• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Kanbarê Sîpana ji bo RMU-yan 24kV bi Şoreşdarên Eko: Bisîv û Yekînlav

Dyson
qalab: Standardsên Elektrîkî
China

Bingehên bêrdestkirî pêşkeftî bi serbiseyên hewlêr taybetand bêrdestkirina ji bo yekîneyên 24 kV ya dawiyên sîmoran e. Bi hevparastina performansa bêrdestkirî û qubûlkirina biçûk, bikarhêneriya bêrdestkirî pêşkeftî pêşkeftina testên bêrdestkirî digere ne ku di demê de çendiyên nînivîsa an nînivîs-zerdeştê biguhezine. Encapsulation of the pole can address the insulation of the vacuum interrupter and its connected conductors.

Ji bo baranê 24 kV a dergeha, bi xwazdaya phase spacing li ser 110 mm, vulcanizing the busbar surface can reduce the electric field strength and the electric field non-uniformity coefficient. Table 4 calculates the electric field under different phase spacings and busbar insulation thicknesses. It can be seen that by appropriately increasing the phase spacing to 130 mm and applying 5 mm epoxy vulcanization treatment to the round busbar, the electric field strength reaches 2298 kV/m, which still has a certain margin compared to the maximum electric field strength of 3000 kV/m that dry air can withstand.

Table 1 Electric field conditions under different phase spacings and busbar insulation thicknesses

Phase Spacing mm 110 110 110 120 120 130
Copper Bar Diameter mm 25 25 25 25 25 25
Vulcanization Thickness mm 0
2
5 0 5 5
Maximum Electric Field Strength in Air Gap under Composite Insulation (Eqmax) kV/m 3037.25 2828.83 2609.73 2868.77 2437.53 2298.04
Insulation Utilization Coefficient (q) / 0.48 0.55 0.64 0.46 0.60 0.57
Electric Field Unevenness Coefficient (f) / 2.07 1.83 1.57 2.18 1.66 1.75

Due to the low dielectric strength of dry air, solid insulation cannot solve the problem of voltage withstand at the isolation break. A double-break disconnector uses two gas gaps in series to effectively divide the voltage. Electric field shielding and grading rings are designed at locations with concentrated electric fields, such as the stationary contacts of the isolator and grounding switch, to reduce electric field intensity and effectively minimize the size of the air gap. As shown in Figure 1, the double-break mechanism achieves operational states—working, isolated, and grounded—through enhanced rotation of a nylon main shaft. The grading ring at the stationary contact has a diameter of 60 mm and is treated with epoxy vulcanization; a 100 mm clearance can withstand a 150 kV lightning impulse voltage.

RMU.jpg

Other solutions, such as longitudinal single-phase arrangement using high-strength alloy enclosures for each phase or moderately increasing the gas pressure, can also meet the 24 kV dielectric requirements. However, ring main units (RMUs) require low cost, and excessively high costs are unacceptable to users. Through optimized design and moderate widening of the RMU cabinet, it is possible to achieve low-cost and compact 24 kV environmentally friendly gas-insulated RMUs.

Grounding Switch Arrangement in Eco-Friendly Gas RMUs

There are two methods in RMUs to achieve grounding function in the main circuit:

  • Outgoing line-side earthing switch (lower earthing switch)

  • Busbar-side earthing switch (upper earthing switch)

The busbar-side earthing switch can be selected as Class E0, which requires coordination with the main switch during operation. According to the Standardized Design Scheme for 12 kV Ring Main Units (Boxes) issued by State Grid in 2022, regarding three-position switches, the scheme specifies that three-position switches should adopt a busbar-side arrangement and redefines them as "busbar-side combined functional earthing switches."

Power safety regulations stipulate that no circuit breaker or fuse shall be connected between grounding wires, earthing switches, and equipment under maintenance. If, due to equipment constraints, a circuit breaker exists between the earthing switch and the equipment under maintenance, measures must be taken to ensure that the circuit breaker cannot open after both the earthing switch and the circuit breaker have been closed.

Therefore, the line-side earthing switch is located downstream of the circuit breaker. It connects directly to the outgoing cable being grounded, satisfying the requirement that no circuit breaker or fuse exists between the grounding point, the earthing switch, and the equipment under maintenance. In contrast, the busbar-side earthing switch is located upstream of the circuit breaker. There is a vacuum circuit breaker between the earthing switch and the outgoing cable being grounded—it does not connect directly. Since a circuit breaker lies between the earthing switch and the equipment under maintenance, measures must be implemented to prevent the circuit breaker from opening once both the earthing switch and the circuit breaker are closed. For example, the trip circuit of the circuit breaker may be disconnected via a link plate, or mechanical means may be used to prevent accidental tripping, thereby avoiding unintended disconnection of the grounding path.

The State Grid Standardized Design Scheme also specifies interlocking requirements for the busbar-side combined functional earthing switch. When the combined functional earthing switch on the busbar side uses closure of the circuit breaker to achieve grounding of the cable side, it must include both mechanical and electrical interlocks to prevent manual or electric opening of the circuit breaker.

RMU.jpg

State Grid adopts the busbar-side three-position isolation/grounding switch primarily considering the short-circuit making (closing) capability. In SF6-insulated RMUs, the earthing switch benefits from SF6’s dielectric strength being about three times that of air and its arc-quenching capability approximately 100 times greater than air due to superior arc cooling. Thus, the closing capacity of the earthing switch is reliably ensured.

In contrast, eco-friendly gases lack arc-quenching capability and have lower insulation performance. Therefore, very high closing speed is required. However, RMU operating mechanisms have limited energy and cannot provide sufficient force for high-speed closing. Using a line-side earthing switch would require increased closing speed and improved arc resistance and electrodynamic analysis of the contacts, potentially leading to larger operating forces and higher costs. The busbar-side earthing switch, by solving the circuit breaker interlock issue, can still ensure reliable grounding while offering stronger making capacity.

Through technical and product analysis of SF6 versus eco-friendly gases, it can be seen that 12 kV eco-friendly gas-insulated RMUs can meet insulation and temperature rise requirements with only minor increases in size, indicating mature technical solutions.

However, there are few 24 kV eco-friendly gas-insulated products available. The key challenge lies in the higher voltage rating, which leads to significantly increased dimensions. Excessive size and high price will restrict the development of 24 kV eco-friendly gas-insulated RMUs. A balanced approach considering insulating gas type, filling pressure, enclosure volume, and auxiliary insulation cost is needed to design low-cost, compact RMUs. Only then can true SF6 replacement be achieved—enabling not only domestic market dominance but also global export, promoting China's low-carbon, environmentally friendly electrical equipment worldwide.

Bexşişek bidin û nuşkarê wê bikevin!​

Pêşniyariyek

Xalakên û Pêşkêşkirina Yekfîlan Dihênan da Tirazên 10kV
Taybetmendiyên şiklê xwezayî û amûrên vedibijêrin şiklê xwezayî ya yek-fazê ya li ser zemîn1. Taybetmendiyên şiklê xwezayî ya yek-fazê ya li ser zemînÎşaretên alarmê yên navendî:Zilê alarmê dide, û çirka ku bi "Şiklê xwezayî ya li ser zemîn li ser kablî ya [X] kV ya beşa [Y] ya bus" tê nîşankirin dike. Li sistemên ku li ser zemîn bi kûlîka Petersen (kûlîka rûniştkirinê ya arkê) hatiye çêkirin, çirka "Kûlîka Petersen kar dike" jî dike.Nîşanên voltmetreya kontrolkirina îzolasyonê:Voltajê ya fazê y
01/30/2026
Moda operasyonî da vengkirina dîmenê ji bo transformatorên şebê elektrik 110kV~220kV
Cihêna girîngkirina wêje nötr da ji bo dawereyên elektrik 110kV~220kV divê bixebitandina nişanên dijla wekheviya cihêna nötr yên transformatoran biguheze û hewce bike ku impedaansa sifiriyê ya stasyonên transformasyonê tevahî neqdar bike. Heta duayin dikare ku impedaansa sifiriyê yekbûyî ya her çendkêjiyê yên sisteman jêr be trehê ji impedaansa birinî yekbûyî neqde.Ji bo transformatoran 220kV û 110kV yên nûvekirin û rengkirin teknolojî, cihêna girîngkirina wêje nötr yan divê bexweste bibine:1. T
01/29/2026
Bisînhê Li Kîjan Diyan Bistîn û Dîwarên Berzok û Pirîvan Bistinandin?
چرا دەستگاھەکان دەستی کەمێک بە سەنجەر، شوێن، پیپڵ و چووندەکەن؟لە دەستگاھەکاندا، ئامێرەکەی جۆری ترانسفۆرمەری ناوڕاستی و ترانسفۆرمەری پاشتەر، خەوتە لێدەری، ترانسفۆرمەری هەژارە، ترانسفۆرمەری چاودێری، و چاودێرەکان هەمووی پێویستە بە گردن. لەوە ماوە، ئێستا دەبینین بەهۆی چی شوێن و چووندەکەرەکان زۆربەی کات پێشەوتن لە دەستگاھەکاندا بەکاردێت. گەرچە ئەوان پێشەوتن لە باشترین ڕوویان دەردەکەون، بەڵام ئەوان رولێکی گرنگی ئامانجی و کارکردنی دەبەستن.لە ڕێگەکەی گردنی دەستگاھ - بەخاصة کاتێک چەند ڕێگەی گردنیش هەبێت
01/29/2026
HECI GCB ji Jeneratoran – Dabejkirina Tez SF₆
1.Pêşnûmara û Pêkhatina1.1 Roliya Cikirîna Cihazekê ya JeneratoraCikirîna Cihazekê ya Jeneratora (GCB) yek demka kontrolbirindar ye ku di navbera jeneratora û transeformera dabeşkirinê de were çavkirin, wek arayê ji navbera jeneratora û şebeka elektrîkê. Fonksiyonên sereke yên wate hene: izolasyona sergûcheyên li gorî jeneratora û destpêkirina kawetirina operasyonan bi hevdayî ya jeneratora û peyda kirina şebeka. Prinsîpa karbikê ya GCB ne bide berbiyayi taybetandî ji cikirîna standard, lê, vege
01/06/2026
Pêşnîyar bişînin​
+86
کرتە بکە بۆ بارکردنی فایل
Daxistin
IEE-Business Zêdekirin Bîzînin Wekandin
Bi karanîna sepanê IEE-Business, li her der û her dem amûr bibînin, çareseriyan bistînin, bi pîsporan re têkiliyê ava bikin, û beşdarî hevkariya pîşesaziyê bibin — ev hemû ji pêşveçûna projeyên hêz û karsaziya we re piştgirîyeke tev e.​