Transformers yê teyên zi an jî hene, ew dîsa oil-immersed û dry-type. Cihazên wan di navbera windings, core, connecting components û oil contamination de bûn. Mînakî, winding insulation damage, open circuits, short circuits û inter-turn short circuits li ser connection points. Endamên xerîdar ên transformerdan binivîsandin ku severe overheating, excessive temperature rise, abnormal noise û three-phase imbalance.
Routine transformer maintenance mainly includes insulation testing (insulation resistance, dielectric absorption ratio, etc.), DC resistance measurement (for detecting winding-related faults), core lifting inspection, and no-load tests. Some enterprises also analyze the oil quality of oil-immersed transformers to ensure that its electrical insulation and thermal performance remain intact.
Below are several advanced transformer testing methods for reference.
1. ALL-Test Method
The core of the ALL-Test method is to use high-frequency, low-voltage signals—instead of high-voltage signals—to measure internal parameters such as DC resistance, impedance, winding inductance phase angle, and the current-to-frequency ratio (I/F) of winding-based equipment. This allows for accurate assessment of internal faults and their development stages. The advantages of this method are:
Enables rapid on-site fault diagnosis, helping determine whether further time-consuming and labor-intensive inspections—such as core lifting—are necessary.
High measurement accuracy. Since transformer winding DC resistance is typically very low, using low-voltage high-frequency signals avoids aggravating existing defects. With precision up to three decimal places, even minor inter-turn short circuits can be detected through noticeable changes in DC resistance (R)—something conventional DC resistance testing cannot achieve.
Facilitates condition-based monitoring. Each measurement can be recorded and stored. By conducting regular tests and plotting trend curves, changes in key parameters can be monitored over time, providing reliable data for early fault detection and predictive maintenance—supporting quantitative fault management in industrial facilities.
Comprehensive parameter analysis (R, Z, L, tgφ, I/F) offers a more complete, timely, and accurate description of internal transformer faults.
Basic Procedure for ALL-Test:
After disconnecting power to the transformer, ground the secondary (or primary) side. Then connect the instrument’s signal leads to the primary (or secondary) terminals (H1, H2, H3) one by one, measuring inter-phase parameters (R, Z, L, tgφ, I/F). By comparing results between phases or against historical data from the same phase at different times, the fault condition of the transformer can be determined.
As a reference, the following are recommended empirical evaluation criteria:
Resistance (R):
If R > 0.25 Ω, a phase-to-phase difference exceeding 5% indicates three-phase imbalance.
If R ≤ 0.2 Ω, use a 7.5% threshold for imbalance judgment.
Impedance (Z):
Inter-phase imbalance should not exceed 5%.
Failed transformers often show imbalance trending toward over 100%.
Inductance (L):
Imbalance must not exceed 5%.
Phase Angle Tangent (tgφ):
Difference between phases should be within one digit (e.g., 0.1 vs 0.2 is acceptable; 0.1 vs 0.3 is not).
Current-to-Frequency Ratio (I/F):
Inter-phase difference should not exceed two digits (e.g., 1.23 vs 1.25 is acceptable).
Based on field experience, during the progression from imbalance to failure, transformer test data undergoes dramatic changes. For critical transformers, it is recommended to perform ALL-Test measurements at least once per month.
Table 1 Experimental data of a good 2500kVA, 28800:4300 transformer, secondary side test
| H₁ - H₂ | H₁ - H₃ | H₂ - H₃ | |
| R | 0.103 | 0.100 | 0.096 |
| Z | 15 | 14 | 14 |
| L | 2 |
2 | 2 |
| tgφ | 75 | 75 | 75 |
| I/F | -48 | -48 | -49 |
Cizra 2 Ji bo transestar 500kVA, 13800:240V ku hewce dihat, agahîna rastîn ya pêncereya yekem
| H₁ - H₂ | H₁ - H₃ | H₂ - H₃ | |
| R | 116.1 | 88.20 | 48.50 |
| Z | 4972 | 1427 | 1406 |
| L | 7911 | 2267 | 2237 |
| tgφ | 23 |
21 | 20 |
| I/F | -33 | -29 |
-29 |
2. Rêbaza Pirastina Daîna
Di testkirin transformatoran di cihan de, pirastina daîna bixwekî têne metoda serkeftî û çep dibe li ser destkirina xabûnên navendî—wisa wirîna nederbasdar, şort sirkît, an şert bera. Di dema xebitandeyê de, ji ber guhertina çêdikaniyê an zêdekirina nehatiya îzolasyonê, daîna hîstî ya transformatorê dikare jêrve bike ji nîşana nameyê. Eger bi rastî pîvandin, daîna hîstîya transformatorê dikare wek îmîçar ênî peyva bêtir be bikar bîne li ser destkirina û pêşketina xabûnên navendî. Ji bo kerdestin vê, testker van transformator turns ratio (TTR) bikar e, ku hewce ye ku pîvandiya pîvan bêhevs dikin.
3. Testkirina Kalîteya Êliyê Transformator
Transformatoran êliyayî zêde hatine bikar kirin, û parçeya herî girînga pêşgotinê yekemîn û şopandina rêzik û şopandina êliyê. Şînên bêrazeên êliyê—wisa rengi tarî, dufta tirî, kamkirina nîgahî (berdewamîya viraz), an formasyona malî—herî hêsan dikarin bi nirxandina derbarî bêdin. Di navbera vê, analîza kantîta yên ênî yên êliyê—wisa viskozî, pointa flash, û nîrvana su—di navbera vê, pêşniyar bêne ji bo birayîna kompîl.
| Seriyal Nomer | Tişt | Cihaz Gerilim Sınıfı (kV) | Kalite İndeksi | İnceleme Yöntemi | |
| İşletmeye Alınmadan Önce Yağ | İşlemdeki Yağ | ||||
| 1 |
Su Çözünür Asit (pH Değeri) | >5.4 | ≥4.2 | GB7598 | |
| 2 | Asit Değeri (mgKOH/G) | ≤0.03 | ≤0.1 | GB7599 or GB264 | |
| 3 | Alev Noktası (Kapalı Kupa) | >140 (No. 10, 25 Yağ için) >135 (No. 45 Yağ için) |
1. Yeni yağ standardından 5 az olmayacak 2. Önceki ölçüm değerinden 5 az olmayacak |
GB261 | |
| 4 | Mekanik Karışıklık | Yok | Yok | Görsel İnceleme | |
| 5 | Serbest Karbon | Yok | Yok | Görsel İnceleme | |
Bijîher bi serenan vê tekmînan ji bo analîz û înspeksiyon bikişanîn di gas chromatography de. Wanemîne ku dîlîna transformasyonê veqetin an çewtî çikin, yekîkên sereke ya li vir rastîniyek û ew taybetmendîya ku hûn dikarin derketina nîşana dîlîn ji transformasyonê bigihînin paş bêtirîna elektrîk, analîz bikin navên û pirtûbên gazên dibistîn, û lê zimanîna çewtîyan rê bêtirînin. Li şertên normal, pirtûba gazan di dîlîn de zevî ye, tebihîda gazên berdestkirî yên ku yan têne wergerandin têne 0.001% derbas 0.1% di herêmên guhertin.
Lê wanemîne ku severîya çewtîyan transformasyonê piştguhîne, dîl û materyalên însulyasyon ên solid pirgazên mirîdîn di tasiyên termîk û electromagnetîk de têne wergerandin. Mînak, wanemîne ku hûrga çewtîya parçeyek be, materyalên însulyasyon pir mîqdara CO û CO₂ têne wergerandin; wanemîne ku dîl xwe çewtî be, pir mîqdara etilen û metan têne wergerandin. Bi karberdanê pirtûba gazan ên berdestkirî yên bilînîn, reyarên din dikarin bikar bînin: pirtûba gazan dijîrî 0.1% belîşanê, 0.1% derbas 0.5% belîşanê çewtîya hêviyê, jorî 0.5% belîşanê çewtîya severî.
Gazan ên seren di çewtîyan ên elektrîkî yên transformasyonan de H₂ (hidrogen) û C₂H₂ (asetilin), ke bi tenê çap û sparkan têne wergerandin. Reyarên din dikarin bikar bînin ji bo belîşan: pirtûba H₂ <0.01% belîşan, 0.01–0.02% hewceye kiribî, û >0.02% belîşanê çewtî; C₂H₂ <0.0005% belîşan, û >0.001% belîşanê çewtî.
Paş wanemîne ku transformasyon berî, pirtûba H₂ (hidrogen) têne zi dike, wanemîne ku hidrogen bi karberdanê elektroliz di tîrê de têne wergerandin. Ev danên gazan dikarin biguherînin ji bo belîşanê rêbazê transformasyonê.