Unsa ang mga paagi sa pag-awhag sa kaso sa current transformers?

Felix Spark
Larangan: Pagkabag-o ug Pagpangutana
China

Isipag-utana sa mga kahibalo sa pagpangita sa kasala, ang among gibuhat kada adlaw mao ang pagtumong sa mga current transformers (CTs). Ang secondary winding sa CT nga nagoperasyon dili pwede mag-open circuit! Kon mag-open circuit na, ang secondary current ug demagnetizing potential mosunod. Ang tanang primary-side magnetic potential mosunod isip exciting potential sa iron core, naka-increase ang iyang magnetic flux density. Ang taas nga voltage sa secondary side magdudulot og panganak sa kalambigitan anytime.

Bisan kon may strict nga mga regulasyon sa power operation, ang mga electrician sa user adunay dili maayo nga management ug teknikal nga kalidad. Bisag molihok na ang power operation market, ang mga design units adunay dili maayo nga pagdesign, ug ang installation teams dili mogamit sa mga drawing o safety measures. Busa, ang CT accidents sa panahon sa operasyon walay limitado nga mobusog. Ang usa ka typical capacity-increase project accident nga gi-handle ko niadto ililisay kini, ug ipabahin nako.

1. Pagdiskubre sa Kasala: Ang Lugar sa Naka-burn nga Transformer

Sa Setyembre 27, 2012, ang among engineering installation company nagsugyot og substation capacity-increase project. Sa panahon namo og pagcut-off sa power aron mopalit sa CT sa incoming line cabinet, giguol ko kini ug nakita nako nga ang CT giburn beyond recognition! Nagmaintain na ko sa daghan nga tuig, nakita nako daghan na nga burned-out, apan ang CT nga nagburn out suddanan dili normal, kini kinahanglan dugayan sa mas sayon nga pagdiskubre sa rason.

2. Pagsusi sa Rason: Man-made Open Circuit + Management Chaos
(1) On-site Investigation, Locking on "Secondary Wires Cut"

Ang akong team ug ko mi nagconduct og thorough investigation: Ang secondary outgoing wires sa CT sa incoming line cabinet gisunod gyud! Tracing back, ang matang sa butang mao ang commissioning sa substation:

  • Sa una, ang transformation ratios sa incoming line cabinet ug metering cabinet parehas 75/5;

  • Sa unang capacity increase, ang CT sa metering cabinet gipalit ngadto sa 150/5, pero ang CT para sa protection sa incoming line cabinet wala gipalit ug gisunod pa gyud 75/5;

  • Pagkatapos sa capacity increase, ang equipment wala naka-show og abnormality, apan sa pagtaas sa transformer capacity, ang protection setting value wala giusab.

(2) Misjudging the Fault, Man-made Open Circuit

Sa higayon, sa pagtaas sa electricity consumption, ang over-current protection mobati gyud. Ang user electrician wala makita ang problema ug mis-isip nga CT fault ang nag-cause sa relay nga mobati, ug giputli ang secondary wires! Pagkatapos sa power transmission, ang protection wala mobati, apan ang secondary circuit sa CT direkta open-circuited - disaster!

(3) Hazards of Open Circuit: Iron Core Saturation → Burning

Ang secondary side sa CT orihinal nga gamay ra ang impedance ug operasyon close to short-circuit. Kon mag-open circuit, ang magnetic force gikan sa primary current dili mahatagan og offset sa secondary side, ang iron core severe saturation, ang iron loss mobati, ug ang CT mismo overheats ug burn out.

Sa final analysis, ang insidente mao ang major management loophole: Ang construction team wala gipalit sa CT sa incoming line cabinet, ang protection setting value wala giusab, ug ang electrician blind operation, leading to the CT being damaged layer by layer.

3. Preventive Measures: A "Life-saving Checklist" for Maintenance Workers

Sa aming trabaho, kita kinahanglan plug ang loopholes gikan sa source. Combining this accident, I have sorted out 6 strict measures, and operation and maintenance, design, and installation must all follow the rules:

(1) Design + Drawing Review: Strictly Comply with Specifications

Design units must conduct on-site surveys and produce drawings in accordance with specifications; the owner must supervise the drawing review to prevent "wrong designs" from entering the site.

(2) Equipment Control: Full-process Supervision

The owner must follow national and industry standards for procurement, testing, and acceptance to prevent defective products from entering the power grid.

(3) Operation Qualifications: Electricians Must Be Certified

If operation and maintenance personnel have no qualifications? Don't let them touch the equipment! Moreover, random modification of wiring and disassembly of equipment are strictly prohibited — this is a red line.

(4) Installation and Acceptance: Keep an Eye on the Construction Team

The installation team must follow the procedures, and any wrong installation, corner-cutting, or under-installation must be reworked immediately! The acceptance must be strict to avoid hidden dangers.

(5) Regular Inspections: Strengthen in Special Periods

Daily inspections and panel monitoring are essential, and special periods such as high load, high temperature, and typhoon days must be closely monitored! Check the appearance, smell for peculiar odors, and listen for abnormal noises to detect abnormalities early.

(6) Overhaul and Testing: Don't Let "Sick CTs" Be Put into Use

Overhauls must be carried out in strict accordance with standards, and the process must be in place; electrical tests must be thorough, and CTs with defects must never be put into use.

4. Conclusion: CT Open Circuit is Extremely Dangerous, Maintenance Workers Must Know "Prevention and Rescue"

A secondary open-circuit of a CT is no small matter; it can cause equipment outages, protection maloperations/refusals to operate, and lead to major accidents at any time. As front-line maintenance workers, we must thoroughly understand the hazards and causes of open circuits, conduct more inspections and investigations in daily work, and be able to solve problems immediately when abnormalities occur. Only by implementing these measures can CTs operate stably and the power grid have fewer troubles!

Maghatag og tip ug pagsalig sa author

Gipareserbado

Unsa ang Kalainan Tungod sa mga Rectifier Transformers ug Power Transformers
Ano ang Rectifier Transformer?"Power conversion" usa ka pangngalan nga naglakip sa rectification, inversion, ug frequency conversion, diin ang rectification ang labing gamit. Ang mga kagamitan sa rectification mogamit og input na AC power isip DC output pinaagi sa rectification ug filtering. Ang rectifier transformer magsilbi isip power supply transformer alang sa mga kagamitan sa rectification. Sa industriya, ang daghang DC power supplies nakakuha gikan sa pagkombinasyon sa rectifier transforme
01/29/2026
Isyuha sa Pagpili og Grounding Transformers sa Boost Stations
Isyuha sa Pagpili og Grounding Transformers sa Boost StationsAng grounding transformer, kasagaran gisulti nga "grounding transformer," nagoperar sa kondisyon nga walay carga sa normal nga operasyon sa grid ug sobrahan sa short-circuit faults. Batas sa pagkakaiba sa filling medium, ang mga karaniwan nga klase mao ang oil-immersed ug dry-type; batas sa numero sa phase, sila mahimong ma classify isip three-phase ug single-phase grounding transformers. Ang grounding transformer naghimo og artificial
01/27/2026
Solusyon sa Pagkontrol sa Ingong sa Transformer para sa Mga Dili Parehas nga Pagsulay
1.Pag- kontrol sa Bulakbo para sa mga Ground-Level Independent Transformer RoomsStratehiya sa Pag- kontrol:Una, gihahayag ang pag-inspekta ug pag-maintain sa transformer nga walay kuryente, kasama ang pag-bagong insulating oil nga lumad, pag-suri ug pag-pigsa sa tanang fasteners, ug pag-limpyo sa dust mula sa unit.Pangalawa, palig-onon ang foundation sa transformer o i-install ang mga vibration isolation devices—tulad ng rubber pads o spring isolators—na pinili batas sa grabe sa vibration.Finalm
12/25/2025
Pag-identipikar sa mga Panganib ug mga Pamaagi sa Pagkontrol Alang sa Pagbag-o sa Distribusyon Transformer
1. Pagpanalipod ug Pagkontrol sa Panganak sa KuryenteBatasan sa tipikal nga disenyo alang sa pag-upgrade sa network sa distribusyon, ang distansya gikan sa drop-out fuse sa transformer hangtod sa taas nga terminal sa kuryente mao ang 1.5 metro. Kon gamiton ang crane aron matukar, dili mahimong panalipdan ang kinahanglan nga minimum nga clearance sa 2 metro tali sa crane boom, lifting gear, slings, wire ropes, ug ang 10 kV live parts, nagdudulot og seriyosong panganak sa kuryente.Mga Pamaagi sa P
12/25/2025
Inquiry
+86
I-klik aron i-upload ang file
Pangutana
Pangutana sa IEE-Business Application
Pangita og mga equipment gamit ang IEE-Business app asa asa ug kailan man sugad og pagkuha og solusyon pagsulay sa mga eksperto ug pagpadayon sa industriya nga pakisayran suportahan ang imong proyekto sa kuryente ug negosyo