Electrodynamometer Type Wattmeter

Encyclopedia
Encyclopedia
Field: Encyclopedia
0
China

Electrodynamometer Wattmeter Definition


An electrodynamometer type wattmeter measures electrical power by using the interaction between magnetic fields and electric currents.


Working Principle


Now let us look at constructional details of electrodynamometer. It consists of following parts.There are two types of coils present in the electrodynamometer. They are :


Moving Coil


The moving coil moves the pointer with the help of a spring control instrument. To prevent overheating, a limited current flows through the moving coil by connecting a high-value resistor in series. The air-cored moving coil is mounted on a pivoted spindle and can move freely. In an electrodynamometer type wattmeter, the moving coil acts as a pressure coil and is connected across the voltage, so the current through it is proportional to the voltage.


Fixed Coil


The fixed coil is divided into two equal parts and these are connected in series with the load, therefore the load current will flow through these coils. Now the reason is very obvious of using two fixed coils instead of one, so that it can be constructed to carry considerable amount of electric current. 


These coils are called the current coils of electrodynamometer type wattmeter. Earlier these fixed coils are designed to carry the current of about 100 amperes but now the modern wattmeter are designed to carry current of about 20 amperes in order to save power.


Control System


Out of two controlling systems i.e.


Gravity control


Spring control, only spring controlled systems are used in these types of wattmeter. Gravity controlled system cannot be employed because there will be appreciable amount of errors.


Damping System


Air friction damping is used because eddy current damping can distort the weak operating magnetic field, leading to errors.


There is uniform scale which is used in these types of instrument as moving coil moves linearly over a range of 40 degrees to 50 degrees on either side.


Now let us derive the expressions for the controlling torque and deflecting torques. In order to derive these expressions let us consider the circuit diagram given below:

 

9131cdae17853d6dfe3cfb3f249a7055.jpeg

 

We know that instantaneous torque in electrodynamic type instruments is directly proportional to the product of instantaneous values of currents flowing through both the coils and the rate of change of flux linked with the circuit.


Let I1 and I2 be the instantaneous values of currents in pressure and current coils respectively. So the expression for the torque can be written as:

 

65c01cfae06ca9a3843d154d4264ea11.jpeg

 

Where, x is the angle.


Now let the applied value of voltage across the pressure coil be

 

0749259f9178f078cbf0b88040d2f883.jpeg

 

Since the electrical resistance of the pressure coil is very high, we can neglect its reactance compared to its resistance. Thus, the impedance is equal to its electrical resistance, making it purely resistive.

The expression for instantaneous current can be written as I2 = v / Rp where Rp is the resistance of pressure coil.

 

6b25e9e95a562a7fff38ec3db617b544.jpeg

 

If there is phase difference between voltage and electric current, then expression for instantaneous current through current coil can be written as


2b23bb0b6bdb3bf7880bf08b00613dac.jpeg


As current through the pressure coil is very very small compared to the current through current coil hence current through the current coil can be considered as equal to total load current.Hence the instantaneous value of torque can be written as


851dc04955ce3a477f5f1ce1347a52d1.jpeg

Average value of deflecting torque can be obtained by integrating the instantaneous torque from limit 0 to T, where T is the time period of the cycle.


f51c520ea3dcf220e5eb60f3ac67d989.jpeg


Controlling torque is given by Tc = Kx where K is spring constant and x is final steady state value of deflection.


Advantages


  • Scale is uniform upto a certain limit.

  • They can be used for both to measure ac as well dc quantities as scale is calibrated for both.


Errors


  • Errors in the pressure coil inductance.



  • Errors may be due to pressure coil capacitance.



  • Errors may be due to mutual inductance effects.



  • Errors may be due connections.(i.e. pressure coil is connected after current coil)



  • Error due to Eddy currents.



  • Errors caused by vibration of moving system.



  • Temperature error.


  • Errors due to stray magnetic field.

Give a tip and encourage the author!
Recommended
What Are Combined Transformer Standards? Key Specs & Tests
What Are Combined Transformer Standards? Key Specs & Tests
Combined Instrument Transformers: Technical Requirements and Testing Standards Explained with DataA combined instrument transformer integrates a voltage transformer (VT) and a current transformer (CT) into a single unit. Its design and performance are governed by comprehensive standards covering technical specifications, testing procedures, and operational reliability.1. Technical RequirementsRated Voltage:The primary rated voltages include 3kV, 6kV, 10kV, and 35kV, among others. The secondary v
Edwiin
10/23/2025
MVDC: Future of Efficient, Sustainable Power Grids
MVDC: Future of Efficient, Sustainable Power Grids
The Global Energy Landscape Is Undergoing a Fundamental Transformation toward a "fully electrified society," characterized by widespread carbon-neutral energy and the electrification of industry, transportation, and residential loads.In today’s context of high copper prices, critical mineral conflicts, and congested AC power grids, Medium-Voltage Direct Current (MVDC) systems can overcome many limitations of traditional AC networks. MVDC significantly enhances transmission capacity and efficienc
Edwiin
10/21/2025
Grounding Causes of Cable Lines and the Principles of Incident Handling
Grounding Causes of Cable Lines and the Principles of Incident Handling
Our 220 kV substation is located far from the urban center in a remote area, surrounded primarily by industrial zones such as Lanshan, Hebin, and Tasha Industrial Parks. Major high-load consumers in these zones—including silicon carbide, ferroalloy, and calcium carbide plants—account for approximately 83.87% of our bureau’s total load. The substation operates at voltage levels of 220 kV, 110 kV, and 35 kV.The 35 kV low-voltage side mainly supplies feeders to ferroalloy and silicon carbide plants
Felix Spark
10/21/2025
Overhead Power Lines & Towers: Types, Design & Safety
Overhead Power Lines & Towers: Types, Design & Safety
Besides ultra-high voltage AC substations, what we encounter more frequently are power transmission and distribution lines. Tall towers carry conductors that leap across mountains and seas, stretching into the distance before reaching cities and villages. This is also an interesting topic—today, let's explore transmission lines and their supporting towers.Power Transmission and DistributionFirst, let’s understand how electricity is delivered. The electric power industry primarily consists of fou
Encyclopedia
10/21/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.