What is Transformer Water Content Test?

Encyclopedia
Field: Encyclopedia
0
China

What is Transformer Water Content Test?

Water Content Test Definition

The water content test in insulating oil is defined as a process using Karl Fischer Titration to measure water levels.

17a5077e8ab5adff5c4fbd2e599af959.jpeg

 Karl Fischer Principle

To measure water content in insulating oil, we use Karl Fischer Titration. In this method, water (H2O) reacts chemically with iodine (I2), sulfur dioxide (SO2), an organic base (C5H5C), and alcohol (CH3OH) in an organic solvent.

The sample is mixed with sulfur dioxide, iodide ions, and an organic base/alcohol. Iodide ions are produced by electrolysis and participate in the reactions. As long as the reaction continues, no free iodide ions remain in the solution.

ef3b26676339f56a848ad8448b52b93c.jpeg

 The iodide ions produced by electrolysis are consumed as long as water molecules are present. When there is no more water to react, the Karl Fischer reactions stop. Two platinum electrodes in the solution detect this endpoint. The presence of iodide ions after the reaction changes the voltage-current ratio, indicating the reaction’s end.

According to Faraday law of electrolysis, the amount of iodine reacting is proportional to the electricity consumed for electrolysis during the Karl Fischer reactions. By measuring the electricity consumed until the reaction ends, we can calculate the actual mass of iodine involved. From the reaction equation, we know that one mole of iodine reacts with one mole of water. Therefore, 127 grams of iodine will react with 18 grams of water. This allows us to determine the exact amount of water in the insulating oil sample.

Electrolysis Role

Electrolysis produces iodide ions, which react with water in the solution.

Detection of Reaction Endpoint

Platinum electrodes detect the endpoint of the Karl Fischer reaction when no more water is present.

Calculation of Water Content

Using the electricity consumed during the reaction, the exact quantity of water in the insulating oil is calculated.

Give a tip and encourage the author!
Recommended
Strange Devices on Transmission Lines: 5 Little-Known Practical Functions(1)
1 Aviation Warning SpheresAviation warning spheres, also known as reflective safety spheres, are used on overhead transmission lines near airports, especially on extra-high-voltage (above 220kV) lines and river-crossing transmission lines. Highly visible aviation marker spheres (aviation warning spheres) must be installed along the lines to provide warning signals.The aviation marker sphere (aviation warning sphere) has a diameter of ф=600mm. The sphere can be manufactured in various bright colo
Leon
09/04/2025
Transmission Line
In transmission lines, a "π" connection involves breaking the original line from Substation A to Substation B and inserting Substation C, forming a "π" configuration. After the "π" connection, the original single line is divided into two independent transmission lines. Following the "π" connection, Substations B and C may both be powered by Substation A (in this case, Substation C receives power via a feeder from Substation B's busbar, or possibly from another voltage point within Substation B);
Encyclopedia
09/04/2025
What are the principles of forced re-energization of transmission lines?
Principles of Forced Re-energization of Transmission LinesRegulations for Forced Re-energization of Transmission Lines Correctly select the forced re-energization end of the line. If necessary, change the connection configuration before forced re-energization, taking into account the reduction of short-circuit capacity and its impact on grid stability. There must be a transformer with its neutral point directly grounded on the busbar at the forced re-energization end. Pay attention to the impact
Edwiin
09/04/2025
Analysis of Accident Handling in Transmission Lines
Analysis of Transmission Line Fault HandlingAs a fundamental component of the power grid, transmission lines are widely distributed and numerous, often exposed to diverse geographical and climatic conditions, making them highly susceptible to faults. Common causes include overvoltage, pollution flashover, insulation damage, tree encroachment, and external damage. Line tripping is one of the most frequent faults in power plant and substation operations, with fault types including single-phase-to-
Leon
09/04/2025
Seed Inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.