Rate
    Annual absolute CO production rates (6&ndash;22 mL/d since operation) follow a &ldquo;decrease - increase - decrease - increase&rdquo; pattern, gradually flattening. Per DL/T722, rates stay below the 100 mL/d alert. CO&rsquo;s low oil solubility ug temperature - driven volatility (no sustained growth) confirm no faults.

  • CO₂ Production Rate
    Annual absolute CO₂ production rates (40&ndash;100 mL/d since operation) decline yearly, trending flat. Per DL/T722 - 2014, rates stay below the 200 mL/d alert. Initial high production aligns with normal operation; no sustained growth (temperature - driven volatility) confirms no faults.

  • CO₂/CO Ratio
    Offline CO₂/CO ratios (4&ndash;7 since commissioning) align with DL/T722 - 2014 (10.2.3.1: use CO₂/CO increments for solid - insulation faults). Annual increment ratios (4&ndash;6, Figure 3) stay within 3&ndash;7, confirming no solid - insulation faults/aging.

  • High - Voltage Insulation
    Latest tests show:

  • Insulation resistance &ge; 200 G&Omega;;

  • Winding tan&delta; < 0.6 (&le;30% increase vs. history); capacitance change &le; 3%;

  • DC resistance differences: <2% of 3 - phase avg. (no neutral lead: <1% avg.); &le;2% vs. historical values.

All data meet DL/T 596 - 2021 requirements.

Over 5 years (no oil filtration), CO/CO₂ concentrations rose faster due to their closed - environment accumulation ug high operating temps (max 66&deg;C), accelerating oil/insulation oxidation/cracking. No internal faults or insulation aging exist.

3. Recommendations

Analyzing characteristic gases identifies faults/deterioration for targeted maintenance, ensuring grid stability. For long - term reactor O&M:

  • Check seals (reactor body, oil conservator) for slow gas - content growth; replace if needed.

  • Enhance oil - sample chromatography: measure furfural/nitrogen - oxygen content (pre - filtration) to assess oil/paper oxidation.

  • Perform oil filtration; track post - filtration samples.

  • Monitor operations for overloads, short - term current surges, and abnormal oil - temp spikes.

Maghatag og tip ug pagsalig sa author
Gipareserbado
Minimum nga Operasyonal nga Voltaje para sa Vacuum Circuit Breakers
Minimum nga Operasyonal nga Voltaje para sa Vacuum Circuit Breakers
Minimum Operating Voltage for Trip and Close Operations in Vacuum Circuit Breakers1. IntroductionKung makita nimo ang termino "vacuum circuit breaker," mahimong dili familiar kini. Apan kon mogwarta ta og "circuit breaker" o "power switch," daghan sa mga tawo ang mosabot kini. Sa katunayan, ang vacuum circuit breakers mao ang importante nga komponente sa modernong sistema sa kuryente, responsable sa pagprotekta sa mga kuryente gikan sa pinsala. Karon, atong i-explore ang importante nga konsepto
Dyson
10/18/2025
Effektibo nga Optymizasyon sa Wind-PV Hybrid System nga may Storage
Effektibo nga Optymizasyon sa Wind-PV Hybrid System nga may Storage
1. Pag-analisa sa mga Katangian sa Generasyon sa Kuryente gikan sa Hangin ug Solar PhotovoltaicAng pag-analisa sa mga katangian sa generasyon sa kuryente gikan sa hangin ug solar photovoltaic (PV) mahimong pundok sa pagdisenyo og komplementaryong sistema. Ang estadistikal nga analisis sa taas nga datos sa hangin ug solar irradiance para sa isyuha nga rehiyon nagpakita nga ang mga resources sa hangin adunay seasonal nga pagkakaiba, uban sa mas taas nga bilis sa hangin sa yelo ug tagsibol ug mas b
Dyson
10/15/2025
Sistema nga Iot nga Gigikanan sa Hybrid nga Wind-Solar Power para sa Real-Time nga Monitoring sa Tubo sa Tubig
Sistema nga Iot nga Gigikanan sa Hybrid nga Wind-Solar Power para sa Real-Time nga Monitoring sa Tubo sa Tubig
I. Kasinatian ug Nagkalabay nga ProblemaKaron, ang mga kompanya sa paghatag og tubig adunay makapadlan nga mga network sa pipeline nga gihatag sa ilalum sa yuta sa urban ug rural nga mga dapit. Ang real-time monitoring sa data sa operasyon sa pipeline mahimong importante alang sa efektibong komando ug kontrol sa produksyon ug distribusyon sa tubig. Isip resulta, kinahanglan nga imbuhan ang daghang mga estasyon sa monitoring sa data sa pipelan. Subalang, dili kadalasan ang adunay matul-an ug hand
Dyson
10/14/2025
Paunsa ang usa ka sistema sa gudang nga may basehan sa AGV
Paunsa ang usa ka sistema sa gudang nga may basehan sa AGV
Sistema nga Intelligente sa Warehouse Logistics Batasan sa AGVHuman sa matangis na pag-abot sa industriya sa logistics, nagdako ang kahigayonan sa yuta, ug tumaas ang gasto sa trabaho, ang mga warehouse—nga nagserbiha isip key logistics hubs—nagpakita og significant challenges. Tungod kay ang mga warehouse naging mas dako, ang frequency sa operasyon nataas, ang komplikado sa impormasyon nataas, ug ang order-picking tasks naging mas mahirap, ang pag-achieve og low error rates ug reduced labor cos
Dyson
10/08/2025
Inquiry
Pangutana
Pangutana sa IEE-Business Application
Pangita og mga equipment gamit ang IEE-Business app asa asa ug kailan man sugad og pagkuha og solusyon pagsulay sa mga eksperto ug pagpadayon sa industriya nga pakisayran suportahan ang imong proyekto sa kuryente ug negosyo