Analysis of Gas Concentration in High - Voltage Reactors of Large - Scale Hydroelectric Generator Sets

Oliver Watts
07/11/2025

1.Gas Generation and Analysis Principle of High - Voltage Reactors
High - voltage reactors use oil and insulating paper for insulation. Normal operation may see local overheating or discharges (e.g., iron core/winding issues, inter - turn short circuits), causing insulation cracking and producing gases like hydrocarbons (methane, etc.), CO, CO2, H2). These gases reflect internal insulation status, enabling real - time monitoring.
For closed oil - filled reactors, insulation aging and oil oxidation continuously generate (CO)/(CO2). Their concentrations rise over time due to accumulation, so pure (CO)/(CO2) increase can’t judge faults. But gas production rate (average daily gas output) helps distinguish normal aging from faults:
Here: γa = absolute gas production rate (mL/d); (Ci,2)/(Ci,1) = gas concentrations of second/first sampling (μL/L); Δt = actual operation interval (d); m = total oil volume (t); ρ = oil density (t/m3).
1.2 Gas Concentration Analysis Method for High - Voltage Reactors
Regular oil chromatography tests track oil - gas concentrations long - term, showing insulation aging/deterioration. Use three - phase reactor data for scientific analysis. Continuous monitoring and gas production rate calculation help accurately identify insulation status and pre - warn faults.
2. Actual Case
During regular inspection of a power station’s high - voltage reactor (model: BKD - 16700/550 - 66), CO three - phase concentrations were 1089.08 μL/L (A), 1152.71 μL/L (B), 1338.24 μL/L (C); CO₂ three - phase data: 4955.73 μL/L (A), 5431.25 μL/L (B), 6736.33 μL/L (C). Some values exceeded alarm thresholds (CO: 850 μL/L; CO₂: 5000 μL/L).Normal paper insulation aging and fault - induced cracking both produce CO/CO₂. Solid insulation aging reflects in oil - dissolved CO/CO₂, with unclear boundaries/patterns.To determine if these alarm - level concentrations are normal, historical dissolved gas test reports were analyzed to identify gas production trends and assess the reactor’s current state.
2.1 CO & CO₂ Production Rate Analysis in Reactor Oil
CO annual absolute production rates are in Table 1, with trends in Figure 1. CO₂ annual rates are in Table 2, trends in Figure 2.
2.2 Analysis of Gas Increment Ratio in the Oil of a High - Voltage Reactor at a Certain Power Station
With reference to the judgment on CO and CO2 in section 10.3 of the DL/T722 standard, when suspecting the aging of the solid insulation material of the equipment, generally CO2/CO > 7; when suspecting that the fault involves the solid insulation material, CO2/CO < 3.
Calculations were made on the data over the years, and none were less than 3 or greater than 7. There was no sudden change in the growth trend, indicating that there was no fault or aging involving solid materials. The curve of the ratio of offline data of CO2/CO gas over previous times is shown in Figure 3.
In accordance with the Guidelines for Analysis and Judgment of Dissolved Gases in Transformer Oil (DL/T722), the calculated incremental ratios of CO₂ and CO over the years and the gas production rates are both maintained within the standard ranges. There is no occurrence of solid insulation faults or aging phenomena (the standard for the absolute gas production rate of CO₂ is 200 mL/d, and that for CO is 100 mL/d).
2.3 Data Analysis
  • Gas Content Trend
    Since commissioning, CO/CO₂ in the reactor shows an overall upward trend. Fluctuations relate to measurement errors and temperature changes; no sudden spikes occur, with a stable gas - production curve slope.
  • CO Production Rate
    Annual absolute CO production rates (6–22 mL/d since operation) follow a “decrease - increase - decrease - increase” pattern, gradually flattening. Per DL/T722, rates stay below the 100 mL/d alert. CO’s low oil solubility and temperature - driven volatility (no sustained growth) confirm no faults.
  • CO₂ Production Rate
    Annual absolute CO₂ production rates (40–100 mL/d since operation) decline yearly, trending flat. Per DL/T722 - 2014, rates stay below the 200 mL/d alert. Initial high production aligns with normal operation; no sustained growth (temperature - driven volatility) confirms no faults.
  • CO₂/CO Ratio
    Offline CO₂/CO ratios (4–7 since commissioning) align with DL/T722 - 2014 (10.2.3.1: use CO₂/CO increments for solid - insulation faults). Annual increment ratios (4–6, Figure 3) stay within 3–7, confirming no solid - insulation faults/aging.
  • High - Voltage Insulation
    Latest tests show:
  • Insulation resistance ≥ 200 GΩ;
  • Winding tanδ < 0.6 (≤30% increase vs. history); capacitance change ≤ 3%;
  • DC resistance differences: <2% of 3 - phase avg. (no neutral lead: <1% avg.); ≤2% vs. historical values.
All data meet DL/T 596 - 2021 requirements.
Over 5 years (no oil filtration), CO/CO₂ concentrations rose faster due to their closed - environment accumulation and high operating temps (max 66°C), accelerating oil/insulation oxidation/cracking. No internal faults or insulation aging exist.
3. Recommendations
Analyzing characteristic gases identifies faults/deterioration for targeted maintenance, ensuring grid stability. For long - term reactor O&M:
  • Check seals (reactor body, oil conservator) for slow gas - content growth; replace if needed.
  • Enhance oil - sample chromatography: measure furfural/nitrogen - oxygen content (pre - filtration) to assess oil/paper oxidation.
  • Perform oil filtration; track post - filtration samples.
  • Monitor operations for overloads, short - term current surges, and abnormal oil - temp spikes.
Oliver Watts

Hey! I'm Oliver Watts, an electrical engineer in Inspection and Testing. With years of hands - on experience, I ensure electrical systems meet top safety and performance standards. Using advanced gear, I conduct diverse tests, easily spotting issues in both large - scale industrial and small - scale commercial setups. I love teaming up, sharing knowledge, and keeping up with industry regs. Also, I'm skilled at data analysis with software. If you're into electrical inspection or just want to chat engineering, reach out. Let's connect and explore!

Research on Low - Voltage Anti - DC Current Transformer and Detection Device
Research on Low - Voltage Anti - DC Current Transformer and Detection Device
1. Overview of Components and IssuesTA (low-voltage current transformer) and electric energy meters are key components of low-voltage electric energy metering. The load current of such meters is no less than 60A. Electric energy meters vary in type, model, and anti-DC performance, and are connected in series in the metering device. Due to the lack of anti-DC capability, they suffer from metering errors under DC component loads, usually caused by non-linear loads. With the increasing use of DC or
Dyson
07/16/2025
Anti - Theft Device for Low - Voltage Current Transformers
Anti - Theft Device for Low - Voltage Current Transformers
1. Innovation BackgroundWith the progress of society and economic development, the electricity demand of power users is expanding increasingly. Lawbreakers, aiming to save electricity costs and pursue high profits, gradually use high - tech methods to steal electricity, causing huge economic losses to power supply enterprises. Currently, popular electricity theft methods in the market include illegally opening the wiring cover of low - voltage transformers in electric energy metering boxes, alte
Dyson
07/16/2025
What aspects should be taken into consideration during the design of AIS voltage transformers?
What aspects should be taken into consideration during the design of AIS voltage transformers?
I. Key Elements of Mechanical Structure DesignThe mechanical structure design of AIS voltage transformers ensures long - term stable operation. For 66 kV outdoor AIS voltage transformers (pillar - type structure):Pillar Material: Use epoxy resin casting + metal frame for mechanical strength, pollution/weather resistance. Special design needed for 66 kV (vs 35 kV & below). Dry - type insulation (porcelain/epoxy shell) requires sufficient bending/impact resistance for harsh outdoors.Heat Dissi
Dyson
07/15/2025
Exploring the Design and Application of Photoelectric Current Transformers in GIS
Exploring the Design and Application of Photoelectric Current Transformers in GIS
1.Design and Application Example of Photoelectric Current Transformer in GISThis article takes a 126kV GIS project as a specific example to deeply explore the design ideas and practical application of photoelectric current transformers in the GIS system. Since this GIS project was officially put into operation, the power system has remained stable, with no major failures occurring, and the operation status is relatively ideal.1.1 Design and Application Ideas of Photoelectric Current TransformerI
Dyson
07/07/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!