Analysis of Gas Concentration in High - Voltage Reactors of Large - Scale Hydroelectric Generator Sets

07/11/2025

1.Gas Generation and Analysis Principle of High - Voltage Reactors
High - voltage reactors use oil and insulating paper for insulation. Normal operation may see local overheating or discharges (e.g., iron core/winding issues, inter - turn short circuits), causing insulation cracking and producing gases like hydrocarbons (methane, etc.), CO, CO2, H2). These gases reflect internal insulation status, enabling real - time monitoring.
For closed oil - filled reactors, insulation aging and oil oxidation continuously generate (CO)/(CO2). Their concentrations rise over time due to accumulation, so pure (CO)/(CO2) increase can’t judge faults. But gas production rate (average daily gas output) helps distinguish normal aging from faults:
Here: γa = absolute gas production rate (mL/d); (Ci,2)/(Ci,1) = gas concentrations of second/first sampling (μL/L); Δt = actual operation interval (d); m = total oil volume (t); ρ = oil density (t/m3).
1.2 Gas Concentration Analysis Method for High - Voltage Reactors
Regular oil chromatography tests track oil - gas concentrations long - term, showing insulation aging/deterioration. Use three - phase reactor data for scientific analysis. Continuous monitoring and gas production rate calculation help accurately identify insulation status and pre - warn faults.
2. Actual Case
During regular inspection of a power station’s high - voltage reactor (model: BKD - 16700/550 - 66), CO three - phase concentrations were 1089.08 μL/L (A), 1152.71 μL/L (B), 1338.24 μL/L (C); CO₂ three - phase data: 4955.73 μL/L (A), 5431.25 μL/L (B), 6736.33 μL/L (C). Some values exceeded alarm thresholds (CO: 850 μL/L; CO₂: 5000 μL/L).Normal paper insulation aging and fault - induced cracking both produce CO/CO₂. Solid insulation aging reflects in oil - dissolved CO/CO₂, with unclear boundaries/patterns.To determine if these alarm - level concentrations are normal, historical dissolved gas test reports were analyzed to identify gas production trends and assess the reactor’s current state.
2.1 CO & CO₂ Production Rate Analysis in Reactor Oil
CO annual absolute production rates are in Table 1, with trends in Figure 1. CO₂ annual rates are in Table 2, trends in Figure 2.
2.2 Analysis of Gas Increment Ratio in the Oil of a High - Voltage Reactor at a Certain Power Station
With reference to the judgment on CO and CO2 in section 10.3 of the DL/T722 standard, when suspecting the aging of the solid insulation material of the equipment, generally CO2/CO > 7; when suspecting that the fault involves the solid insulation material, CO2/CO < 3.
Calculations were made on the data over the years, and none were less than 3 or greater than 7. There was no sudden change in the growth trend, indicating that there was no fault or aging involving solid materials. The curve of the ratio of offline data of CO2/CO gas over previous times is shown in Figure 3.
In accordance with the Guidelines for Analysis and Judgment of Dissolved Gases in Transformer Oil (DL/T722), the calculated incremental ratios of CO₂ and CO over the years and the gas production rates are both maintained within the standard ranges. There is no occurrence of solid insulation faults or aging phenomena (the standard for the absolute gas production rate of CO₂ is 200 mL/d, and that for CO is 100 mL/d).
2.3 Data Analysis
  • Gas Content Trend
    Since commissioning, CO/CO₂ in the reactor shows an overall upward trend. Fluctuations relate to measurement errors and temperature changes; no sudden spikes occur, with a stable gas - production curve slope.
  • CO Production Rate
    Annual absolute CO production rates (6–22 mL/d since operation) follow a “decrease - increase - decrease - increase” pattern, gradually flattening. Per DL/T722, rates stay below the 100 mL/d alert. CO’s low oil solubility and temperature - driven volatility (no sustained growth) confirm no faults.
  • CO₂ Production Rate
    Annual absolute CO₂ production rates (40–100 mL/d since operation) decline yearly, trending flat. Per DL/T722 - 2014, rates stay below the 200 mL/d alert. Initial high production aligns with normal operation; no sustained growth (temperature - driven volatility) confirms no faults.
  • CO₂/CO Ratio
    Offline CO₂/CO ratios (4–7 since commissioning) align with DL/T722 - 2014 (10.2.3.1: use CO₂/CO increments for solid - insulation faults). Annual increment ratios (4–6, Figure 3) stay within 3–7, confirming no solid - insulation faults/aging.
  • High - Voltage Insulation
    Latest tests show:
  • Insulation resistance ≥ 200 GΩ;
  • Winding tanδ < 0.6 (≤30% increase vs. history); capacitance change ≤ 3%;
  • DC resistance differences: <2% of 3 - phase avg. (no neutral lead: <1% avg.); ≤2% vs. historical values.
All data meet DL/T 596 - 2021 requirements.
Over 5 years (no oil filtration), CO/CO₂ concentrations rose faster due to their closed - environment accumulation and high operating temps (max 66°C), accelerating oil/insulation oxidation/cracking. No internal faults or insulation aging exist.
3. Recommendations
Analyzing characteristic gases identifies faults/deterioration for targeted maintenance, ensuring grid stability. For long - term reactor O&M:
  • Check seals (reactor body, oil conservator) for slow gas - content growth; replace if needed.
  • Enhance oil - sample chromatography: measure furfural/nitrogen - oxygen content (pre - filtration) to assess oil/paper oxidation.
  • Perform oil filtration; track post - filtration samples.
  • Monitor operations for overloads, short - term current surges, and abnormal oil - temp spikes.

Focused on the design of electrical equipment, proficient in electrical principles and relevant specifications, and skilled in using design software. From intelligent substations to various types of electrical equipment, I am adept at optimizing design solutions, integrating new technologies. With practical experience and collaborative management capabilities, I deliver outstanding electrical design achievements.

Key Technologies of Low-Voltage DC Solid-State Circuit Breakers
Key Technologies of Low-Voltage DC Solid-State Circuit Breakers
1 Technical Challenges1.1Stability of Device ParallelingIn practical applications, the current-carrying capacity of a single power electronic device is relatively limited. To meet high-current requirements, multiple devices are often connected in parallel. However, parameter variations between devices—such as slight differences in on-resistance and threshold voltage—can cause uneven current distribution during parallel operation. During switching transients, parasitic inductance and capacitance
09/02/2025
Research on Bridge-Type Fault Current Limiters
Research on Bridge-Type Fault Current Limiters
1 Bridge-Type Superconducting Fault Current Limiter1.1 Structure and Operating Principle of the Bridge-Type SFCLFigure 1 shows the single-phase circuit diagram of the bridge-type SFCL, which consists of four diodes D₁ to D₄, a DC bias voltage source V_b, and a superconducting coil L. A circuit breaker CB is connected in series with the limiter to interrupt the fault current after it has been limited. The bias source V_b provides a bias current i_b to the superconducting coil L. The voltage of V_
08/25/2025
What should be paid attention to in the design of low-voltage pole-mounted circuit breakers?
What should be paid attention to in the design of low-voltage pole-mounted circuit breakers?
Low-voltage pole-mounted circuit breakers are critical protective and control devices in power systems, whose design and operation directly affect system safety and reliability. Their design must comprehensively address environmental adaptability, electrical parameter coordination, and actuator selection to ensure stable operation under diverse conditions. During operation, strict adherence to safety protocols, regular maintenance, and proper handling of exceptional situations are essential to p
08/21/2025
Study on Steep - Wave Breakdown Characteristics of Hybrid Porcelain Insulators
Study on Steep - Wave Breakdown Characteristics of Hybrid Porcelain Insulators
Porcelain and glass insulators exhibit excellent insulation performance and mechanical strength, but are prone to pollution flashover under severe contamination, threatening the stable operation of power grids. To enhance the pollution flashover resistance of external insulation, manufacturers commonly apply room-temperature vulcanized silicone rubber (RTV) coatings with superior hydrophobicity and hydrophobicity transfer properties onto insulator surfaces, thereby reducing flashover risks. Init
08/20/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!