38kV 38.5kV 40.5kV 44kV Three-phase outdoor vacuum distribution recloser/Reclosure direct Supply

  • 38kV 38.5kV 40.5kV 44kV Three-phase outdoor vacuum distribution recloser/Reclosure direct Supply

Key attributes

Brand ROCKWILL
Model NO. 38kV 38.5kV 40.5kV 44kV Three-phase outdoor vacuum distribution recloser/Reclosure direct Supply
Rated voltage 38kV
Rated normal current 1250A
Rated short circuit breaking current 25kA
Power frequency withstand voltage 85kV/min
Rated lightning impulse voltage 185kV
manual closing No
Series RCW

Product descriptions from the supplier

Description

Description:

As a pioneering OEM in China’s recloser sector, we leverage decades of R&D strength to set the original industry standards, build a fully autonomous full-chain production system, and provide reliable solutions for power grid projects.

The RCW   series automatic circuit reclosers can use on overhead distribution lines as well as distribution substation applications for all voltage classes 11kV up to 38kV at 50/60Hz power system.  and it’s rated current can reach 1250A.The RCW   series automatic circuit reclosers integrates the functions of control, protection, measurement, communication, fault detection, on-linemonitoring of closing or opening.The RCW   series vacuum recloser is mainly combined with integration terminal, current transformer, permanent magnetic actuator and it’s recloser controller.

Features:

  • Optional grades available in rated current range.

  • With optional relay protection and logic for user selection.

  • With optional communication protocols and I/O ports for users to choose.

  • PC software for controller testing, setup, programming, updates.

  • Solving the dual challenges of tropical heat and humidity

  • Resistant to salt fog corrosion, suitable for offshore / coastal power applications

  • Fully sealed design, preventing sand and dust from affecting

  • Operable in wide temperature range: -30°C to +40°C, handling extreme temperature variations

Parameters:

The voltage classes of some of these Automatic Reclosers include 6kV, 6.3kV, 6.6kV, 6.9kV, 7.2kV, 10kV, 10.5kV, 11kV, 11.5kV, 12kV, 13.2kV, 13.8kV, 14.5kV, 14.4kV, 15kV, 15.5kV, 15.6kV, 17.5kV, 20kV, 21.9kV, 22kV, 24kV, 30kV, 33kV, 33.5kV, 34.5kV, 35kV, 36kV, 38kV, 38.5kV, 40.5kV, 44kV, 45kV, 46kV, 66kV and 69kV. Rated Short-Circuit Breaking Current includes 8kA, 12.5kA, 16kA, 20kA, 25kA, 31.5kA and customization is available.

Rated maximum voltage

38kV

Rated maximum current

1250A

Rated frequency

50Hz

Rated short circuit breaking current

12.5kA

Rated peak value withstand current

31.5kA

Rated 1min power frequency withstand voltage (Three-phase Epoxy resin pole)

85kV

Rated lightning impulse voltage (Three-phase Epoxy resin pole)

185kV

Operation sequence

C-0.3-CO-180-CO (Spring mechanism)

Mechanical life

n:10000 (Spring mechanism)

Power supply and operating voltage     

110/220V (Customized)

Ratio of current transformer

400/1A (Customized)

Number of voltage sensors (Three-phase Epoxy resin pole)

≤6

Opening time

≤50ms (Spring mechanism)

Closing time

≤60ms (Spring mechanism)

Minimum creepage distance

31, level 4 (mm/kV)

Minimum distance between phases

360mm

Potential transformer

110/220V (Customized)

Cable length

6,8,12m (Customized)

Cable clamp (Three-phase Epoxy resin pole)

4-hole NEMA

Lightning arrester

≤6

Mounting type

Single / double column


With optional relay protection & logics for user choice

Instantaneous over-current protection

Timing over-current protection

Negative sequence over-current protection

Directional over-current protection(⁽¹⁾)

Over-voltage protection / Under voltage protection

Programmable protection relay curves (total 10 nos ANSI/IEC curves)

Cold load pickup protection TCC + Hot line tag

Earth protection E/F SEF + Zone- Sequence Co-ordination

More relay functions can be customized

With optional communication protocols & I/O port for user choice

RS-232 and RS-485 ports supporting

DNP3.0 communication protocol support

Modbus communication protocol is optional

IEC 60870-501 communication protocol support

IEC 60870-5-104 communication protocol support

The recloser can communicate through GPRS(or) GSM(or) GPRS/GSM module with English or Specified language

With optional functions for use

Rated currents, System phase current,

Rated voltages, System phase voltage and secondary low voltage power supply voltage Frequency

power (kWh), reactive power (kVarh), power factor

With optional reclosing interval for user pre-program

reclosing times setting support

Dead time setting support

With events recording function

SOE 10000 operations record

Fault record and normal operation record

Note:mean should customized by manufacturer if needed

Environmental requirement:

Maximum temperature:

+40°C

Minimum temperature:

-30°C

Monthly average humidity

95%

Humidity:

90%

Above sea level:

2500m or higher

Ambient air Not apparently polluted by corrosive and flammable gas, vapor


Product show:

image.png

What are the mechanical failures of outdoor vacuum reclosers?

Operating Mechanism Faults:

Spring-Operated Mechanism:

  • Spring Fatigue: Spring fatigue is a common issue. If the spring remains compressed for a long time or is frequently operated, it may lose its elasticity, causing the closing speed to slow down or the closing position to be inaccurate. Additionally, mechanical transmission components of the spring-operated mechanism, such as connecting rods and toggle arms, can wear out, deform, or become stuck, affecting the accuracy and reliability of the opening and closing operations.

Permanent Magnet-Operated Mechanism:

  • Magnet Demagnetization: Demagnetization of the permanent magnet is a potential fault in permanent magnet-operated mechanisms. High-temperature environments, strong vibrations, or prolonged exposure to high currents can weaken the magnetic properties of the permanent magnet, affecting the performance of the operating mechanism. Furthermore, faults in the control circuit of the permanent magnet-operated mechanism, such as capacitor aging or electronic component failure, can also lead to abnormal opening and closing operations.

Transmission Component Faults:

  • Loose or Detached Connecting Rods: In outdoor vacuum reclosers, the transmission connecting rods may loosen or even detach over time due to vibration, corrosion, or other factors. This can prevent the opening and closing actions from being transmitted properly, causing the recloser to fail to operate correctly.

  • Wear or Breakage of Pivot Pins: Pivot pins can wear out during rotation. Severe wear can increase the clearance between transmission components, affecting the precision of the opening and closing actions. If a pivot pin breaks, it can directly interrupt the transmission chain of the recloser, preventing it from performing opening and closing operations.


Documentation Resource Library
Restricted
38kV automatic recloser technology specification
Technical Data Sheet
English
Consulting
Consulting
Restricted
15kV/27kV/38kV outdoor auto break vacuum recloser brochure
Brochure
English
Consulting
Consulting
Restricted
10 to 38kV auto vacuum break recloser Catalog
Catalogue
English
Consulting
Consulting
Public.
DEKRA Recloser Test Report
Test Report
English
Know your supplier
Online store
On-time delivery rate
Response time
100.0%
≤4h
Company overview
Workplace: 108000m²m² Total staff: 700+ Highest Annual Export(usD): 150000000
Workplace: 108000m²m²
Total staff: 700+
Highest Annual Export(usD): 150000000
Services
Business Type: Design/Manufacture/Sales
Main Categories: High Voltage Electrical Apparatus/Electric transformer
Whole life care manager
Whole-life care management services for equipment procurement, use, maintenance, and after-sales, ensuring safe operation of electrical equipment, continuous control, and worry-free electricity consumption.
The equipment supplier has passed platform qualification certification and technical evaluation, ensuring compliance, professionalism, and reliability from the source.

Related Products

Related Knowledges

  • Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
    Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
    01/30/2026
  • Neutral point grounding operation mode for 110kV~220kV power grid transformers
    The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
    01/29/2026
  • Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
    Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
    01/29/2026
  • Why Must a Transformer Core Be Grounded at Only One Point? Isn't Multi-Point Grounding More Reliable?
    Why Does the Transformer Core Need to Be Grounded?During operation, the transformer core, along with the metal structures, parts, and components that fix the core and windings, are all situated in a strong electric field. Under the influence of this electric field, they acquire a relatively high potential with respect to ground. If the core is not grounded, a potential difference will exist between the core and the grounded clamping structures and tank, which may lead to intermittent discharge.I
    01/29/2026
  • Understanding Transformer Neutral Grounding
    I. What is a Neutral Point?In transformers and generators, the neutral point is a specific point in the winding where the absolute voltage between this point and each external terminal is equal. In the diagram below, pointOrepresents the neutral point.II. Why Does the Neutral Point Need Grounding?The electrical connection method between the neutral point and earth in a three-phase AC power system is called theneutral grounding method. This grounding method directly affects:The safety, reliabilit
    01/29/2026
  • What’s the Difference Between Rectifier Transformers and Power Transformers?
    What is a Rectifier Transformer?"Power conversion" is a general term encompassing rectification, inversion, and frequency conversion, with rectification being the most widely used among them. Rectifier equipment converts input AC power into DC output through rectification and filtering. A rectifier transformer serves as the power supply transformer for such rectifier equipment. In industrial applications, most DC power supplies are obtained by combining a rectifier transformer with rectifier equ
    01/29/2026

Related Solutions

  • Intelligent Operation Solution for 12kV Vacuum Circuit Breakers: Integrating Real-time Monitoring & Lifetime Optimization
    Ⅰ. Equipment Operation & MaintenanceIntelligent Monitoring System Integration​Multi-parameter Real-time Monitoring: Embedded sensors (temperature, displacement, Hall effect current sensors) track contact temperature rise, mechanical characteristics (opening/closing speed, overtravel), coil current, and partial discharge signals. Data undergoes preprocessing via edge computing prior to cloud upload.​Lifetime Prediction Model: Dynamically evaluates remaining lifespan using electrical wear data
    06/10/2025
  • SF6 Circuit Breaker Solutions for Outdoor Installation (Anti-Pollution & Seismic Resistance)
    I.Core Challenges in Outdoor Installation​In high-voltage transmission and distribution systems, SF6 circuit breakers are exposed to complex outdoor environments for extended periods, facing the following critical issues:​Pollution & Insulation Degradation​Dust, salt fog, and industrial pollutants in outdoor environments easily adhere to equipment surfaces. In coastal or industrial areas, pollution levels may reach ​Class IV, resulting in insufficient creepage distance and triggering ​flasho
    05/12/2025
  • 12kV Indoor Vacuum Circuit Breaker Southeast Asia Solution: Anti-Corrosion Compact Design
    12kV Indoor Vacuum Circuit Breaker Southeast Asia Solution: Anti-Corrosion Compact DesignⅠ. Executive Summary​Southeast Asia faces rapidly growing electricity demand alongside environmental challenges including high temperatures, humidity, salt spray corrosion, and grid instability. This solution recommends ​Solid Insulated Pole-Mounted Vacuum Circuit Breakers (VCB)​​ featuring ​high reliability, ​compact design, and ​smart monitoring. Tailored for tropical climates and industrial scenarios, it
    06/10/2025
Haven't found the right supplier yet? Let matching verified suppliers find you. Get Quotation Now
Haven't found the right supplier yet? Let matching verified suppliers find you.
Get Quotation Now
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.