Transformer Main Protection: Gas Protection vs Differential Protection Explained

Rockwell
Field: Manufacturing
China

Transformer Main Protection

The main protection for transformers consists of gas protection and differential protection.

Gas Protection

Gas protection is a protective mechanism that responds to internal faults within the transformer tank and to a drop in oil level. When an internal fault occurs in the transformer tank, gases generated from the decomposition of transformer oil and insulation materials due to fault currents and arcing flow from the tank toward the upper part of the oil conservator. The protection that operates based on these gas and oil flows is known as gas protection. Designed according to the characteristic that gases are produced during internal transformer faults, gas protection serves as the primary protection for internal transformer faults and is unique to transformers.

  • Scope of Gas Protection

    • Internal phase-to-phase short circuits in the transformer.

    • Turn-to-turn short circuits, short circuits between windings and the core or tank.

    • Core faults (such as overheating and burnout).

    • Decrease in oil level or oil leakage.

    • Poor contact in tap changers or defective conductor welding.

  • Advantages and Disadvantages of Gas Protection

    • Cannot detect external transformer faults (such as those on bushings and lead wires), so it cannot serve as the sole protection for all types of transformer faults.

    • Poor resistance to external interference; for example, it is prone to maloperation during earthquakes.

    • Advantages: Simple structure, fast operation, high sensitivity. It can detect various internal tank faults, including minor ones such as slight turn-to-turn short circuits and core damage. It can detect faults that differential protection may miss, such as minor inter-turn faults, core problems, and ingress of air into the transformer.

    • Disadvantages:

Differential Protection

Transformer longitudinal differential protection, commonly referred to as differential protection, is designed based on the circulating current principle. Differential protection is the main protection for various short-circuit faults in transformer windings, bushings, and lead wires. However, it is not highly sensitive to certain internal faults such as minor turn-to-turn short circuits. Therefore, differential protection and gas protection are typically used together to form the main protection system for transformers. Longitudinal differential protection is recommended for large, critical transformers, or when the sensitivity of instantaneous overcurrent protection is insufficient.

  • Scope of Differential Protection
    The protection zone covers the primary electrical components between the current transformers on all sides of the transformer.

    • Multi-phase short circuits in the transformer leads and windings.

    • Severe turn-to-turn short circuits.

    • Grounding faults on windings and leads in high-current grounding systems.

  • Advantages and Disadvantages of Differential Protection

    • Advantages: Capable of quickly and effectively clearing faults within its protection zone. When correctly wired and properly commissioned, it operates reliably without maloperation.

    • Disadvantages: Not sufficiently sensitive to minor internal turn-to-turn short circuits.

Give a tip and encourage the author!
Recommended
What Is a Magnetic Levitation Transformer? Uses & Future
What Is a Magnetic Levitation Transformer? Uses & Future
In today’s rapidly advancing technological era, the efficient transmission and conversion of electric power have become continuous goals pursued across various industries. Magnetic levitation transformers, as an emerging type of electrical equipment, are gradually demonstrating their unique advantages and broad application potential. This article will thoroughly explore the application fields of magnetic levitation transformers, analyze their technical characteristics and future development tren
Baker
12/09/2025
How Often Should Transformers Be Overhauled?
How Often Should Transformers Be Overhauled?
1. Transformer Major Overhaul Cycle The main transformer shall undergo a core-lifting inspection before being put into service, and thereafter a core-lifting overhaul shall be performed every 5 to 10 years. Core-lifting overhaul shall also be carried out if a fault occurs during operation or if issues are identified during preventive tests. Distribution transformers operating continuously under normal load conditions may be overhauled once every 10 years. For on-load tap-changing transformers, t
Felix Spark
12/09/2025
Low-Voltage Distribution Lines and Power Distribution Requirements for Construction Sites
Low-Voltage Distribution Lines and Power Distribution Requirements for Construction Sites
Low-voltage distribution lines refer to the circuits that, through a distribution transformer, step down the high voltage of 10 kV to the 380/220 V level—i.e., the low-voltage lines running from the substation to the end-use equipment.Low-voltage distribution lines should be considered during the design phase of substation wiring configurations. In factories, for workshops with relatively high power demand, dedicated workshop substations are often installed, where transformers supply power direc
James
12/09/2025
Adjustment and Precautions for H61 Oil Power 26kV Electric Transformer Tap Changers
Adjustment and Precautions for H61 Oil Power 26kV Electric Transformer Tap Changers
Preparatory Work Before Adjusting the Tap Changer of H61 Oil Power 26kV Electric Transformer Apply for and issue a work permit; carefully fill out the operation ticket; conduct a simulation board operation test to ensure the operation is error-free; confirm the personnel who will carry out and supervise the operation; if load reduction is required, notify affected users in advance. Before construction, power must be disconnected to take the transformer out of service, and voltage testing must be
James
12/08/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.