Optimizing Temperature Rise and Performance for 2000A Cabinets: Design & Testing Solutions

Garca
Garca
Field: Design & Maintenance
Congo

Regarding the temperature rise solution for 2000A, 800mm wide cabinets: reduce self-heating, implement rational ventilation design; 2000A solid-sealed pole column circuit breakers can also use heat sinks; use two 80×10mm busbars made of high-quality busbar material; increase contact pressure and bolt tightening torque.

For 650mm width with lightning impulse withstand voltage: do not assume that 17.5kV 95kV BIL, being a higher voltage level, necessarily requires larger dimensions and wider cabinets. Since 17.5kV is not a standard domestic voltage grade, it is not necessary to follow domestic technical standards strictly—such as the requirement that heat-shrink tubing cannot reduce clearance distances. The power frequency withstand voltage for 17.5kV is 36kV, and international creepage distance requirements are relatively lower, allowing creepage as low as 16mm/kV.

There is no need to worry about operational issues, as overseas switchgear installation requirements, operating environments, and maintenance management are generally stricter than domestic practices. When dealing with international customers, one must be practical and not focus solely on appearance. Instead, focus on meticulously manufacturing high-quality products, ensuring technical parameters are solidly guaranteed. Temperature rise and impulse withstand voltage must be verified through testing, not merely based on experience. New or modified products should not be released without proper testing, relying solely on trial reports that have no proven value.

For the short-circuit closing test of earthing switches, the standard requires internal switchgear cabinet testing. Key factors include closing speed, contact pressure, and contact material. Installation of earthing switches is rarely studied, yet the installation orientation and copper busbar routing significantly affect the closing test performance. It is essential to fully understand the dynamic and thermal stability and the short-circuit closing process to select high-quality switches. Regarding resistance distribution, appropriately increasing the shorting resistor and reducing contact resistance can lower the risk of overheating and welding. The routing of connecting copper busbars determines closing speed and whether electromagnetic forces assist or hinder closure.

For arc-resistant switchgear design, it is crucial to understand the arc release process, ensuring smooth pressure relief channels and easily opened pressure relief covers. Research the weak points of shock wave overpressure on doors, covers, and enclosures, study the thermal effects of sustained arc burning, improve the cabinet's fire resistance, and ensure rapid flame extinction.

High-quality KYN28 switchgear has a clear market positioning, with performance significantly superior to ordinary domestic metal-clad switchgear. Its technical depth, meticulous design, premium materials, comprehensive manufacturing processes, careful assembly, thorough and standardized testing, and focus on serving mid-to-high-end customers contribute to elevating industry standards.

Give a tip and encourage the author!
Recommended
PT Fuse Slow Blow: Causes, Detection & Prevention
PT Fuse Slow Blow: Causes, Detection & Prevention
I. Fuse Structure and Root Cause AnalysisSlow Fuse Blowing:From the design principle of fuses, when a large fault current passes through the fuse element, due to the metal effect (certain refractory metals become fusible under specific alloy conditions), the fuse first melts at the soldered tin ball. The arc then rapidly vaporizes the entire fuse element. The resulting arc is quickly extinguished by quartz sand.However, due to harsh operating environments, the fuse element may age under the comb
Edwiin
10/24/2025
Why Fuses Blow: Overload, Short Circuit & Surge Causes
Why Fuses Blow: Overload, Short Circuit & Surge Causes
Common Causes of Fuse BlowingCommon reasons for fuse blowing include voltage fluctuations, short circuits, lightning strikes during storms, and current overloads. These conditions can easily cause the fuse element to melt.A fuse is an electrical device that interrupts the circuit by melting its fusible element due to heat generated when current exceeds a specified value. It operates on the principle that, after an overcurrent persists for a certain period, the heat produced by the current melts
Echo
10/24/2025
Fuse Maintenance & Replacement: Safety and Best Practices
Fuse Maintenance & Replacement: Safety and Best Practices
1. Fuse MaintenanceFuses in service should be regularly inspected. The inspection includes the following items: Load current should be compatible with the rated current of the fuse element. For fuses equipped with a fuse blown indicator, check whether the indicator has actuated. Check the conductors, connection points, and the fuse itself for overheating; ensure connections are tight and making good contact. Inspect the fuse exterior for cracks, contamination, or signs of arcing/discharge. Liste
James
10/24/2025
Maintenance and Repair Items for 10kV High-Voltage Switchgear
Maintenance and Repair Items for 10kV High-Voltage Switchgear
I. Routine Maintenance and Inspection(1) Visual Inspection of Switchgear Enclosure No deformation or physical damage to the enclosure. Protective paint coating shows no severe rust, peeling, or flaking. Cabinet is securely installed, clean on the surface, and free of foreign objects. Nameplates and identification labels are neatly affixed and not falling off.(2) Check of Switchgear Operating Parameters Instruments and meters indicate normal values (comparable to typical operating data, with no s