Energy Meter with Lag Adjustment Devices

Electrical4u
Electrical4u
Field: Basic Electrical
0
China

What Is Energy Meter With Lag Adjustment Devices

We know that in induction type energy meters, in order to maintain speed of rotation proportional to power “The phase angle between supply voltage and pressure coil flux should be equal to 90o“. However in actual practice, the angle between supply voltage and pressure coil flux is exactly not 90o but few degrees less. Therefore, some lag adjustment devices are used for adjustment of lag angle. Let us consider the figure given beside:

energy meter

In the beside figure we have introduced another coil which is located on the central limb with number of turns equal to N. This coil is called lag coil. When we give supply voltage to the pressure coil it produces flux F. Now this flux is divided into two parts Fp and Fg, Fp flux cuts the moving disc and also links with the lag coil. Due to lag coil there induces an emf El which lags behind the flux Fp by angle of 90o, also Il is lagging behind El by an angle of 90o. The lagging coil produces a flux Fl. The resultant flux so obtained that cuts the moving disc is the combination of Fl and Fp. Now the resultant value of this flux is in phase with resultant mmf of lag or shading coil and the resultant value of mmf of shading coil can adjusted by using two methods

  1. By adjusting electrical resistance.

  2. By adjusting shading bands.

Let us discuss these points in more detail:
(1) Adjustment of coil resistance:
lag coil

If electrical resistance in the coil is high the current will be low and hence mmf of the coil decreases therefore the lag angle also decreases. So we have to decrease the resistance,and the resistance can be decreased by using thick wire in coils. So by adjusting electrical resistance we can indirectly adjust lag angle.
(2) By adjusting the shading bands up and down on the central limb we can adjust lag angle because when we move shading bands upward, then they embrace more flux hence the induced emf increases therefore mmf increases with increase in the value of lag angle. When we move shading bands downwards then it will embrace less flux hence the induced emf will decrease therefore mmf decreases with decrease in the value of lag angle. So by adjusting the position of shading bands we can adjust the lag angle.

Friction Compensation

friction compensation
In order to compensate friction forces we have to apply small force in the direction of rotation of disc. This applied force should be independent of load, so that the meter can read correctly at light load also. But over compensation of friction leads to creeping. Creeping may be defined as the continuous rotation of disc only by energizing the pressure coil while there is no current flowing through the current coil. In order to avoid creeping two holes are drilled, which are diametrically opposite to each other on the disc. Due to this, the effective circular eddy current path of the disc is distorted as shown in the figure. Also the center of effective eddy current paths is shifted to C1 from C. Now C1 becomes the equivalent magnetic pole as produced by these eddy currents so the net force on the rotating disc, will tend to move C1 further away from the pole axis C. Thus disc will creep until the drilled hole reaches near the edge of pole, however further rotation of disc is opposed by opposite torque which is produced by above mechanism.

Overload Compensation

Under load conditions the disc continuously moves. Therefore there induced an emf which is due to rotation called dynamically induced emf. Due to this emf the eddy currents are produced which interacts with the series magnetic field to produce breaking torque. Now this breaking torque is directly proportional to square of current hence it continuously increases and opposes the rotation of disc. In order to avoid the production of this self breaking torque, the full load speed of disc is kept as low as possible so that self breaking torque can be reduced. Errors in single phase energy meters: The errors caused by both the system (i.e. driving and braking) are separating written as follows:

Error caused by Driving System

  1. Error Due to Non SymmetricalMagnetic Circuit
    If the 
    magnetic circuit is not symmetrical there produce a driving torque, due to which meter creep.

  2. Error Due to Wrong Phase Angle
    If there is not a proper phase difference between the various phasors then it results in improper rotation of disc. Improper phase angle is due to improper lag adjustment, variation of resistance with temperature or it may be due to abnormal frequency of supply voltage.

  3. Error Due to Wrong Magnitude of Fluxes
    There are several reasons for wrong magnitude of fluxes out of these main reasons are abnormal values of current and voltage.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!
Recommended
PT Fuse Slow Blow: Causes, Detection & Prevention
PT Fuse Slow Blow: Causes, Detection & Prevention
I. Fuse Structure and Root Cause AnalysisSlow Fuse Blowing:From the design principle of fuses, when a large fault current passes through the fuse element, due to the metal effect (certain refractory metals become fusible under specific alloy conditions), the fuse first melts at the soldered tin ball. The arc then rapidly vaporizes the entire fuse element. The resulting arc is quickly extinguished by quartz sand.However, due to harsh operating environments, the fuse element may age under the comb
Edwiin
10/24/2025
Why Fuses Blow: Overload, Short Circuit & Surge Causes
Why Fuses Blow: Overload, Short Circuit & Surge Causes
Common Causes of Fuse BlowingCommon reasons for fuse blowing include voltage fluctuations, short circuits, lightning strikes during storms, and current overloads. These conditions can easily cause the fuse element to melt.A fuse is an electrical device that interrupts the circuit by melting its fusible element due to heat generated when current exceeds a specified value. It operates on the principle that, after an overcurrent persists for a certain period, the heat produced by the current melts
Echo
10/24/2025
Fuse Maintenance & Replacement: Safety and Best Practices
Fuse Maintenance & Replacement: Safety and Best Practices
1. Fuse MaintenanceFuses in service should be regularly inspected. The inspection includes the following items: Load current should be compatible with the rated current of the fuse element. For fuses equipped with a fuse blown indicator, check whether the indicator has actuated. Check the conductors, connection points, and the fuse itself for overheating; ensure connections are tight and making good contact. Inspect the fuse exterior for cracks, contamination, or signs of arcing/discharge. Liste
James
10/24/2025
Maintenance and Repair Items for 10kV High-Voltage Switchgear
Maintenance and Repair Items for 10kV High-Voltage Switchgear
I. Routine Maintenance and Inspection(1) Visual Inspection of Switchgear Enclosure No deformation or physical damage to the enclosure. Protective paint coating shows no severe rust, peeling, or flaking. Cabinet is securely installed, clean on the surface, and free of foreign objects. Nameplates and identification labels are neatly affixed and not falling off.(2) Check of Switchgear Operating Parameters Instruments and meters indicate normal values (comparable to typical operating data, with no s
Edwiin
10/24/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.